Kont.m Darw DILM7-38 2DI 1-0-A (DIL-SWD-32-002)

Eaton · Control & Automation · I/O Modules · Ireland · eaton.com
Part Number
DIL-SWD-32-002  ·  HS 8538.90
Kont.m Darw DILM7-38 2DI 1-0-A (DIL-SWD-32-002)

Technical Specifications

Manufacturer part number (MPN)DIL-SWD-32-002
EAN / GTIN4015081168316
Sales unitpcs
Package quantity5 pcs
Eaton catalogue number118561
Depth72 mm
Height38 mm
Width45 mm
Weight0.037 kg
CertificationsUL 508; IEC/EN 60947; UL; EN 50178; CE; CSA File No.: 2324643; CSA Class No.: 3211-07; UL File No.: E29184; IEC/EN 61131-2; UL Category Control No.: NKCR; CSA-C22.2 No. 14-05; IEC/EN 60947-4-1; CSA
Constant acceleration1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max0.3 m
Mounting positionAs DILM7 to DILM38
Shock resistance15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Ambient operating temperature - max60 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-30 °C
Environmental conditionsCondensation: prevent with appropriate measures
Relative humidity5 - 95 % (non-condensing, IEC/EN 60068-2-30)
AddressingAddress set automatically
Connection to SmartWire-DTYes
Connection typeSWD: Plug, 8-pole; Push in terminals, Auxiliary contact; External device plug SWD4-8SF2-5, SmartWire-DT
LED indicatorStatus indication of SmartWire-DT network: Green and orange LED
StationSmartWire-DT slave, SmartWire-DT network
Number of auxiliary contacts2
Static heat dissipation, non-current-dependent Pvs0.8 W
Rated operational voltage15 V DC (auxiliary contact)
Supply voltage at DC - max15 VDC
Supply voltage at DC - min15 VDC
Air discharge8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3; 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
Contact discharge4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008); 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008); 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference classClass A (EN 55011)
Electric connection typeSpring clamp connection
FeaturesFieldbus connection over separate bus coupler possible; Fieldbus connection over separate bus coupler possible
Fitted withOwn supply
FunctionsDisplay of Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position; For connecting the contactors to SmartWire-DT; Contactor actuation
Operating modeAddress allocation via Rotary switch; Control mode
Cable length≤ 2.8 m, Connection auxiliary contact
Current consumption40 mA, SmartWire-DT network
Degree of protectionIP20
Input current at signal 13 mA
Number of inputs (digital)2
Number of outputs (digital)1
Output current0.5 A
Overvoltage categoryII
Pollution degree2
Product categorySmartWire-DT slave
ProtocolOther bus systems
TypeSWD contactor modules
Voltage typeDC
Pick-up current125 mA (for DILM 7-9); 188 mA (for DILM 12-15); 500 mA (for DILM 17-38)
Sealing current188 mA, SmartWire-DT network for DILM 12-15; 21 mA, SmartWire-DT network for DILM 17-38; 125 mA, SmartWire-DT network for DILM 7-9
Power consumption3 W for DILM 7-9 (Pick-up power); 4.5 W for DILM 12-15 (Sealing power); 12 W for DILM 17-38 (Pick-up power); 3 W for DILM 7-9 (Sealing power); 4.5 W for DILM 12-15 (Pick-up power); 0.5 W for DILM 17-38 (Sealing power)
Explosion safety category for dustNone
Explosion safety category for gasNone
Potential isolationConnection auxiliary contact: no
Terminal capacity0.2 - 1.5 mm² (24 - 16 AWG), solid; 0.25 - 1.5 mm², flexible with ferrule
Certified for UL hazardous location division 1No
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)No
Certified for UL hazardous location group B (hydrogen)No
Certified for UL hazardous location group C (ethylene)No
Certified for UL hazardous location group D (propane)No
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class INo
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC15 V
Number of digital inputs2
Number of digital outputs1
Digital inputs configurableNo
Digital outputs configurableNo
Permitted voltage at input15 V
Type of voltage (input voltage)DC
Permitted voltage at output20.4–28.8 V
Type of output voltageDC
Short-circuit protection, outputs availableNo
Number of HW-interfaces other1
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsYes
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Type of electric connectionSpring clamp connection
Time delay at signal change10–84 ms
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingNo
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Country of originGermany

Properties

MOQ1

Cross-References