| Manufacturer part number (MPN) | XC-204-C21-001 |
| EAN / GTIN | 4015081997633 |
| Sales unit | pcs |
| Package quantity | 3 pcs |
| Eaton catalogue number | 199975 |
| Depth | 104.2 mm |
| Height | 29.3 mm |
| Width | 80.3 mm |
| Weight | 0.11 kg |
| Certifications | UL listed; EN 61131; EAC; UL File No.: E205091; CE; cULus Listed |
| Mounting position | Vertical (on horizontal top-hat rail) |
| Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts |
| Vibration resistance | 5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g |
| Air pressure | 795 - 1080 hPa (operation) |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 70 °C |
| Ambient operating temperature - min | -20 °C |
| Ambient storage temperature - min | -25 °C |
| Relative humidity | < 95 % (non-condensing) |
| Interfaces | 2 x ETH; CAN; DIO; XN300 |
| Protocol | CAN; EtherNet/IP; MODBUS; Other bus systems; TCP/IP |
| Heat dissipation details | The max. heat dissipation is specified as the maximum power produced inside the device's housing. |
| Static heat dissipation, non-current-dependent Pvs | 6.3 W |
| Emitted interference | 40 dB (at 30 - 230 MHz, Class A, radiated, high frequency); 47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency) |
| Fitted with | XSOFT-CODESYS 3 |
| Functions | Additional program memory possible; Redundancy |
| Connection type | Push-in spring-cage terminal, Connection design in TOP direction |
| Degree of protection | IP20 |
| Model | Modular |
| Mounting method | Rail mounting possible |
| Overvoltage category | II |
| Pollution degree | 2 |
| Potential isolation | Between Digital inputs: no; Between Digital outputs: no |
| Voltage type | DC |
| Delay time | 200 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal; 200 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal |
| Input current | ≤ 1.1 mA (Digital inputs, low level); ≥ 2.0 mA (Digital inputs, high level) |
| Number of channels | 2 |
| Number of inputs (analog) | 0 |
| Number of inputs (digital) | 2 |
| Number of outputs (analog) | 0 |
| Number of outputs (digital) | 2 |
| Number of relay outputs | 0 |
| Rated operational current (Ie) | 2.4 A (supply input) |
| Utilization factor | 100 % (Ʃ IAmax = 2A) |
| Input voltage | 0 - 5 V (Digital inputs, low level); 24 V DC (Digital inputs); 15 - 30 V (Digital inputs, high level) |
| Supply voltage at DC - max | 30 VDC |
| Supply voltage at DC - min | 19.2 VDC |
| Voltage dips | 20 ms; 10 ms |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Memory capacity | 512,000 kByte |
| Terminal capacity | 0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
| Terminal capacity (AWG) | 24 - 16 |
| Terminal capacity (flexible with ferrule) | 0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight); 0.25 - 1.5 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
| Terminal capacity (flexible) | 0.2 - 1.5 mm², H 07V-K |
| Terminal capacity (solid) | 0.2 - 1.5 mm², H07V-U |
| With display | No |
| Suitable for safety functions | No |
| Number of digital inputs | 2 |
| Number of digital outputs | 2 |
| Type of memory | RAM |
| Memory size | 512000 kByte |
| Processing time (1K, binary operation) | 0.00125 ms |
| Supporting protocol for LON | No |
| Number of HW-interfaces industrial Ethernet | 2 |
| Number of HW-interfaces USB | 1 |
| Number of HW-interfaces other | 2 |
| With optical interface | No |
| Additional program memory possible | Yes |
| Supporting protocol for TCP/IP | Yes |
| Supporting protocol for ASI | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | Yes |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for other bus systems | Yes |
| Redundancy | Yes |
| Suitable for rail mounting | Yes |
| System accessory | Yes |
| Appendant operation agent (Ex ia) | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for INTERBUS-Safety | No |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Wall mounting/direct mounting | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| IO link master | No |
| Max. number of time switches | 1000 |
| Performance level according to EN ISO 13849-1 | None |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for EtherNet/IP | Yes |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supply voltage DC | 19.2–30 V |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| Long-Term Evolution (LTE) | No |
| SIL according to IEC 61508 | None |
| Supporting protocol for IEC 61850 Ethernet | No |
| Supporting protocol for DNP3 | No |
| Supporting protocol for IEC 60870 | No |
| Mobile communications standard 4G (LTE) | No |
| Supporting protocol for EtherCAT | No |
| Certified for UL hazardous location class I | No |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Certified for UL hazardous location division 1 | No |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | No |
| Certified for UL hazardous location group B (hydrogen) | No |
| Certified for UL hazardous location group C (ethylene) | No |
| Certified for UL hazardous location group D (propane) | No |
| Certified for UL hazardous location group E (metal dusts) | No |
| Country of origin | Germany |