| Manufacturer part number (MPN) | EASY-E4-AC-12RC1 EAN / GTIN: 4015081939442 Sales unit: pcs Eaton catalogue number: 197215 Depth: 58 mm Height: 90 mm Width: 72 mm Weight: 0.25 kg Compliances: Eaton supports the product until its end of life Catalog Notes: Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible Drop and topple: 50 mm Drop height, Drop to IEC/EN 60068-2-31 Height of fall (IEC/EN 60068-2-32) - max: 0.3 m Mounting position: Horizontal; Vertical Shock resistance: 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts Vibration resistance: According to IEC/EN 60068-2-6; 57 - 150 Hz, 2 g constant acceleration; 10 - 57 Hz, 0.15 mm constant amplitude Cable length: 100 m (max. permissible per input I7 to I8), digital inputs 115/230 V AC; 40 m (max. permissible per input I1 to I6), digital inputs 115/230 V AC Cable type: Ethernet: CAT5 Air pressure: 795 - 1080 hPa (operation) Ambient operating temperature - max: 55 °C Ambient storage temperature - max: 70 °C Ambient operating temperature - min: -25 °C Ambient storage temperature - min: -40 °C Environmental conditions: Condensation: prevent with appropriate measures; Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 Relative humidity: 5 - 95 % (IEC 60068-2-30 |
| IEC 60068-2-78) Connection type | Screw terminal; Ethernet: RJ45 plug, 8-pole Data transfer rate: 10/100 MBit/s Equipment heat dissipation, current-dependent Pvid: 4 W Static heat dissipation, non-current-dependent Pvs: 4 W Conventional thermal current Ith of auxiliary contacts (1-pole, open): 8 A Inrush current: 12.5 A (for 6 ms) Power consumption: 4 W Power loss: 10 W Rated breaking capacity: 300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h); 200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) Rated insulation voltage (Ui): 240 V Rated operational voltage: Max. 300 V DC; 100/110/115/120/230/240 AC (-15 %/+10 %); 85 - 264 V AC; Max. 300 V AC; 110/120 V DC (power supply); 240 V AC Supply frequency: 50/60 Hz (± 5%) Supply voltage at AC 50 Hz - max: 264 VAC Supply voltage at AC 50 Hz - min: 85 VAC Supply voltage at DC - max: 264 VDC Supply voltage at DC - min: 85 VDC Uninterrupted current: 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA); 8 A AC, at 240 V AC (UL/CSA); 8 A DC, at 24 V DC (UL/CSA); 1 A DC, at R 300 (UL/CSA) Air discharge: 8 kV Burst impulse: 2 kV, Signal cable; According to IEC/EN 61000-4-4; 2 kV |
| Supply cable Contact discharge | 6 kV Electromagnetic fields: 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3); 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3); 10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3) Immunity to line-conducted interference: 10 V (according to IEC/EN 61000-4-6) Radio interference class: Class B (EN 61000-6-3) Surge rating: 1 kV, Supply cables, symmetrical, power pulses (Surge), EMC; According to IEC/EN 61000-4-5, power pulses (Surge), EMC; 2 kV, Supply cables, asymmetrical, power pulses (Surge) |
| EMC Voltage dips | 10 ms Features: Networkable (Ethernet); Expandable; Display indication of 6 lines x 16 characters Fitted with: Relay output; Timer; Keypad; Display; Real time clock Indication: LCD-display used as status indication of digital inputs 115/230 V AC Degree of protection: IP20 Display temperature - max: 55 °C Display temperature - min: 0 °C Display type: Monochrome Input frequency: 50/60 Hz (digital inputs, at 115/230 V AC); 50/60 Hz (digital inputs, at 24 V DC) Insulation resistance: According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 Lifespan, mechanical: 1,000,000 Operations Mounting method: Screw fixing using fixing brackets ZB4-101-GF1 (accessories); Rail mounting possible; Top-hat rail fixing (according to IEC/EN 60715, 35 mm); Wall mounting/direct mounting; Front build in possible Overvoltage category: III Pollution degree: 2 Product category: Control relays easyE4 Protection: B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay Protocol: TCP/IP; MODBUS Rated impulse withstand voltage (Uimp): Relay outputs: 6 kV (contact-coil) Residual ripple: ≤ 5 % Resolution: 1 min (Range H:M) 1 s (Range M:S) 5 ms (Range S) Software: EASYSOFT-SWLIC/easySoft Switching frequency: 10 Hz, Relay outputs; 2 Hz, Resistive load/lamp load, Relay outputs; 0.5 Hz, Inductive load |
| Relay outputs Type | easyE4 base device Used with: easyE4 Utilization category: B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC; R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC Voltage type: AC Accuracy: ± 1 %, Repetition accuracy of timing relays (of values); ± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year) Input current: 2 x 4 mA (I7 - I8, at 115 V AC, 60 Hz, at signal 1); 6 x 0.25 mA (I1 - I6, at 115 V AC, 60 Hz, at signal 1); 2 x 6 mA (I7 - I8, at 230 V AC, 50 Hz, at signal 1); 6 x 0.5 mA (I1 - I6, at 230 V AC, 50 Hz, at signal 1) Input voltage: Condition 0: 0 - 40 V AC, digital inputs 115/230 V AC); Condition 1: 79 - 264 V AC, digital inputs, 115/230 V AC) Making/breaking capacity: 3600/360 VA (AC, at B 300); 28/28 VA (DC, at R 300) Number of inputs (analogue): 0 Number of inputs (digital): 8 Number of outputs (analogue): 0 Number of outputs (digital): 4 Output: Relay outputs in groups of 1; 4 Relay Outputs; > 500 mA (Relay outputs Recommended for load: 12 V AC/DC); Voltage; Current Parallel switching: Not permitted Explosion safety category for dust: None Explosion safety category for gas: None Protection against polarity reversal: Yes, for supply voltage (Siemens MPI optional) Safe isolation: 300 V AC, Between two contacts, According to EN 50178; 300 V AC, Between coil and contact, According to EN 50178 Short-circuit protection: ≥ 1A (T), Fuse |
| Power supply Screwdriver size | 3.5 x 0.8 mm |
| Terminal screw Terminal capacity | 0.2 - 4 mm² (AWG 22 - 12), solid; 0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule Tightening torque: 0.6 Nm, Screw terminals Certified for UL hazardous location division 1: No Certified for UL hazardous location division 2: Yes Certified for UL hazardous location group A (acetylene): Yes Certified for UL hazardous location group B (hydrogen): Yes Certified for UL hazardous location group C (ethylene): Yes Certified for UL hazardous location group D (propane): Yes Certified for UL hazardous location group E (metal dusts): No Certified for UL hazardous location class I: Yes Certified for UL hazardous location class II: No Certified for UL hazardous location class III: No Supporting protocol for EtherCAT: No Supply voltage AC 50 Hz: 85–264 V Supply voltage AC 60 Hz: 85–264 V Supply voltage DC: 85–264 V Switching current: 8 A Number of digital inputs: 8 Number of digital outputs: 4 With relay output: Yes Number of HW-interfaces industrial Ethernet: 1 Number of HW-interfaces other: 1 With optical interface: No Supporting protocol for TCP/IP: Yes Supporting protocol for PROFIBUS: No Supporting protocol for CAN: No Supporting protocol for INTERBUS: No Supporting protocol for ASI: No Supporting protocol for KNX: No Supporting protocol for Modbus: Yes Supporting protocol for Data-Highway: No Supporting protocol for DeviceNet: No Supporting protocol for SUCONET: No Supporting protocol for LON: No Supporting protocol for PROFINET IO: No Supporting protocol for PROFINET CBA: No Supporting protocol for SERCOS: No Supporting protocol for Foundation Fieldbus: No Supporting protocol for EtherNet/IP: No Supporting protocol for AS-Interface Safety at Work: No Supporting protocol for DeviceNet Safety: No Supporting protocol for INTERBUS-Safety: No Supporting protocol for PROFIsafe: No Supporting protocol for SafetyBUS p: No Supporting protocol for other bus systems: No Radio standard Bluetooth: No Radio standard WLAN 802.11: No Radio standard GPRS: No Radio standard GSM: No Mobile communications standard 3G (UMTS): No IO link master: No Redundancy: No With display: Yes Basic device: Yes Expandable: Yes Expansion device: No With time switch clock: Yes Suitable for rail mounting: Yes Wall mounting/direct mounting: Yes Front built-in possible: Yes Rack-assembly possible: No Suitable for safety functions: No SIL according to IEC 61508: None Performance level according to EN ISO 13849-1: None Appendant operation agent (Ex ia): No Country of origin: Estonia |