cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton IZMX40H3-V16F-1

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
IZMX40H3-V16F-1  ·  HS 8536.20
Eaton IZMX40H3-V16F-1

Technical Specifications

Manufacturer part number (MPN)IZMX40H3-V16F-1
EAN / GTIN4015081794577
Sales unitpcs
Eaton catalogue number183721
Depth584 mm
Height597 mm
Width521 mm
Weight45 kg
CompliancesIEC; IEC/EN 60947; RoHS conform
Amperage Rating1600 A
FeaturesComplete device with protection unit; Motor drive optional
Fitted withSwitched-off indicator
FrameIZMX40
Number of polesThree-pole
Release systemElectronic release
TypeAir circuit breakers/switch-disconnector Open circuit breaker
Used withAir circuit breakers/switch-disconnector; Open circuit breaker
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-20 °C
Ambient operating temperature details-20 °C - 70 °C
Ambient storage temperature - min-20 °C
Equipment heat dissipation, current-dependent100 W
Heat dissipation at rated current with fixed mounting100 W
Rated operational current for specified heat dissipation (In)1600 A
Actuator typePush button
Adjustment range short-term delayed short-circuit release - max16000 A
Adjustment range short-term delayed short-circuit release - min960 A
Adjustment range undelayed short-circuit release - max24000 A
Adjustment range undelayed short-circuit release - min3200 A
Closing delay via spring release35 ms
Direction of incoming supplyAs required
Electrical connection type of main circuitRail connection
Lifespan, electrical10000 operations (switching capacity); 20000 operations (switching cycles ON/OFF, with maintenance)
Number of standard mechanical operations per hour - max60
Operating sequence up to 690 V, 50/60 Hz (IEC/EN 60947)85 kA
Overload release current setting - max1600 A
Overload release current setting - min640 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp)12 kV AC
Rated insulation voltage (Ui)1000 V
Rated operating voltage (Ue) - max690 V
Rated operating voltage (Ue) - min240 V
Rated short-circuit breaking capacity at 400 V, 50 Hz105 kA
Rated short-circuit making capacity up to 440 V, 50/60 Hz231 kA
Rated short-circuit making capacity up to 690 V, 50/60 Hz166 kA
Rated short-time withstand current (t = 1 s)85 kA
Rated short-time withstand current at 50/60 Hz (t = 3 s)66 kA
Rated uninterrupted current (Iu)1600 A
Rated uninterrupted current (Iu) at 50°C1600 A
Rated uninterrupted current (Iu) at 60°C1600 A
Rated uninterrupted current (Iu) at 70°C1600 A
Short-circuit release delayed setting - max16000 A
Short-circuit release delayed setting - min1200 A
Short-circuit release non-delayed setting1.5 - 10 x Ir
Short-circuit release non-delayed setting - max24000 A
Utilization categoryB
Voltage rating at AC690 V AC
Degree of protectionIP55 with protective cover; IP31; IP31 with door seals
Device constructionBuilt-in device fixed built-in technique
Lifespan, mechanical12500 switching cycles (ON/OFF); 25000 operations (switching capacity, with maintenance)
Mounting MethodFixed
Number of auxiliary contacts (change-over contacts)2
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitBack side
ProtectionSelective operation
Weight of fixed mounting version (3-pole)43 kg
Terminal capacity (copper bar)80 mm x 10 mm (1x) for fixed mounting (black)
Rated permanent current Iu1600 A
With integrated under voltage releaseNo
Overload release current setting400–1000 A
Number of auxiliary contacts as change-over contact2
Rated voltage690 V
Power loss100 W
Motor drive integratedNo
Type of electrical connection of main circuitRail connection
Type of control elementPush button
With switched-off indicatorYes
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz105 kA
Adjustment range short-term delayed short-circuit release2400–16000 A
Adjustment range undelayed short-circuit release3200–24000 A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Country of originUnited States

Properties

MOQ1

Cross-References