Eaton PFR-W-35 Residual-Current Transformer for PFR-5, 35 mm Opening

Eaton · Electrical Components · Current Transformers · Ireland · eaton.com
Part Number
PFR-W-35  ·  HS 8536.41
Eaton PFR-W-35 Residual-Current Transformer for PFR-5, 35 mm Opening

Eaton PFR-W-35 is a summation residual-current transformer with a 35 mm opening diameter, intended for use with the PFR-5 earth-fault relay on NZM1/2/3/4 frames. The unit is rated for 690 V AC service and ships with a DIN-rail mounting clip. Delay adjustment is not provided at the transformer, and the PFR combination is not UL/CSA approved. Country of origin is Spain.

Technical Specifications

Manufacturer part number (MPN)PFR-W-35
EAN / GTIN4015082856007
Sales unitpcs
Eaton catalogue number285600
Depth115 mm
Height45 mm
Width105 mm
Weight0.143 kg
CompliancesRoHS conform
CertificationsIEC
FrameNZM1/2/3/4
Special featuresIn combination with PFR residual current relay not UL/CSA approved
TypeEarth-fault releases, transformer
Voltage rating690 V AC 50/60 Hz
Voltage rating of relay contact690 V (50/60 Hz)
Mounting MethodIncl. fixing clip for DIN-rail mounting
Transformer opening diameter35 mm
Delay adjustableNo
Country of originSpain