| Manufacturer part number (MPN) | MSC-D-2,5-M7(230V50HZ) |
| EAN / GTIN | 4015082831424 |
| Sales unit | pcs |
| Eaton catalogue number | 283142 |
| Depth | 95 mm |
| Height | 180 mm |
| Width | 45 mm |
| Weight | 0.584 kg |
| Certifications | VDE 0660; CE; CSA Class No.: 3211-24; IEC/EN 60947-4-1; UL Category Control No.: NLRV; UL File No.: E36332; CSA File No.: 012528; CSA-C22.2 No. 60947-4-1-14; CSA; UL; UL 60947-4-1 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -25 °C |
| Equipment heat dissipation, current-dependent Pvid | 5.7 W |
| Heat dissipation per pole, current-dependent Pvid | 1.9 W |
| Rated operational current for specified heat dissipation (In) | 2.5 A |
| Static heat dissipation, non-current-dependent Pvs | 1.4 W |
| Rated operational current (Ie) | 1.9 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 2.5 A |
| Rated operational power at AC-3, 220/230 V, 50 Hz | 0.37 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 0.75 kW |
| Rated operational voltage | 230 - 415 V AC |
| Switching capacity (auxiliary contacts, general use) | 1 A, 250 V DC, (UL/CSA); 15 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA); P300, DC operated (UL/CSA) |
| Fitted with | Short-circuit release |
| Functions | Temperature compensated overload protection |
| Class | CLASS 10 A |
| Connection | Screw terminals |
| Connection to SmartWire-DT | No |
| Coordination type | 2 |
| Degree of protection | IP20; NEMA Other |
| Model | IEC/UL starter |
| Mounting method | DIN rail |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Overload release current setting - max | 2.5 A |
| Overload release current setting - min | 1.6 A |
| Overvoltage category | III |
| Pollution degree | 3 |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Suitable for | Also motors with efficiency class IE3 |
| Type | Starter with Bi-Metal release |
| Voltage type | AC |
| Power consumption, sealing, 50 Hz | 1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 230 V |
| Short-circuit release (Irm) - max | 38.8 A |
| With transformer | No |
| Power consumption | 1.4 W |
| Rated operation power at AC-3, 400 V | 0.75 kW |
| Number of auxiliary contacts as normally open contact | 1 |
| Suitable for emergency stop | No |
| Rated operation current Ie | 1.9 A |
| Overload release current setting | 1.6–2.5 A |
| Supporting protocol for LON | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for ASI | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for other bus systems | No |
| External reset possible | No |
| Suitable for rail mounting | Yes |
| Rated control supply voltage AC 50 Hz | 230 V |
| Supporting protocol for SERCOS | No |
| Supporting protocol for INTERBUS-Safety | No |
| Release class | CLASS 10 |
| With short-circuit release | Yes |
| With fuse | No |
| Type of electrical connection of main circuit | Screw connection |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Voltage type for actuating | AC |
| Type of motor starter | Direct online starter (DOL) |
| Rated operation power at AC-3, 230 V, 3-phase | 0.37 kW |
| Rated operation current at AC-3, 400 V | 2.5 A |
| Ambient temperature, upper operating limit | 60 °C |
| Temperature compensated overload protection | Yes |
| Rated conditional short-circuit current, type 2, 400 V | 50000 A |
| Rated conditional short-circuit current, type 2, 230 V | 50000 A |
| Coordination class according to IEC 60947-4-3 | Class 2 |
| Country of origin | Germany |