Eaton NZMB1-M80-SVE

Eaton · Electrical Components · Motor Protection Circuit Breakers · Ireland · eaton.com
Part Number
NZMB1-M80-SVE  ·  HS 8536.20
Eaton NZMB1-M80-SVE

Technical Specifications

Manufacturer part number (MPN)NZMB1-M80-SVE
EAN / GTIN4015081122622
Sales unitpcs
Eaton catalogue number112722
Depth90 mm
Height201 mm
Width95 mm
Weight1.201 kg
CompliancesRoHS conform
CertificationsIEC; IEC/EN 60947
FunctionsPhase failure sensitive; Motor protection
Accessories requiredNZM1-XSVS
Amperage Rating80 A
ApplicationUse in unearthed supply systems at 440 V
Circuit breaker frame typeNZM1
Fitted withThermal protection
Number of polesThree-pole
Release systemThermomagnetic release
TypeCircuit breaker
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent20.83 W
Rated operational current for specified heat dissipation (In)80 A
Direction of incoming supplyAs required
Electrical connection type of main circuitOther
Handle typeRocker lever
Instantaneous current setting (Ii) - max1120 A
Instantaneous current setting (Ii) - min640 A
Isolation500 V AC (between auxiliary contacts and main contacts); 300 V AC (between the auxiliary contacts)
Lifespan, electrical7500 operations at 400 V AC-1; 7500 operations at 415 V AC-1
Number of operations per hour - max120
Overload current setting (Ir) - max80 A
Overload current setting (Ir) - min63 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts6000 V
Rated insulation voltage (Ui)690 V
Rated operating power at AC-3
230 V22 kW
Rated operating power at AC-3
400 V45 kW
Rated operational current68 A (400 V AC-3)
Rated short-circuit making capacity Icm at 240 V
50/60 Hz63 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz53 kA
Rated short-circuit making capacity Icm at 440 V
Short-circuit release non-delayed setting - max1120 A
Short-circuit release non-delayed setting - min640 A
Short-circuit total breaktime< 10 ms
Utilization categoryA (IEC/EN 60947-2)
Voltage rating440 V - 440 V
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Degree of protectionIP20; IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front sideIP66 (with door coupling rotary handle); IP40 (with insulating surround)
Degree of protection (terminations)IP10 (tunnel terminal); IP00 (terminations, phase insulator and strip terminal)
Lifespan, mechanical20000 operations
Mounting MethodPlug-in unit; Built-in device plug-in technique
Protection against direct contactFinger and back-of-hand proof to VDE 0106 part 100
Shock resistance20 g (half-sinusoidal shock 20 ms)
Switch off techniqueThermomagnetic
Optional terminalsConnection on rear. Screw terminal. Tunnel terminal
Standard terminalsBox terminal
Terminal capacity (aluminum solid conductor/cable)10 mm² - 16 mm² (2x) direct at switch rear-side connection; 16 mm² (1x) at tunnel terminal; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 35 mm² (2x) direct at switch rear-side connection; 25 mm² - 95 mm² (1x) at tunnel terminal; 25 mm² - 35 mm² (1x) direct at switch rear-side connection
Terminal capacity (control cable)0.75 mm² - 2.5 mm² (1x); 0.75 mm² - 1.5 mm² (2x)
Terminal capacity (copper busbar)Max. 16 mm x 5 mm direct at switch rear-side connection; Min. 12 mm x 5 mm direct at switch rear-side connection; M6 at rear-side screw connection
Terminal capacity (copper solid conductor/cable)16 mm² (1x) at tunnel terminal; 6 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) at box terminal; 6 mm² - 16 mm² (2x) at box terminal; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)25 mm² - 95 mm² (1x) at 1-hole tunnel terminal; 25 mm² (2x) direct at switch rear-side connection; 10 mm² - 70 mm² (1x) at box terminal; 6 mm² - 25 mm² (2x) at box terminal; 10 mm² - 70 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper strip)Min. 2 segments of 9 mm x 0.8 mm at box terminal; Max. 9 segments of 9 mm x 0.8 mm at box terminal
Document NameDescription Action
Rated operation power at AC-3, 400 V45 kW
With integrated auxiliary switchNo
Rated permanent current Iu80 A
With integrated under voltage releaseNo
Rated operating voltage440 V
Overload release current setting63–80 A
Power loss20.8 W
With thermal overload protectionYes
Type of control elementRocker lever
Rated operation power at AC-3, 230 V22 kW
Rated short-circuit breaking capacity Icu at 400 V
AC18.5 kA
Adjustment range undelayed short-circuit release640–1120 A
Phase failure sensitiveYes
Device constructionBuilt-in device plug-in technique
Country of originRomania

Properties

MOQ1

Cross-References

Attached Documents