cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton NZMH4-PX1250-TAZ Molded-Case Circuit Breaker 3-Pole 1250A 85KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMH4-PX1250-TAZ  ·  HS 8536.20
Eaton NZMH4-PX1250-TAZ Molded-Case Circuit Breaker 3-Pole 1250A 85KA

Eaton NZM4 molded-case circuit breaker, type NZMH4-PX1250-TAZ. 3-pole, rated current 1250 A, breaking-capacity class H, frame size NZM4 (up to 1600 A). Rated operational voltage 690 V AC; rated ultimate short-circuit breaking capacity (Icu) 85 kA at 400/415 V AC to IEC/EN 60947-2. Electronic trip unit — adjustable LSI protection with integrated energy metering and communication. Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMH4-PX1250-TAZ
SeriesEaton NZM4 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classH (high breaking capacity)
Number of poles3-Pole
Rated current (In)1250 A
Frame sizeNZM4 (up to 1600 A)
Rated operational voltage (Ue)690 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC85 kA
Trip unit / releaseElectronic trip unit — adjustable LSI protection with integrated energy metering and communication
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
EAN / GTIN4015081875665
HS code8536.20
Sales unitpcs
Eaton catalogue number189619
Depth375 mm
Height170 mm
Width210 mm
Weight19 kg
CompliancesRoHS conform
CertificationsIEC; IEC/EN 60947
FunctionsEarth-fault protection; Systems, cable, selectivity and generator protection; ARMS maintenance mode; Integrated earth fault protection; Zone selectivity
Amperage Rating1250 A
Application525 V
Circuit breaker frame typeNZM4
FeaturesProtection unit; Motor drive optional
Release systemElectronic release
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent173.44 W
Rated operational current for specified heat dissipation (In)1250 A
Direction of incoming supplyAs required
Earth-fault current setting (Ig) - max1250 x In
Earth-fault current setting (Ig) - min250 x In
Electrical connection type of main circuitScrew connection
Handle typeRocker lever
Instantaneous current setting (Ii) - max37500 A
Instantaneous current setting (Ii) - min2500 A
Isolation300 V AC (between the auxiliary contacts); 500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical2000 operations at 690 V AC-1; 3000 operations at 400 V AC-1; 3000 operations at 415 V AC-1
Number of operations per hour - max60
Overload current setting (Ir) - max1250 A
Overload current setting (Ir) - min500 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts8000 V
Rated short-circuit making capacity Icm at 240 V
50/60 Hz275 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz187 kA
Rated short-circuit making capacity Icm at 440 V
Rated short-circuit making capacity Icm at 525 V
50/60 Hz143 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz100 kA
Rated short-time withstand current (t = 0.3 s)19.2 kA
Rated short-time withstand current (t = 1 s)19.2 kA
Short delay current setting (Isd) - max10 A
Short delay current setting (Isd) - min2 A
Short-circuit release delayed setting - max10 A
Short-circuit release delayed setting - min2 A
Short-circuit release non-delayed setting - max15 A
Short-circuit release non-delayed setting - min2 A
Short-circuit total breaktime< 25 ms (≦ 415 V); < 35 ms (> 415 V)
Voltage rating690 V - 690 V
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Degree of protectionIP20; IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front sideIP40 (with insulating surround); IP66 (with door coupling rotary handle)
Degree of protection (terminations)IP00 (terminations, phase insulator and strip terminal); IP10 (tunnel terminal)
Lifespan, mechanical10000 operations
Mounting MethodBuilt-in device fixed built-in technique; Fixed
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Protection against direct contactFinger and back-of-hand proof to VDE 0106 part 100
Shock resistance15 g (half-sinusoidal shock 11 ms)
Optional terminalsConnection on rear. Strip terminal. Tunnel terminal
Standard terminalsScrew connection
Terminal capacity (aluminum stranded conductor/cable)50 mm² - 240 mm² (4x) at 4-hole tunnel terminal
Terminal capacity (control cable)0.75 mm² - 2.5 mm² (1x); 0.75 mm² - 1.5 mm² (2x)
Terminal capacity (copper stranded conductor/cable)50 mm² - 185 mm² (4x) direct at switch rear-side connection; 120 mm² - 185 mm² (1x) direct at switch rear-side connection

Properties

Primary standardEaton NZM
MOQ1

Standards

Cross-References

Attached Documents