cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton NZMH3-VE400-S1 Molded-Case Circuit Breaker 3-Pole 400A 150KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMH3-VE400-S1  ·  HS 8536.20
Eaton NZMH3-VE400-S1 Molded-Case Circuit Breaker 3-Pole 400A 150KA

Eaton NZM3 molded-case circuit breaker, type NZMH3-VE400-S1. 3-pole, rated current 400 A, breaking-capacity class H, frame size NZM3 (up to 630 A). Rated operational voltage 1000 V AC; rated ultimate short-circuit breaking capacity (Icu) 150 kA at 400/415 V AC to IEC/EN 60947-2. Electronic trip unit — adjustable overload and short-circuit protection. 1000 V AC circuit-breaker (NZM…-S1 range). Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMH3-VE400-S1
SeriesEaton NZM3 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classH (high breaking capacity)
Number of poles3-Pole
Rated current (In)400 A
Frame sizeNZM3 (up to 630 A)
Rated operational voltage (Ue)1000 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC150 kA
Trip unit / releaseElectronic trip unit — adjustable overload and short-circuit protection
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
Configuration1000 V AC circuit-breaker (NZM…-S1 range)
EAN / GTIN4015081175031
HS code8536.20
Sales unitpcs
Eaton catalogue number119367
Depth166 mm
Height275 mm
Width140 mm
Weight6.34 kg
CompliancesRoHS conform
CertificationsIEC
FunctionsSystems, cable, selectivity and generator protection
Amperage Rating400 A
Circuit breaker frame typeNZM3
FeaturesMotor drive optional; Protection unit
Release systemElectronic release
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent48 W
Rated operational current for specified heat dissipation (In)400 A
Electrical connection type of main circuitScrew connection
Handle typeRocker lever
Instantaneous current setting (Ii) - max4400 A
Instantaneous current setting (Ii) - min800 A
Lifespan, electrical1000 operations at 1000 V AC-1
Number of operations per hour - max60
Overload current setting (Ir) - max400 A
Overload current setting (Ir) - min200 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts8000 V
Rated short-circuit making capacity Icm at 1000 V
50/60 Hz17 kA
Rated short-circuit making capacity Icm at 240 V
50/60 Hz330 kA
Rated short-circuit making capacity Icm at 400/415 V
Rated short-circuit making capacity Icm at 440 V
50/60 Hz286 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz143 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz74 kA
Rated short-time withstand current (t = 0.3 s)3.3 kA
Rated short-time withstand current (t = 1 s)3.3 kA
Short delay current setting (Isd) - max4000 A
Short delay current setting (Isd) - min400 A
Short-circuit release delayed setting - max4000 A
Short-circuit release delayed setting - min400 A
Short-circuit release non-delayed setting - max4400 A
Short-circuit release non-delayed setting - min800 A
Voltage rating1000 V - 1000 V
Degree of protectionIP20
Lifespan, mechanical15000 operations
Mounting MethodBuilt-in device fixed built-in technique; Fixed
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Standard terminalsScrew terminal
Terminal capacity (aluminum solid conductor/cable)16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)50 mm² - 240 mm² (1x) at 2-hole tunnel terminal; 50 mm² - 240 mm² (2x) at 2-hole tunnel terminal; 25 mm² - 185 mm² (1x) at tunnel terminal
Terminal capacity (control cable)0.75 mm² - 1.5 mm² (2x); 0.75 mm² - 2.5 mm² (1x)
Terminal capacity (copper busbar)Min. 20 mm x 5 mm direct at switch rear-side connection; Max. 10 mm x 50 mm (2x) at rear-side width extension; M10 at rear-side screw connection; Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)16 mm² (2x) at box terminal; 16 mm² (1x) direct at switch rear-side connection; 10 mm² - 16 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)25 mm² - 120 mm² (2x) direct at switch rear-side connection; 25 mm² - 120 mm² (1x) direct at switch rear-side connection; 35 mm² - 240 mm² (1x) at box terminal; 25 mm² - 185 mm² (1x) at tunnel terminal; 25 mm² - 120 mm² (2x) at box terminal
Document NameDescription Action

Properties

Primary standardEaton NZM
MOQ1

Standards

Cross-References

Attached Documents