cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton NZMH2-4-PX100/VAR-SVE Molded-Case Circuit Breaker 4-Pole 100A 150KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMH2-4-PX100/VAR-SVE  ·  HS 8536.20
Eaton NZMH2-4-PX100/VAR-SVE Molded-Case Circuit Breaker 4-Pole 100A 150KA

Eaton NZM2 molded-case circuit breaker, type NZMH2-4-PX100/VAR-SVE. 4-pole, rated current 100 A, breaking-capacity class H, frame size NZM2 (up to 250 A). Rated operational voltage 690 V AC; rated ultimate short-circuit breaking capacity (Icu) 150 kA at 400/415 V AC to IEC/EN 60947-2. Electronic trip unit — adjustable LSI protection with integrated energy metering and communication. Plug-in (withdrawable) version. Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMH2-4-PX100/VAR-SVE
SeriesEaton NZM2 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classH (high breaking capacity)
Number of poles4-Pole
Rated current (In)100 A
Frame sizeNZM2 (up to 250 A)
Rated operational voltage (Ue)690 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC150 kA
Trip unit / releaseElectronic trip unit — adjustable LSI protection with integrated energy metering and communication
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
ConfigurationPlug-in (withdrawable) version
EAN / GTIN4015081926299
HS code8536.20
Sales unitpcs
Eaton catalogue number192078
Depth190 mm
Height160 mm
Width145 mm
Weight3 kg
CompliancesRoHS conform
CertificationsIEC; IEC/EN 60947
FunctionsSystems, cable, selectivity and generator protection
Accessories requiredNZM2-4-XSVS
Amperage Rating100 A
ApplicationUse in unearthed supply systems at 690 V
Circuit breaker frame typeNZM2
FeaturesMotor drive optional; Protection unit
Release systemElectronic release
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent8.25 W
Rated operational current for specified heat dissipation (In)100 A
Current rating of neutral conductor0 - 60% - 100% of phase conductor
Direction of incoming supplyAs required
Electrical connection type of main circuitOther
Handle typeRocker lever
Instantaneous current setting (Ii) - max18 A
Instantaneous current setting (Ii) - min2 A
Isolation500 V AC (between auxiliary contacts and main contacts); 300 V AC (between the auxiliary contacts)
Lifespan, electrical10000 operations at 400 V AC-1; 7500 operations at 690 V AC-1; 10000 operations at 415 V AC-1
Number of operations per hour - max120
Overload current setting (Ir) - max100 A
Overload current setting (Ir) - min40 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts8000 V
Rated short-circuit making capacity Icm at 240 V
50/60 Hz330 kA
Rated short-circuit making capacity Icm at 400/415 V
Rated short-circuit making capacity Icm at 440 V
50/60 Hz286 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz105 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz40 kA
Rated short-time withstand current (t = 0.3 s)1.9 kA
Rated short-time withstand current (t = 1 s)1.9 kA
Short delay current setting (Isd) - max10 A
Short delay current setting (Isd) - min2 A
Short-circuit release delayed setting - max1000 A
Short-circuit release delayed setting - min80 A
Short-circuit release non-delayed setting - max1800 A
Short-circuit release non-delayed setting - min200 A
Short-circuit total breaktime< 10 ms
Voltage rating690 V - 690 V
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Degree of protectionIP20; IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front sideIP66 (with door coupling rotary handle); IP40 (with insulating surround)
Degree of protection (terminations)IP00 (terminations, phase insulator and strip terminal); IP10 (tunnel terminal)
Lifespan, mechanical20000 operations
Mounting MethodBuilt-in device plug-in technique; Plug-in unit
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitConnection at separate chassis part
Protection against direct contactFinger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance20 g (half-sinusoidal shock 20 ms)
Optional terminalsBox terminal. Connection on rear. Tunnel terminal
Standard terminalsScrew terminal
Terminal capacity (aluminum solid conductor/cable)16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 185 mm² (1x) at tunnel terminal
Terminal capacity (control cable)0.75 mm² - 1.5 mm² (2x); 0.75 mm² - 2.5 mm² (1x)
Terminal capacity (copper busbar)Min. 16 mm x 5 mm direct at switch rear-side connection; Max. 24 mm x 8 mm direct at switch rear-side connection; M8 at rear-side screw connection
Terminal capacity (copper solid conductor/cable)16 mm² (1x) at tunnel terminal; 6 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) at box terminal; 6 mm² - 16 mm² (2x) at box terminal; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)25 mm² - 70 mm² (2x) direct at switch rear-side connection; 25 mm² - 70 mm² (2x) at box terminal; 25 mm² - 185 mm² (1x) direct at switch rear-side connection; 25 mm² - 185 mm² (1x) at 1-hole tunnel terminal; 25 mm² - 185 mm² (1x) at box terminal
Terminal capacity (copper strip)Max. 10 segments of 16 mm x 0.8 mm at box terminal; Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched); Min. 2 segments of 9 mm x 0.8 mm at box terminal; Max. 8 segments of 24 mm x 1 mm (2x) at box terminal; Min. 2 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Document NameDescription Action

Properties

Primary standardEaton NZM
MOQ1

Standards

Cross-References

Attached Documents