Eaton NZMH2-A20-S1 Molded-Case Circuit Breaker 3-Pole 20A 150KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMH2-A20-S1  ·  HS 8536.20
Eaton NZMH2-A20-S1 Molded-Case Circuit Breaker 3-Pole 20A 150KA

Eaton NZM2 molded-case circuit breaker, type NZMH2-A20-S1. 3-pole, rated current 20 A, breaking-capacity class H, frame size NZM2 (up to 250 A). Rated operational voltage 1000 V AC; rated ultimate short-circuit breaking capacity (Icu) 150 kA at 400/415 V AC to IEC/EN 60947-2. Thermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection. 1000 V AC circuit-breaker (NZM…-S1 range). Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMH2-A20-S1
SeriesEaton NZM2 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classH (high breaking capacity)
Number of poles3-Pole
Rated current (In)20 A
Frame sizeNZM2 (up to 250 A)
Rated operational voltage (Ue)1000 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC150 kA
Trip unit / releaseThermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
Configuration1000 V AC circuit-breaker (NZM…-S1 range)
EAN / GTIN4015082903558
HS code8536.20
Sales unitpcs
Eaton catalogue number290355
Depth149 mm
Height184 mm
Width105 mm
Weight2.345 kg
CompliancesRoHS conform
CertificationsIEC
FunctionsSystem and cable protection
Amperage Rating20 A
Circuit breaker frame typeNZM2
FeaturesProtection unit; Motor drive optional
Release systemThermomagnetic release
Special featuresLifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release NZM...S1 terminal type: NZM...XKSA cover required Rated current = rated uninterrupted current: 20 A Terminal capacity hint: Up to 240 mm² can be connected depending on the cable manufacturer.
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent5.1 W
Rated operational current for specified heat dissipation (In)20 A
Electrical connection type of main circuitScrew connection
Handle typeRocker lever
Instantaneous current setting (Ii) - max350 A
Instantaneous current setting (Ii) - min350 A
Lifespan, electrical3000 operations at 1000 V AC-1
Number of operations per hour - max120
Overload current setting (Ir) - max20 A
Overload current setting (Ir) - min15 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts8000 V
Rated short-circuit making capacity Icm at 1000 V
50/60 Hz17 kA
Rated short-circuit making capacity Icm at 240 V
50/60 Hz330 kA
Rated short-circuit making capacity Icm at 400/415 V
Rated short-circuit making capacity Icm at 440 V
50/60 Hz286 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz105 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz40 kA
Rated short-time withstand current (t = 0.3 s)1.9 kA
Rated short-time withstand current (t = 1 s)1.9 kA
Short-circuit release non-delayed setting - max350 A
Short-circuit release non-delayed setting - min350 A
Voltage rating1000 V - 1000 V
Degree of protectionIP20
Lifespan, mechanical20000 operations
Mounting MethodDIN rail (top hat rail) mounting optional; Built-in device fixed built-in technique; Fixed
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Standard terminalsScrew terminal
Terminal capacity (aluminum solid conductor/cable)16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 185 mm² (1x) at tunnel terminal
Terminal capacity (control cable)0.75 mm² - 1.5 mm² (2x); 0.75 mm² - 2.5 mm² (1x)
Terminal capacity (copper busbar)Max. 24 mm x 8 mm direct at switch rear-side connection; Min. 16 mm x 5 mm direct at switch rear-side connection; M8 at rear-side screw connection
Terminal capacity (copper solid conductor/cable)10 mm² - 16 mm² (1x) direct at switch rear-side connection; 10 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) at box terminal; 6 mm² - 16 mm² (2x) at box terminal; 16 mm² (1x) at tunnel terminal
Terminal capacity (copper stranded conductor/cable)25 mm² - 185 mm² (1x) at tunnel terminal; 25 mm² - 185 mm² (1x) at box terminal; 25 mm² - 70 mm² (2x) at box terminal; 25 mm² - 50 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper strip)Max. 8 segments of 24 mm x 1 mm (2x) at box terminal; Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched); Min. 2 segments of 9 mm x 0.8 mm at box terminal; Max. 10 segments of 16 mm x 0.8 mm at box terminal; Min. 2 segments of 16 mm x 0.8 mm at rear-side connection (punched)