cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton NZMN2-4-VE160 Molded-Case Circuit Breaker 4-Pole 160A 50KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMN2-4-VE160  ·  HS 8536.20
Eaton NZMN2-4-VE160 Molded-Case Circuit Breaker 4-Pole 160A 50KA

Eaton NZM2 molded-case circuit breaker, type NZMN2-4-VE160. 4-pole, rated current 160 A, breaking-capacity class N, frame size NZM2 (up to 250 A). Rated operational voltage 690 V AC; rated ultimate short-circuit breaking capacity (Icu) 50 kA at 400/415 V AC to IEC/EN 60947-2. Electronic trip unit — adjustable overload and short-circuit protection. Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMN2-4-VE160
SeriesEaton NZM2 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classN (standard breaking capacity)
Number of poles4-Pole
Rated current (In)160 A
Frame sizeNZM2 (up to 250 A)
Rated operational voltage (Ue)690 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC50 kA
Trip unit / releaseElectronic trip unit — adjustable overload and short-circuit protection
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
EAN / GTIN4015082659356
HS code8536.20
Sales unitpcs
Eaton catalogue number265935
Depth149 mm
Height184 mm
Width140 mm
Weight3.172 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947; IEC
FunctionsSystems, cable, selectivity and generator protection
Amperage Rating160 A
ApplicationUse in unearthed supply systems at 690 V
Circuit breaker frame typeNZM2
FeaturesMotor drive optional; Protection unit
Release systemElectronic release
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent21.12 W
Rated operational current for specified heat dissipation (In)160 A
Current rating of neutral conductor200% of phase conductor
Direction of incoming supplyAs required
Electrical connection type of main circuitScrew connection
Handle typeRocker lever
Instantaneous current setting (Ii) - max1920 A
Instantaneous current setting (Ii) - min1920 A
Isolation300 V AC (between the auxiliary contacts); 500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical10000 operations at 400 V AC-1; 6500 operations at 400 V AC-3; 7500 operations at 690 V AC-1; 10000 operations at 415 V AC-1; 5000 operations at 690 V AC-3; 6500 operations at 415 V AC-3
Number of operations per hour - max120
Overload current setting (Ir)80 A - 160 A
Overload current setting (Ir) - max160 A
Overload current setting (Ir) - min80 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts8000 V
Rated short-circuit making capacity Icm at 240 V
50/60 Hz187 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz105 kA
Rated short-circuit making capacity Icm at 440 V
50/60 Hz74 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz53 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz40 kA
Rated short-time withstand current (t = 0.3 s)1.9 kA
Rated short-time withstand current (t = 1 s)1.9 kA
Short delay current setting (Isd) - max1600 A
Short delay current setting (Isd) - min160 A
Short-circuit release delayed setting - max1600 A
Short-circuit release delayed setting - min160 A
Short-circuit release non-delayed setting - max1920 A
Short-circuit release non-delayed setting - min1920 A
Short-circuit total breaktime< 10 ms
Voltage rating690 V - 690 V
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Degree of protectionIP20 (basic degree of protection, in the operating controls area); IP20
Degree of protection (IP), front sideIP40 (with insulating surround); IP66 (with door coupling rotary handle)
Degree of protection (terminations)IP10 (tunnel terminal); IP00 (terminations, phase insulator and strip terminal)
Lifespan, mechanical20000 operations
Mounting MethodFixed; Built-in device fixed built-in technique; DIN rail (top hat rail) mounting optional
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Protection against direct contactFinger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance20 g (half-sinusoidal shock 20 ms)
Optional terminalsBox terminal. Connection on rear. Tunnel terminal
Standard terminalsScrew terminal
Terminal capacity (aluminum solid conductor/cable)16 mm² (1x) at tunnel terminal; 10 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 50 mm² (2x) direct at switch rear-side connection; 25 mm² - 185 mm² (1x) at tunnel terminal; 25 mm² - 50 mm² (1x) direct at switch rear-side connection
Terminal capacity (control cable)0.75 mm² - 2.5 mm² (1x); 0.75 mm² - 1.5 mm² (2x)
Terminal capacity (copper busbar)M8 at rear-side screw connection; Max. 24 mm x 8 mm direct at switch rear-side connection; Min. 16 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)6 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) at box terminal; 16 mm² (1x) at tunnel terminal; 6 mm² - 16 mm² (2x) at box terminal; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)25 mm² - 185 mm² (1x) at 1-hole tunnel terminal; 25 mm² - 70 mm² (2x) direct at switch rear-side connection; 25 mm² - 70 mm² (2x) at box terminal; 25 mm² - 185 mm² (1x) direct at switch rear-side connection; 25 mm² - 185 mm² (1x) at box terminal

Properties

Primary standardEaton NZM
MOQ1

Standards

Cross-References

Attached Documents