Eaton Load-break switch 4P 125A

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
N1-4-125  ·  HS 8536.90
Eaton Load-break switch 4P 125A

Eaton N1-4-125 Load-break switch 4P 125A.

Technical Specifications

Manufacturer part number (MPN)N1-4-125
EAN / GTIN4015082660048
HS code8536.90
Sales unitpcs
Eaton catalogue number266004
Depth88 mm
Height145 mm
Width120 mm
Weight1.077 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947; IEC
FunctionsVoltage release optional; Interlockable; Disconnectors/main switches
Amperage Rating125 A
ApplicationUse in unearthed supply systems at 690 V
Circuit breaker frame typeN1
FeaturesVersion as main switch; Version as maintenance-/service switch; Version as emergency stop installation
Number of polesFour-pole
Special featuresMain switch characteristics including positive drive to IEC/EN 60204 and VDE 0113. Isolating characteristics to IEC/EN 60947-3 and VDE 0660. Busbar tag shroud to VDE 0160 Part 100. Rated current = rated uninterrupted current: 125 A
TypeSwitch-disconnector
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Equipment heat dissipation, current-dependent17.81 W
Rated operational current for specified heat dissipation (In)125 A
Direction of incoming supplyAs required
Electrical connection type of main circuitFrame clamp
Handle typeRocker lever
Isolation500 V AC (between auxiliary contacts and main contacts); 300 V AC (between the auxiliary contacts)
Lifespan, electrical1000 operations at 690 V AC-23A; 7500 operations at 690 V AC-1; 1000 operations at 415 V AC-23A; 10000 operations at 415 V AC-1; 1000 operations at 400 V AC-23A; 10000 operations at 400 V AC-1
Number of operations per hour - max120
Overvoltage categoryIII
Pollution degree3
Rated conditional short-circuit current with back-up fuse80 kA at 690 V; 100 kA at 400/415 V; 125 gG/gL
Rated conditional short-circuit current with downstream fuse10 kA at 690 V; 100 kA at 400/415 V; 125 gG/gL
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts6000 V
Rated insulation voltage (Ui)690 V
Rated operating frequency50 Hz
Rated operating power at AC-23, 400 V55 kW
Rated operating voltage (Ue) at AC - max690 V
Rated operational current160 A (415 V AC-22/23A, making and breaking capacity); 160 A (690 V AC-22/23A, making and breaking capacity)
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz2.8 kA
Rated short-time withstand current (Icw)2 kA
Rated short-time withstand current (t = 0.3 s)2 kA
Rated short-time withstand current (t = 1 s)2 kA
Short-circuit protective device fuses - max125 A gL
Voltage rating690 V - 690 V
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Degree of protectionIP20 (basic protection type, in the area of the HMI devices); Other
Degree of protection (IP), front sideIP40 (with insulating surround); IP66 (with door coupling rotary handle); IP20
Degree of protection (terminations)IP10 (tunnel terminal); IP00 (terminations, phase insulator and band terminal)
Handle colorBlack
Lifespan, mechanical20000 operations
Mounting MethodIntermediate mounting; Ground mounting; Built-in device fixed built-in technique; Distribution board installation; Fixed
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of switches1
Protection against direct contactFinger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance20 g (half-sinusoidal shock 20 ms)
Switch positionsI, +, 0
Optional terminalsConnection on rear. Screw terminal. Tunnel terminal
Standard terminalsBox terminal
Terminal capacity (aluminum solid conductor/cable)10 mm² - 16 mm² (1x) direct at switch rear-side connection; 10 mm² - 16 mm² (2x) direct at switch rear-side connection; 16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 95 mm² (1x) at 1-hole tunnel terminal
Terminal capacity (copper busbar)Min. 12 mm x 5 mm direct at switch rear-side connection; M6 at rear-side screw connection; Max. 16 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)10 mm² - 16 mm² (1x) at box terminal; 16 mm² (1x) at tunnel terminal; 6 mm² - 16 mm² (2x) at box terminal; 6 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) direct at switch rear-side connection
Terminal capacity (copper strip)Max. 9 segments of 9 mm x 0.8 mm at box terminal; Min. 2 segments of 9 mm x 0.8 mm at box terminal