Eaton NZMN3-A500-SVE Molded-Case Circuit Breaker 3-Pole 500A 50KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMN3-A500-SVE  ·  HS 8536.20
Eaton NZMN3-A500-SVE Molded-Case Circuit Breaker 3-Pole 500A 50KA

Eaton NZM3 molded-case circuit breaker, type NZMN3-A500-SVE. 3-pole, rated current 500 A, breaking-capacity class N, frame size NZM3 (up to 630 A). Rated operational voltage 690 V AC; rated ultimate short-circuit breaking capacity (Icu) 50 kA at 400/415 V AC to IEC/EN 60947-2. Thermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection. Plug-in (withdrawable) version. Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMN3-A500-SVE
SeriesEaton NZM3 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classN (standard breaking capacity)
Number of poles3-Pole
Rated current (In)500 A
Frame sizeNZM3 (up to 630 A)
Rated operational voltage (Ue)690 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC50 kA
Trip unit / releaseThermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
ConfigurationPlug-in (withdrawable) version
EAN / GTIN4015081649686
HS code8536.20
Sales unitpcs
Eaton catalogue number168488
Depth335 mm
Height215.2 mm
Width140 mm
Weight6.38 kg
CompliancesRoHS conform
Amperage Rating500 A
FeaturesMotor drive optional; Protection unit
Special featuresRated current = rated uninterrupted current: 500 A
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent93 W
Rated operational current for specified heat dissipation (In)500 A
Electrical connection type of main circuitScrew connection
Handle typeRocker lever
Instantaneous current setting (Ii) - max5000 A
Instantaneous current setting (Ii) - min3000 A
Overload current setting (Ir) - max500 A
Overload current setting (Ir) - min400 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 500 V DC30 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 750 V DC30 kA
Short-circuit release non-delayed setting - max5000 A
Short-circuit release non-delayed setting - min3000 A
Voltage rating690 V - 690 V
Degree of protectionIP20
Mounting MethodBuilt-in device plug-in technique
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side