Eaton NZMB1-A63-SVE Molded-Case Circuit Breaker 3-Pole 63A 25KA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NZMB1-A63-SVE  ·  HS 8536.20
Eaton NZMB1-A63-SVE Molded-Case Circuit Breaker 3-Pole 63A 25KA

Eaton NZM1 molded-case circuit breaker, type NZMB1-A63-SVE. 3-pole, rated current 63 A, breaking-capacity class B, frame size NZM1 (up to 160 A). Rated operational voltage 690 V AC; rated ultimate short-circuit breaking capacity (Icu) 25 kA at 400/415 V AC to IEC/EN 60947-2. Thermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection. Plug-in (withdrawable) version. Utilization category A, suitable for isolation.

Technical Specifications

Manufacturer part number (MPN)NZMB1-A63-SVE
SeriesEaton NZM1 (Moeller series NZM)
TypeMolded-case circuit breaker (MCCB)
Breaking-capacity classB (basic breaking capacity)
Number of poles3-Pole
Rated current (In)63 A
Frame sizeNZM1 (up to 160 A)
Rated operational voltage (Ue)690 V AC
Rated insulation voltage (Ui)800 V
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC25 kA
Trip unit / releaseThermomagnetic release — adjustable thermal overload and electromagnetic short-circuit protection
Utilization categoryA
Suitable for isolationYes
StandardIEC/EN 60947-2
ConfigurationPlug-in (withdrawable) version
EAN / GTIN4015081122554
HS code8536.20
Sales unitpcs
Eaton catalogue number112705
Depth90 mm
Height201 mm
Width95 mm
Weight1.199 kg
CompliancesRoHS conform
CertificationsIEC/EN 60947; IEC
FunctionsSystem and cable protection
Accessories requiredNZM1-XSVS
Amperage Rating63 A
ApplicationUse in unearthed supply systems at 440 V
Circuit breaker frame typeNZM1
FeaturesProtection unit
Release systemThermomagnetic release
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent14.17 W
Rated operational current for specified heat dissipation (In)63 A
Direction of incoming supplyAs required
Electrical connection type of main circuitFrame clamp
Handle typeRocker lever
Instantaneous current setting (Ii) - max630 A
Instantaneous current setting (Ii) - min380 A
Isolation500 V AC (between auxiliary contacts and main contacts); 300 V AC (between the auxiliary contacts)
Lifespan, electrical7500 operations at 400 V AC-1; 7500 operations at 415 V AC-1
Number of operations per hour - max120
Overload current setting (Ir) - max63 A
Overload current setting (Ir) - min50 A
Overvoltage categoryIII
Pollution degree3
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts6000 V
Rated short-circuit making capacity Icm at 240 V
50/60 Hz63 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz53 kA
Rated short-circuit making capacity Icm at 440 V
Short-circuit release non-delayed setting - max630 A
Short-circuit release non-delayed setting - min378 A
Short-circuit total breaktime< 10 ms
Voltage rating440 V - 440 V
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Degree of protectionIP20; IP20 (basic degree of protection, in the operating controls area)
Degree of protection (IP), front sideIP66 (with door coupling rotary handle); IP40 (with insulating surround)
Degree of protection (terminations)IP10 (tunnel terminal); IP00 (terminations, phase insulator and strip terminal)
Lifespan, mechanical20000 operations
Mounting MethodDIN rail (top hat rail) mounting optional; Plug-in unit; Built-in device plug-in technique
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Protection against direct contactFinger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance20 g (half-sinusoidal shock 20 ms)
Optional terminalsConnection on rear. Screw terminal. Tunnel terminal
Standard terminalsBox terminal
Terminal capacity (aluminum solid conductor/cable)10 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) direct at switch rear-side connection; 16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 95 mm² (1x) at tunnel terminal; 25 mm² - 35 mm² (1x) direct at switch rear-side connection; 25 mm² - 35 mm² (2x) direct at switch rear-side connection
Terminal capacity (control cable)0.75 mm² - 1.5 mm² (2x); 0.75 mm² - 2.5 mm² (1x)
Terminal capacity (copper busbar)Max. 16 mm x 5 mm direct at switch rear-side connection; M6 at rear-side screw connection; Min. 12 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)10 mm² - 16 mm² (1x) at box terminal; 16 mm² (1x) at tunnel terminal; 6 mm² - 16 mm² (2x) direct at switch rear-side connection; 10 mm² - 16 mm² (1x) direct at switch rear-side connection; 6 mm² - 16 mm² (2x) at box terminal
Terminal capacity (copper stranded conductor/cable)6 mm² - 25 mm² (2x) at box terminal; 10 mm² - 70 mm² (1x) at box terminal; 10 mm² - 70 mm² (1x) direct at switch rear-side connection; 25 mm² - 95 mm² (1x) at 1-hole tunnel terminal; 25 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper strip)Max. 9 segments of 9 mm x 0.8 mm at box terminal; Min. 2 segments of 9 mm x 0.8 mm at box terminal

Properties

Primary standardEaton NZM
MOQ1

Standards

Cross-References

Attached Documents