cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Position safety switch LSM-11/P

Eaton · Sensors & Instrumentation · Position Switches · Ireland · eaton.com
Part Number
LSM-11/P  ·  HS 8536.50
Position safety switch LSM-11/P

Eaton LSM-11/P Position safety switch, LS(M)-…, Roll Plug, complete unit, 1 N/O, 1 NC, yellow.

Technical Specifications

Manufacturer part number (MPN)LSM-11/P
EAN / GTIN4015082661472
Sales unitpcs
Package quantity2 pcs
Eaton catalogue number266147
Depth33.5 mm
Height86 mm
Width31 mm
Weight0.146 kg
CertificationsCSA File No.: 012528; IEC/EN 60947-5; UL 508; CSA Class No.: 3211-03; UL; CSA; CSA-C22.2 No. 14; IEC/EN 60947; UL Category Control No.: NKCR; CE; UL File No.: E29184
Actuating force at beginning/end of stroke1.0 N/8.0 N
Actuating torque of rotary drives0.2 Nm
Actuator typeRoller cam
Operating speedMax. 1/1 m/s (with DIN cam, mechanical actuation); For angle of actuation α = 0°/30°
Mounting positionAs required
Shock resistance25 g, Standard-action contact, Mechanical, Half-sinusoidal shock 20 ms
Ambient operating temperature - max70 °C
Ambient operating temperature - min-25 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Control circuit reliability1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA); 1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA)
Number of contacts (change-over contacts)0
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Heat dissipation per pole, current-dependent Pvid0.17 W
Rated operational current for specified heat dissipation (In)6 A
Rated insulation voltage (Ui)400 V
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V6 A
Rated operational current (Ie) at AC-15, 24 V6 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V4 A
Rated operational current (Ie) at DC-13, 110 V0.6 A
Rated operational current (Ie) at DC-13, 125 V0.8 A
Rated operational current (Ie) at DC-13, 220 V, 230 V0.3 A
Rated operational current (Ie) at DC-13, 24 V3 A
Short-circuit protection ratingMax. 6 A gG/gL, Fuse, Contacts
Supply frequencyMax. 400 Hz, Contacts
Rated conditional short-circuit current (Iq)1 kA
DesignEN 50047 Form C
Electric connection typeCable entry metrical
Enclosure colorYellow Cover
Enclosure materialMetal
FeaturesPositive opening; Forced opening
Switch function typeSlow-action switch
Connection typeCage Clamp
Degree of protectionIP66/IP67; NEMA Other
Lifespan8,000,000 mechanical Operations
Operating frequency6000 Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryRoller plunger
Rated impulse withstand voltage (Uimp)4000 V AC
Repetition accuracy0.15 mm (Contacts/switching capacity)
Suitable forSafety functions
TypeSafety position switch
Explosion safety category for dustNone
Explosion safety category for gasNone
Terminal capacity (flexible with ferrule)1 x (0.5 - 1.5) mm²
Terminal capacity (solid)1 x (0.5 - 2.5) mm²
Switching functionSlow-action switch
Rated operation current Ie at AC-15, 230 V6 A
Rated operation current Ie at DC-13, 230 V0.3 A
Housing materialMetal
Suitable for safety functionsYes
With status indicationNo
Type of interface for safety communicationNone
Type of electric connectionCable entry metrical
Construction type housingCuboid
Forced openingYes
Type of control elementRoller cam
Type of interfaceNone
Output electronicNo
Rated operation current Ie at AC-15, 125 V6 A
Rated operation current Ie at AC-15, 24 V6 A
Rated operation current Ie at DC-13, 125 V0.8 A
Rated operation current Ie at DC-13, 24 V3 A
Width sensor31 mm
Height of sensor61 mm
Length of sensor33.5 mm
Switching function latchingNo
Ambient temperature during operating25–70 °C
Number of contacts as normally closed contact1
Number of contacts as normally open contact1
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents