cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Motor protection circuit breaker, trip block (PKE-XTUWA-32)

Eaton · Electrical Components · Circuit Breaker Accessories · Ireland · eaton.com
Part Number
PKE-XTUWA-32  ·  HS 8536.90
Motor protection circuit breaker, trip block (PKE-XTUWA-32)

Technical Specifications

Manufacturer part number (MPN)PKE-XTUWA-32
EAN / GTIN4015081350421
HS code8536.90
Sales unitpcs
Eaton catalogue number138262
Depth84.4 mm
Height69.9 mm
Width55 mm
Weight0.196 kg
CertificationsCSA Class No.: 3211-05; VDE 0660; IEC/EN 60947; UL 508; UL File No.: E36332; CSA; CSA-C22.2 No. 14-10; IEC/EN 60947-4-1; CE; UL; CSA File No.: 165628; UL Category Control No.: NLRV
Catalog NotesThis is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.
Shock resistance25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Connection to SmartWire-DTIn conjunction with PKE-SWD-SP SmartWire DT PKE module; Yes
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid3.9 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid1.3 W
Rated operational current for specified heat dissipation (In)32 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Rated operational current (Ie)32 A
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)32 A
Supply voltage at AC, 50 Hz - max690 V
Supply voltage at AC, 50 Hz - min690 V
FeaturesPhase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
FunctionsOverload release; Motor protection; Motor protection for heavy starting duty
Number of polesThree-pole
Cut-out periods - min≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protectionDevice: IP20; Terminals: IP00
Operating frequency60 Operations/h
Overload release current setting - max32 A
Overload release current setting - min8 A
Overvoltage categoryIII
Pollution degree3
Product categoryAccessories
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Temperature compensation-5 - 40 °C to IEC/EN 60947, VDE 0660; -25 - 55 °C, Operating range
Voltage typeSelf powered
Rated control supply voltage (Us) at AC, 50 Hz - min0 V
Rated control supply voltage (Us) at AC, 60 Hz - min0 V
Rated control supply voltage (Us) at DC - min0 V
Short-circuit releaseTrip block fixed 15.5 x Ir; Delayed approx. 60 ms, Trip blocks; ± 20% tolerance, Trip blocks
Switching capacity at AC-3 (up to 690 V)32 A

Properties

MOQ1

Cross-References

Attached Documents