| Manufacturer part number (MPN) | PKE-XTUW-32 |
| EAN / GTIN | 4015081350414 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 138261 |
| Depth | 84.4 mm |
| Height | 69.9 mm |
| Width | 55 mm |
| Weight | 0.196 kg |
| Certifications | CSA-C22.2 No. 14-10; VDE 0660; UL; CSA File No.: 165628; CE; IEC/EN 60947; IEC/EN 60947-4-1; CSA Class No.: 3211-05; CSA; UL 508; UL File No.: E36332; UL Category Control No.: NLRV |
| Catalog Notes | This is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures. |
| Shock resistance | 25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | 25 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Connection to SmartWire-DT | No |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Equipment heat dissipation, current-dependent Pvid | 3.9 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 1.3 W |
| Rated operational current for specified heat dissipation (In) | 32 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| Rated frequency - max | 60 Hz |
| Rated frequency - min | 50 Hz |
| Rated operational current (Ie) | 32 A |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Rated uninterrupted current (Iu) | 32 A |
| Supply voltage at AC, 50 Hz - max | 690 V |
| Supply voltage at AC, 50 Hz - min | 690 V |
| Features | Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102) |
| Functions | Motor protection; Overload release; Motor protection for heavy starting duty |
| Number of poles | Three-pole |
| Cut-out periods - min | ≤ 500 ms, main conducting paths, AC-4 cycle operation |
| Degree of protection | Device: IP20; Terminals: IP00 |
| Operating frequency | 60 Operations/h |
| Overload release current setting - max | 32 A |
| Overload release current setting - min | 8 A |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Accessories |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Temperature compensation | -25 - 55 °C, Operating range; -5 - 40 °C to IEC/EN 60947, VDE 0660 |
| Voltage type | Self powered |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Rated control supply voltage (Us) at DC - min | 0 V |
| Short-circuit release | ± 20% tolerance, Trip blocks; Trip block fixed 15.5 x Ir; Delayed approx. 60 ms, Trip blocks |
| Switching capacity at AC-3 (up to 690 V) | 32 A |