cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Eaton Complete PKE65 with Standard trip block 16-65A

Eaton · Electrical Components · Motor Protection Circuit Breakers · Ireland · eaton.com
Part Number
PKE65/XTU-65  ·  HS 8536.20
Eaton Complete PKE65 with Standard trip block 16-65A

Eaton PKE65/XTU-65 Complete PKE65 with Standard trip block 16-65A.

Technical Specifications

Manufacturer part number (MPN)PKE65/XTU-65
EAN / GTIN4015081352951
Sales unitpcs
Eaton catalogue number138516
Depth187 mm
Height162 mm
Width55 mm
Weight1.469 kg
CertificationsCE; CSA-C22.2 No. 60947-4-1-14; CSA; UL Category Control No.: NLRV; UL File No.: E36332; CSA File No.: 165628; UL; UL 60947-4-1; VDE 0660; IEC/EN 60947; CSA Class No.: 3211-05; IEC/EN 60947-4-1
Catalog NotesThis is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
ConnectionScrew terminals
Equipment heat dissipation, current-dependent Pvid21.6 W
Heat dissipation per pole, current-dependent Pvid7.2 W
Rated operational current for specified heat dissipation (In)65 A
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Rated operational current (Ie)65 A
Rated operational power at AC-3e, 220/230 V, 50 Hz18.5 kW
Rated operational power at AC-3e, 380/400 V, 50 Hz30 kW
Rated operational power at AC-3e, 440 V, 50 Hz37 kW
Rated operational power at AC-3e, 500 V, 50 Hz45 kW
Rated operational power at AC-3e, 690 V, 50 Hz55 kW
Rated operational voltage (Ue) - max690 V
Rated operational voltage (Ue) - min690 V
Rated uninterrupted current (Iu)65 A
Actuator typeTurn button
FeaturesPhase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
Fitted withStandard knob
FunctionsMotor protection for heavy starting duty; Overload release; Motor protection
Number of polesThree-pole
Cut-out periods - min≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protectionIP20; Terminals: IP00
Lifespan, electrical50,000 operations (at 400V, AC-3)
Lifespan, mechanical30,000 Operations (Main conducting paths)
Operating frequency60 Operations/h
Overload release current setting - max65 A
Overload release current setting - min16 A
Overvoltage categoryIII
Pollution degree3
Product categoryMotor protective circuit breaker
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Resistance per pole1.6 mΩ
Suitable forAlso motors with efficiency class IE3
Temperature compensation-5 - 40 °C to IEC/EN 60947, VDE 0660; -25 - 55 °C, Operating range
Assigned motor power at 115/120 V, 60 Hz, 1-phase3 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase15 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase10 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase15 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase40 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase40 HP
Short-circuit current rating (group protection)100 kA, 600 V High Fault, Fuse, SCCR (UL/CSA); 200 A, Class J, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
Short-circuit releaseTrip block fixed 15.5 x Ir; ± 20% tolerance, Trip blocks; Delayed approx. 60 ms, Trip blocks; Basic device fixed 15.5 x Iu, Trip Blocks
Switching capacity65 A, AC-3 up to 690 V; 58 A, General use UL/CSA
Stripping length (main cable)14 mm
Terminal capacity (flexible with ferrule)2 x (0.75 - 25) mm², ferrule to DIN 46228; 1 x (0.75 - 35) mm², ferrule to DIN 46228
Terminal capacity (solid)1 x (0.75 - 16) mm²; 2 x (0.75 - 16) mm²
Terminal capacity (solid/stranded AWG)14 - 2
Tightening torque3.3 Nm, Screw terminals, Main cable; 1 Nm, Screw terminals, Control circuit cables
Rated operation power at AC-3, 400 V30 kW
With integrated auxiliary switchNo
Rated permanent current Iu65 A
With integrated under voltage releaseNo
Rated operating voltage690 V
Overload release current setting16–65 A
Power loss21.6 W
With thermal overload protectionYes
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
Switch off techniqueElectronic
Rated operation power at AC-3, 230 V18.5 kW
Adjustment range undelayed short-circuit release1008 A
Phase failure sensitiveYes
Device constructionBuilt-in device fixed built-in technique
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents