| Manufacturer part number (MPN) | AGM2-10-PKZ0 |
| EAN / GTIN | 4015080728986 |
| Sales unit | pcs |
| Package quantity | 2 pcs |
| Eaton catalogue number | 072898 |
| Depth | 68 mm |
| Height | 90 mm |
| Width | 23 mm |
| Weight | 0.035 kg |
| Certifications | CSA Class No.: 3211-05; UL File No.: E36332; CE; IEC/EN 60947-4-1; UL Category Control No.: NLRV; UL; CSA-C22.2 No. 14; CSA; CSA File No.: 165628; UL 508 |
| Ambient operating temperature - max | 55 °C |
| Ambient operating temperature - min | -25 °C |
| Connection type | Screw connection |
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 2 |
| Heat dissipation per pole, current-dependent Pvid | 0.1 W |
| Rated operational current for specified heat dissipation (In) | 3.5 A |
| Rated operational current (Ie) | 1 A at AC-15, 440 V 500 V |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 3.5 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 2 A |
| Rated operational current (Ie) at DC-13, 110 V | 0.5 A |
| Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.25 A |
| Rated operational current (Ie) at DC-13, 24 V | 2 A |
| Rated operational current (Ie) at DC-13, 60 V | 1 A |
| Rated operational voltage (Ue) at DC - max | 250 V |
| Safe isolation | 440 V, Between auxiliary contacts and main contacts, According to EN 61140 |
| Electric connection type | Screw connection |
| Indication | Short-circuits indicated locally by means of a red indicator that can be manually reset; General trip indication (overload) |
| Lifespan, electrical | 50,000 Operations |
| Lifespan, mechanical | 10,000 Operations |
| Model | Top mounting |
| Mounting method | Side mounting |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Accessories |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Used with | Motor protective circuit-breaker |
| Short-circuit protection rating without welding | 10 A gG/gL, Fuse, Auxiliary contacts |
| Switching capacity (auxiliary contacts, general use) | 5 A, 600 V AC, (UL/CSA); 1 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA); Q300, DC operated (UL/CSA) |
| Terminal capacity (solid/flexible with ferrule) | 0.75 - 2.5 mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Country of origin | Germany |