cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Switch-disconnector,DCM-40/1-SK+FM

Eaton · Switchgear & Protection · Disconnect Switches · Ireland · eaton.com
Part Number
DCM-40/1-SK+FM  ·  HS 8536.50
Switch-disconnector,DCM-40/1-SK+FM

Eaton DCM-40/1-SK+FM Switch-Disconnector, DCM, 40 A, 3P + N (solid), stop function optional.

Technical Specifications

Manufacturer part number (MPN)DCM-40/1-SK+FM
EAN / GTIN8711426100961
Sales unitpcs
Eaton catalogue number1314112
Depth150 mm
Height80 mm
Width90 mm
Weight0.384 kg
CertificationsIEC/EN 60947; IEC/EN 60947-3; CE; RoHS; KEMA; VDE 0660; Lloyds; EAC; IEC/EN 60204
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-30 °C
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Heat dissipation per pole, current-dependent Pvid3 W
Rated operational current for specified heat dissipation (In)40 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)320 A
Rated insulation voltage (Ui)690 V
Rated operational current (Ie) at AC-21, 400 V, 415 V40 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V40 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V40 A
Rated operational power at AC-23A, 400 V, 50 Hz20 kW
Rated operational voltage (Ue) at AC - max415 V
Rated uninterrupted current (Iu)40 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FunctionsOptional Stop Function
Number of polesThree-pole + N
Actuator colorOther
Actuator typeOther
Degree of protectionNEMA Other
Degree of protection (front side)IP20
Lifespan, mechanical10,000 Operations
Mounting methodSurface mounting
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch Switch-disconnector
Rated impulse withstand voltage (Uimp)6000 V
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forDistribution board installation; Ground mounting
Breaking current7 kA
Light-through energyMax. 12 kA²s
Rated short-circuit making capacity (Icm)2.2 kAeff
Rated short-time withstand current (Icw)1 kA; 1 kA, Contacts, 1 second
Short-circuit protection rating50, Fuse, Contacts
Stripping length (main cable)14 mm
Terminal capacity1.5 - 25 mm², flexible; 2.5 - 16 mm², solid
Country of originUnited Kingdom

Properties

MOQ1

Cross-References