Eaton NS1-63-NA

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
NS1-63-NA  ·  HS 8536.20
Eaton NS1-63-NA

Technical Specifications

Manufacturer part number (MPN)NS1-63-NA
EAN / GTIN4015081025411
Sales unitpcs
Eaton catalogue number102681
Depth88 mm
Height145 mm
Width90 mm
Weight1.046 kg
CompliancesRoHS conform
CertificationsIEC; CE marking; UL listed; UL/CSA; UL (Category Control Number WJAZ); CSA (File No. 22086); UL (File No. E148671); IEC 60947-2; UL 489; CSA-C22.2 No. 5-09; CSA (Class No. 4652-06); CSA certified; Specially designed for North America
FunctionsDisconnectors/main switches
Amperage Rating63 A
ApplicationBranch circuits, feeder circuits
Circuit breaker frame typeN1
FeaturesProtection unit
Number of polesThree-pole
Special featuresIEC/EN 60947-2: circuit breakers without overcurrent (CBI-X) with main switch characteristics and isolating characteristics to IEC/EN 60204. Rated current = rated uninterrupted current: 63 A Terminal capacity hint: Up to 95 mm² can be connected depending on the cable manufacturer.
TypeSwitch-disconnector
Ambient operating temperature - max70 °C
Ambient storage temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent6.69 W
Rated operational current for specified heat dissipation (In)63 A
Current rating (Iu) (UL 489 csa 22.2 no. 5.1)125 A
Direction of incoming supplyAs required
Electrical connection type of main circuitFrame clamp
Handle typeRocker lever
Instantaneous current setting (Ii) - max1250 A
Instantaneous current setting (Ii) - min1250 A
Lifespan, electrical10000 operations at 415 V AC-1; 7500 operations at 690 V AC-1; 10000 operations at 400 V AC-1
Number of operations per hour - max120
Overvoltage categoryIII
Pollution degree3
Rated current (Iu)125 A
Rated impulse withstand voltage (Uimp) at auxiliary contacts6000 V
Rated impulse withstand voltage (Uimp) at main contacts6000 V
Rated insulation voltage (Ui)690 V AC
Rated operating voltage Ue (UL) - max480 Y / 277 V
Rated short-circuit making capacity Icm at 240 V
50/60 Hz187 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz105 kA
Rated short-circuit making capacity Icm at 440 V
50/60 Hz74 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz53 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz17 kA
Short-circuit release non-delayed setting - max1250 A
Short-circuit release non-delayed setting - min1250 A
Short-circuit total breaktime< 10 ms
Voltage rating690 V - 690 V
Degree of protectionIP20; In the area of the HMI devices: IP20 (basic protection type)
Degree of protection (IP), front sideIP66 (with door coupling rotary handle); IP40 (with insulating surround)
Degree of protection (terminations)IP00 (terminations, phase insulator and band terminal); IP10 (tunnel terminal)
Lifespan, mechanical20000 operations
Mounting MethodFixed; DIN rail (top hat rail) mounting optional; Built-in device fixed built-in technique
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Position of connection for main current circuitFront side
Switch positionsI, +, 0
Optional terminalsConnection on rear. Screw terminal. Tunnel terminal
Standard terminalsBox terminal
Terminal capacity (aluminum solid conductor/cable)10 mm² - 16 mm² (1x) direct at switch rear-side connection; 16 mm² (1x) at tunnel terminal; 10 mm² - 16 mm² (2x) direct at switch rear-side connection
Terminal capacity (aluminum stranded conductor/cable)25 mm² - 35 mm² (1x) direct at switch rear-side connection; 25 mm² - 95 mm² (1x) at 1-hole tunnel terminal; 25 mm² - 35 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper strip)Min. 2 segments of 9 mm x 0.8 mm at box terminal; Max. 9 segments of 9 mm x 0.8 mm at box terminal
Rated permanent current Iu63 A
With integrated under voltage releaseNo
Rated voltage690 V
Power loss6.7 W
Motor drive integratedNo
Type of electrical connection of main circuitFrame clamp
Type of control elementRocker lever
With switched-off indicatorNo
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz50 kA
Adjustment range undelayed short-circuit release1250 A
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Motor drive optionalNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
Country of originRomania

Properties