| Manufacturer part number (MPN) | LS-S11S/RR |
| EAN / GTIN | 4015081065714 |
| Sales unit | pcs |
| Package quantity | 4 pcs |
| Eaton catalogue number | 106804 |
| Depth | 33.5 mm |
| Height | 140 mm |
| Width | 31 mm |
| Weight | 0.078 kg |
| Certifications | UL Category Control No.: NKCR; CSA Class No.: 3211-03; UL; UL File No.: E29184; CE; CSA File No.: 012528; CSA; CSA-C22.2 No. 14; IEC/EN 60947; UL 508; IEC/EN 60947-5 |
| Actuating force at beginning/end of stroke | 1.0 N/8.0 N |
| Actuating torque of rotary drives | 0.2 Nm |
| Actuator type | Actuating rod |
| Operating speed | L = 130 mm; Max. 1.5 m/s (with DIN cam, mechanical actuation) |
| Mounting position | As required |
| Shock resistance | 25 g, Standard-action contact, Mechanical, Half-sinusoidal shock 20 ms |
| Ambient operating temperature - max | 70 °C |
| Ambient operating temperature - min | -25 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Control circuit reliability | 1 failure per 10,000,000 switching operations (Statistically determined, at 24 V DC/5 mA); 1 failure per 5,000,000 switching operations (statistically determined, at 5 V DC/1 mA) |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Heat dissipation per pole, current-dependent Pvid | 0.17 W |
| Rated operational current for specified heat dissipation (In) | 6 A |
| Rated insulation voltage (Ui) | 400 V |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 24 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 4 A |
| Rated operational current (Ie) at DC-13, 110 V | 0.6 A |
| Rated operational current (Ie) at DC-13, 125 V | 0.8 A |
| Rated operational current (Ie) at DC-13, 220 V, 230 V | 0.3 A |
| Rated operational current (Ie) at DC-13, 24 V | 3 A |
| Short-circuit protection rating | Max. 6 A gG/gL, Fuse, Contacts |
| Supply frequency | Max. 400 Hz, Contacts |
| Rated conditional short-circuit current (Iq) | 1 kA |
| Electric connection type | Cable entry metrical |
| Enclosure color | Yellow Cover |
| Enclosure material | Plastic; Insulated material |
| Features | Positive opening; Forced opening; Snap-action contact |
| Switch function type | Quick-break switch |
| Connection type | Screw terminal |
| Degree of protection | IP66/IP67; NEMA Other |
| Lifespan | 8,000,000 mechanical Operations |
| Operating frequency | 6000 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Basic units with spring-powered interlock (closed-circuit principle) |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Repetition accuracy | 0.15 mm (Contacts/switching capacity) |
| Suitable for | Safety functions |
| Type | Position switch Safety position switch |
| Explosion safety category for dust | None |
| Explosion safety category for gas | None |
| Terminal capacity (flexible with ferrule) | 1 x (0.5 - 1.5) mm² |
| Terminal capacity (solid) | 1 x (0.5 - 2.5) mm² |
| Switching function | Quick-break switch |
| Rated operation current Ie at AC-15, 230 V | 6 A |
| Rated operation current Ie at DC-13, 230 V | 0.3 A |
| Housing material | Plastic |
| Suitable for safety functions | Yes |
| With status indication | No |
| Type of interface for safety communication | None |
| Construction type housing | Cuboid |
| Forced opening | Yes |
| Number of safety auxiliary contacts | 1 |
| Type of control element | Actuating rod |
| Type of interface | None |
| Output electronic | No |
| Rated operation current Ie at AC-15, 125 V | 6 A |
| Rated operation current Ie at AC-15, 24 V | 6 A |
| Rated operation current Ie at DC-13, 125 V | 0.8 A |
| Rated operation current Ie at DC-13, 24 V | 3 A |
| Width sensor | 31 mm |
| Height of sensor | 61 mm |
| Length of sensor | 33.5 mm |
| Switching function latching | No |
| Ambient temperature during operating | 25–70 °C |
| Number of contacts as normally closed contact | 1 |
| Number of contacts as normally open contact | 1 |
| Country of origin | Germany |