| Manufacturer part number (MPN) | PKZM0-10-T |
| EAN / GTIN | 4015080889168 |
| Sales unit | pcs |
| Eaton catalogue number | 088916 |
| Depth | 76 mm |
| Height | 93 mm |
| Width | 45 mm |
| Weight | 0.291 kg |
| Certifications | VDE 0660; IEC/EN 60947; CE; UL; CSA; IEC/EN 60947-4-1; CSA Class No.: 3211-05; CSA File No.: 165628; CSA-C22.2 No. 60947-4-1-14; UL 60947-4-1; UL Category Control No.: NLRV; UL File No.: E36332 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Rated operational current for specified heat dissipation (In) | 10 A |
| Equipment heat dissipation, current-dependent Pvid | 6.29 W |
| Heat dissipation per pole, current-dependent Pvid | 2.1 W |
| Rated frequency - max | 60 Hz |
| Rated frequency - min | 50 Hz |
| Rated operational current (Ie) | 10 A |
| Rated operational power at AC-3e, 220/230 V, 50 Hz | 2.2 kW |
| Rated operational power at AC-3e, 380/400 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 440 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 500 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 690 V, 50 Hz | 7.5 kW |
| Rated operational voltage (Ue) - max | 690 V |
| Rated operational voltage (Ue) - min | 690 V |
| Rated uninterrupted current (Iu) | 10 A |
| Actuator type | Turn button |
| Features | Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102) |
| Fitted with | Switched-off indicator |
| Functions | Transformer protection; For the protection of transformers with a high inrush current |
| Number of poles | Three-pole |
| Connection | Screw terminals |
| Degree of protection | Terminals: IP00; IP20 |
| Lifespan, electrical | 100,000 operations |
| Lifespan, mechanical | 100,000 Operations |
| Mounting Method | DIN rail (top hat rail) mounting optional |
| Mounting position | Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height. |
| Operating frequency | 40 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Transformer protective circuit breaker |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Suitable for | Also motors with efficiency class IE3; DIN rail (top hat rail) mounting |
| Temperature compensation | ≤ 0.25 %/K, residual error for T > 40°; -5 - 40 °C to IEC/EN 60947, VDE 0660; -25 - 55 °C, Operating range |
| Rated short-circuit breaking capacity Ics at 400 V AC | 150 kA |
| Rated short-circuit breaking capacity Ics at 440 V AC | 50 kA |
| Rated short-circuit breaking capacity Ics at 500 V AC | 11 kA |
| Rated short-circuit breaking capacity Ics at 690 V AC | 2 kA |
| Rated short-circuit breaking capacity Icu at 400 V AC | 150 kA |
| Rated short-circuit breaking capacity Icu at 440 V AC | 50 kA |
| Rated short-circuit breaking capacity Icu at 500 V AC | 42 kA |
| Rated short-circuit breaking capacity Icu at 690 V AC | 3 kA |
| Short-circuit current | 60 kA DC, up to 250 V DC, Main conducting paths |
| Short-circuit current rating (group protection) | 50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 150 A, 600 V High Fault, Fuse, SCCR (UL/CSA); 30 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA); 30 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA) |
| Short-circuit release | Basic device, fixed 20 x Iu; ± 20% tolerance; 224 A, Irm |
| Switching capacity | 10 A (3 contacts in series), DC-5 up to 250V; 10 A, AC-3 up to 690 V |
| Stripping length (main cable) | 10 mm |
| Terminal capacity (flexible with ferrule) | 2 x (1 - 6) mm², ferrule to DIN 46228; 1 x (1 - 6) mm², ferrule to DIN 46228 |
| Terminal capacity (solid) | 1 x (1 - 6) mm²; 2 x (1 - 6) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 10 |
| Tightening torque | 1.7 Nm, Screw terminals, Main cable |
| Overload release current setting - max | 10 A |
| Overload release current setting - min | 6.3 A |
| Rated permanent current Iu | 10 A |
| With integrated under voltage release | No |
| Overload release current setting | 6.3–10 A |
| Rated voltage | 690 V |
| Power loss | 6.29 W |
| Motor drive integrated | No |
| Type of electrical connection of main circuit | Screw connection |
| Type of control element | Turn button |
| With switched-off indicator | Yes |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 150 kA |
| Adjustment range undelayed short-circuit release | 224 A |
| Suitable for DIN rail (top hat rail) mounting | Yes |
| Integrated earth fault protection | No |
| Motor drive optional | No |
| DIN rail (top hat rail) mounting optional | Yes |
| Complete device with protection unit | Yes |
| Country of origin | Germany |