| Manufacturer part number (MPN) | PKE65/XTUWCP-36 |
| EAN / GTIN | 4015081654642 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 168973 |
| Depth | 187 mm |
| Height | 162 mm |
| Width | 55 mm |
| Weight | 1.427 kg |
| Certifications | VDE 0660; IEC/EN 60947 |
| Catalog Notes | This is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures. |
| Shock resistance | 15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Connection | Screw terminals |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Equipment heat dissipation, current-dependent Pvid | 6.6 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 2.2 W |
| Rated operational current for specified heat dissipation (In) | 36 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| Rated frequency - max | 60 Hz |
| Rated frequency - min | 50 Hz |
| Rated operational current (Ie) | 36 A |
| Rated operational voltage (Ue) - max | 690 V |
| Rated operational voltage (Ue) - min | 690 V |
| Rated uninterrupted current (Iu) | 36 A |
| Actuator type | Turn button |
| Features | Complete device with protection unit |
| Fitted with | Standard knob |
| Functions | Overload release; System protection; Line and cable protection |
| Number of poles | Three-pole |
| Cut-out periods - min | ≤ 500 ms, main conducting paths, AC-4 cycle operation |
| Degree of protection | IP20; Terminals: IP00 |
| Lifespan, electrical | 50,000 operations (at 400V, AC-3) |
| Lifespan, mechanical | 30,000 Operations (Main conducting paths) |
| Mounting Method | DIN rail (top hat rail) mounting optional |
| Operating frequency | 60 Operations/h |
| Overload release current setting - max | 36 A |
| Overload release current setting - min | 15 A |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Circuit-breaker PKE |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Resistance per pole | 2.2 mΩ |
| Suitable for | DIN rail (top hat rail) mounting |
| Temperature compensation | -25 - 55 °C, Operating range; -5 - 40 °C to IEC/EN 60947, VDE 0660 |
| Short-circuit release | ± 20% tolerance, Trip blocks; Basic device fixed 15.5 x Iu, Trip Blocks; Delayed approx. 60 ms, Trip blocks; Trip block adjustable 5 - 8 x Ir |
| Stripping length (main cable) | 14 mm |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 35) mm², ferrule to DIN 46228; 2 x (0.75 - 25) mm², ferrule to DIN 46228 |
| Terminal capacity (solid) | 1 x (0.75 - 16) mm²; 2 x (0.75 - 16) mm² |
| Tightening torque | 1 Nm, Screw terminals, Control circuit cables; 3.3 Nm, Screw terminals, Main cable |