cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Switch, systemprotection (PKE32/XTUCP-36)

Eaton · Electrical Components · Moulded Case Circuit Breakers · Ireland · eaton.com
Part Number
PKE32/XTUCP-36  ·  HS 8536.90
Switch, systemprotection (PKE32/XTUCP-36)

Technical Specifications

Manufacturer part number (MPN)PKE32/XTUCP-36
EAN / GTIN4015081654635
HS code8536.90
Sales unitpcs
Eaton catalogue number168972
Depth101 mm
Height102.5 mm
Width45 mm
Weight0.436 kg
CertificationsVDE 0660; IEC/EN 60947
Shock resistance25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
ConnectionScrew terminals
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid11.4 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid3.8 W
Rated operational current for specified heat dissipation (In)32 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Rated operational current (Ie)36 A
Rated operational voltage (Ue) - max690 V
Rated operational voltage (Ue) - min690 V
Rated uninterrupted current (Iu)36 A
Actuator typeTurn button
FeaturesComplete device with protection unit
Fitted withStandard knob
FunctionsLine and cable protection; System protection; Overload release
Number of polesThree-pole
Cut-out periods - min≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protectionIP20; Terminals: IP00
Lifespan, electrical50,000 operations (at 400V, AC-3)
Lifespan, mechanical50,000 Operations (Main conducting paths)
Mounting MethodDIN rail (top hat rail) mounting optional
Operating frequency60 Operations/h
Overload release current setting - max36 A
Overload release current setting - min15 A
Overvoltage categoryIII
Pollution degree3
Product categoryCircuit-breaker PKE
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Resistance per pole2.7 mΩ
Suitable forDIN rail (top hat rail) mounting
Temperature compensation-25 - 55 °C, Operating range; -5 - 40 °C to IEC/EN 60947, VDE 0660
Short-circuit releaseTrip block adjustable 5 - 8 x Ir; Delayed approx. 60 ms, Trip blocks; ± 20% tolerance, Trip blocks; Basic device fixed 15.5 x Iu, Trip Blocks
Stripping length (main cable)10 mm
Terminal capacity (flexible with ferrule)2 x (1 - 6) mm², ferrule to DIN 46228; 1 x (1 - 6) mm², ferrule to DIN 46228
Terminal capacity (solid)2 x (1 - 6) mm²; 1 x (1 - 6) mm²
Tightening torque1.7 Nm, Screw terminals, Main cable; 1 Nm, Screw terminals, Control circuit cables