cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Motor protection circuit breaker, trip block (PKE-XTUACP-65)

Eaton · Electrical Components · Circuit Breaker Accessories · Ireland · eaton.com
Part Number
PKE-XTUACP-65  ·  HS 8536.90
Motor protection circuit breaker, trip block (PKE-XTUACP-65)

Technical Specifications

Manufacturer part number (MPN)PKE-XTUACP-65
EAN / GTIN4015081652907
HS code8536.90
Sales unitpcs
Eaton catalogue number168799
Depth84.4 mm
Height69.9 mm
Width55 mm
Weight0.238 kg
CertificationsIEC/EN 60947; VDE 0660
Catalog NotesThis is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.
Shock resistance15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTYes; In conjunction with PKE-SWD-SP SmartWire DT PKE module
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid9.3 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid3.1 W
Rated operational current for specified heat dissipation (In)65 A
Static heat dissipation, non-current-dependent Pvs0 W
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Rated operational current (Ie)65 A
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)65 A
Supply voltage at AC, 50 Hz - max690 V
Supply voltage at AC, 50 Hz - min690 V
FunctionsLine and cable protection; System protection; Overcurrent protection; Short-circuit protection
Number of polesThree-pole
Cut-out periods - min≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protectionTerminals: IP00; Device: IP20
Operating frequency60 Operations/h
Overload release current setting - max65 A
Overload release current setting - min30 A
Overvoltage categoryIII
Pollution degree3
Product categoryAccessories
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Temperature compensation-5 - 40 °C to IEC/EN 60947, VDE 0660; -25 - 55 °C, Operating range
Voltage typeSelf powered
Rated control supply voltage (Us) at AC, 50 Hz - min0 V
Rated control supply voltage (Us) at AC, 60 Hz - min0 V
Rated control supply voltage (Us) at DC - min0 V
Short-circuit releaseDelayed approx. 60 ms, Trip blocks; Trip block adjustable 5 - 8 x Ir; 150 - 520 A, Irm, Setting range; ± 20% tolerance, Trip blocks

Properties

MOQ1

Cross-References

Attached Documents