cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Motor protection circuit breaker,PKZM0-4-SPI16

Eaton · Electrical Components · Motor Protection Circuit Breakers · Ireland · eaton.com
Part Number
PKZM0-4-SPI16  ·  HS 8536.90
Motor protection circuit breaker,PKZM0-4-SPI16

Eaton PKZM0-4-SPI16 Motorprotective circuit breaker, 1.5 kW, 2.5 - 4 A, Feed-side screw term./output-side PI term.

Technical Specifications

Manufacturer part number (MPN)PKZM0-4-SPI16
EAN / GTIN4015081972685
HS code8536.90
Sales unitpcs
Eaton catalogue number199184
Depth75 mm
Height94 mm
Width45 mm
Weight0.292 kg
CertificationsIEC/EN 60947; VDE 0660; UL File No.: E36332; IEC/EN 60947-4-1; CSA File No.: 165628; UL Category Control No.: NLRV; UL; CSA-C22.2 No. 60947-4-1-14; CSA Class No.: 3211-05; CSA; UL 60947-4-1; CE
AltitudeMax. 2000 m
Ambient operating temperature - max55 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Rated operational current for specified heat dissipation (In)4 A
Static heat dissipation, non-current-dependent Pvs0 W
Equipment heat dissipation, current-dependent Pvid5.33 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid1.8 W
Rated frequency - max60 Hz
Rated frequency - min50 Hz
Rated operational current (Ie)4 A
Rated operational power at AC-3e, 220/230 V, 50 Hz0.75 kW
Rated operational power at AC-3e, 380/400 V, 50 Hz1.5 kW
Rated operational power at AC-3e, 440 V, 50 Hz1.5 kW
Rated operational power at AC-3e, 500 V, 50 Hz2.2 kW
Rated operational power at AC-3e, 690 V, 50 Hz3 kW
Rated operational voltage (Ue) - max690 V
Rated operational voltage (Ue) - min690 V
Rated uninterrupted current (Iu)4 A
Actuator typeTurn button
FeaturesPhase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
FunctionsMotor protection; Phase failure sensitive
Number of polesThree-pole
ConnectionPush-in terminals on output side; Screw terminals on feed side
Degree of protectionTerminals: IP00; IP20
Lifespan, electrical100,000 operations
Lifespan, mechanical100,000 Operations
Mounting MethodDIN rail (top hat rail) mounting optional
Mounting positionCan be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
Operating frequency40 Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryMotor protective circuit breaker
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Shock resistance25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Suitable forAlso motors with efficiency class IE3; Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
Temperature compensation≤ 0.25 %/K, residual error for T > 40°; -25 - 55 °C, Operating range; -5 - 40 °C to IEC/EN 60947, VDE 0660
Assigned motor power at 115/120 V, 60 Hz, 1-phase0.125 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase0.75 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase0.33 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase0.75 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase2 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase3 HP
Rated short-circuit breaking capacity Ics at 400 V AC150 kA
Rated short-circuit breaking capacity Ics at 440 V AC150 kA
Rated short-circuit breaking capacity Ics at 500 V AC150 kA
Rated short-circuit breaking capacity Ics at 690 V AC3 kA
Rated short-circuit breaking capacity Icu at 400 V AC150 kA
Rated short-circuit breaking capacity Icu at 440 V AC150 kA
Rated short-circuit breaking capacity Icu at 500 V AC150 kA
Rated short-circuit breaking capacity Icu at 690 V AC3 kA
Short-circuit current rating (group protection)50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA); 50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Short-circuit current rating (type E)50 kA, 600 Y/347 V, SCCR (UL/CSA); 65 kA, 240 V, SCCR (UL/CSA); 65 kA, 480 Y/277 V, SCCR (UL/CSA); Accessories required BK25/3-PKZ0-E
Short-circuit releaseBasic device fixed 15.5 x Iu; ± 20% tolerance; 62 A, Irm
Switching capacity4 A, AC-3 up to 690 V
Stripping length (main cable)10 mm
Terminal capacity (flexible with unisolated ferrule)1 x (1 - 6) mm², Screw terminals; 2 x (1 - 6) mm², Screw terminals; 1 x (1 - 2.5) mm², Push-in terminals; 2 x (1 - 2.5) mm², Push-in terminals
Terminal capacity (flexible)1 x (1 - 6) mm², Screw terminals; 2 x (1 - 6) mm², Screw terminals; 1 x (1 - 2.5) mm², Push-in terminals; 2 x (1 - 2.5) mm², Push-in terminals
Terminal capacity (flexible with ultrasonic welded cable end)1 x (1 - 6) mm², Screw terminals; 2 x (1 - 6) mm², Screw terminals; 1 x (1 - 2.5) mm², Push-in terminals; 2 x (1 - 2.5) mm², Push-in terminals
Terminal capacity (solid)1 x (1 - 6) mm², Screw terminals; 2 x (1 - 6) mm², Screw terminals; 1 x (1 - 2.5) mm², Push-in terminals; 2 x (1 - 2.5) mm², Push-in terminals
Terminal capacity (solid/stranded AWG)18 - 10, screw terminals; 20 - 14, Push-in terminals
Tightening torque1.7 Nm, Screw terminals, Main cable
Overload release current setting - max4 A
Overload release current setting - min2.5 A
Tripping characteristicOverload trigger: tripping class 10 A

Properties

MOQ1

Cross-References

Attached Documents