| Manufacturer part number (MPN) | PKZM0-10-PI |
| EAN / GTIN | 4015081972418 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 199157 |
| Depth | 75 mm |
| Height | 109 mm |
| Width | 45 mm |
| Weight | 0.348 kg |
| Certifications | IEC/EN 60947; VDE 0660; UL; CSA; IEC/EN 60947-4-1; UL 60947-4-1; CSA-C22.2 No. 60947-4-1-14; CE; UL File No.: E36332; UL Category Control No.: NLRV; CSA File No.: 165628; CSA Class No.: 3211-05 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Rated operational current for specified heat dissipation (In) | 10 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| Equipment heat dissipation, current-dependent Pvid | 6.48 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 2.2 W |
| Rated frequency - max | 60 Hz |
| Rated frequency - min | 50 Hz |
| Rated operational current (Ie) | 10 A |
| Rated operational power at AC-3e, 220/230 V, 50 Hz | 2.2 kW |
| Rated operational power at AC-3e, 380/400 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 440 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 500 V, 50 Hz | 4 kW |
| Rated operational power at AC-3e, 690 V, 50 Hz | 7.5 kW |
| Rated operational voltage (Ue) - max | 690 V |
| Rated operational voltage (Ue) - min | 690 V |
| Rated uninterrupted current (Iu) | 10 A |
| Actuator type | Turn button |
| Features | Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102) |
| Functions | Motor protection; Phase failure sensitive |
| Number of poles | Three-pole |
| Connection | Push in terminals |
| Degree of protection | IP20 |
| Lifespan, electrical | 100,000 operations |
| Lifespan, mechanical | 100,000 Operations |
| Mounting Method | DIN rail (top hat rail) mounting optional |
| Mounting position | Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height. |
| Operating frequency | 40 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Motor protective circuit breaker |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Suitable for | Also motors with efficiency class IE3; Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA) |
| Temperature compensation | -5 - 40 °C to IEC/EN 60947, VDE 0660; ≤ 0.25 %/K, residual error for T > 40°; -25 - 55 °C, Operating range |
| Assigned motor power at 115/120 V, 60 Hz, 1-phase | 0.5 HP |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 230/240 V, 60 Hz, 1-phase | 1.5 HP |
| Assigned motor power at 230/240 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 7.5 HP |
| Assigned motor power at 575/600 V, 60 Hz, 3-phase | 10 HP |
| Rated short-circuit breaking capacity Ics at 400 V AC | 150 kA |
| Rated short-circuit breaking capacity Ics at 440 V AC | 50 kA |
| Rated short-circuit breaking capacity Ics at 500 V AC | 11 kA |
| Rated short-circuit breaking capacity Ics at 690 V AC | 2 kA |
| Rated short-circuit breaking capacity Icu at 400 V AC | 150 kA |
| Rated short-circuit breaking capacity Icu at 440 V AC | 50 kA |
| Rated short-circuit breaking capacity Icu at 500 V AC | 42 kA |
| Rated short-circuit breaking capacity Icu at 690 V AC | 3 kA |
| Short-circuit current rating (group protection) | 50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 150 A, 600 V High Fault, Fuse, SCCR (UL/CSA); 30 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA); 30 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA) |
| Short-circuit current rating (type E) | 50 kA, 600 Y/347 V, SCCR (UL/CSA); 65 kA, 240 V, SCCR (UL/CSA); 65 kA, 480 Y/277 V, SCCR (UL/CSA) |
| Short-circuit release | Basic device fixed 15.5 x Iu; ± 20% tolerance; 155 A, Irm |
| Switching capacity | 10 A, AC-3 up to 690 V |
| Stripping length (main cable) | 12 mm |
| Terminal capacity (flexible with unisolated ferrule) | 1 x (1 - 6) mm²; 2 x (1 - 6) mm² |
| Terminal capacity (flexible with ferrule) | 1 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-1; 2 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-1; 1 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-4; 2 x (1 - 4) mm², Push-in terminals, ferrule to DIN 46228-4 |
| Terminal capacity (flexible) | 1 x (1 - 6) mm²; 2 x (1 - 6) mm²; 1 x (1 - 6) mm², Push-in terminals; 2 x (1 - 6) mm², Push-in terminals |
| Terminal capacity (flexible with ultrasonic welded cable end) | 1 x (1 - 10) mm²; 2 x (1 - 6) mm² |
| Terminal capacity (solid) | 1 x (1 - 6) mm², Push-in terminals; 2 x (1 - 6) mm², Push-in terminals; 1 x (1 - 6) mm²; 2 x (1 - 6) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 8 |
| Overload release current setting - max | 10 A |
| Overload release current setting - min | 6.3 A |
| Tripping characteristic | Overload trigger: tripping class 10 A |