Switch-disconnector DMM-125/4/I5/C-B

Eaton · Switchgear & Protection · Safety Switches · Ireland · eaton.com
Part Number
DMM-125/4/I5/C-B  ·  HS 8536.50
Switch-disconnector DMM-125/4/I5/C-B

Eaton DMM-125/4/I5/C-B Switch-Disconnector, DMM, 125 A, 4 pole, with blue knap, cylinder lock, in CI-K5 enclosure.

Technical Specifications

Manufacturer part number (MPN)DMM-125/4/I5/C-B
EAN / GTIN4015081694419
Sales unitpcs
Eaton catalogue number172861
Depth280 mm
Height160 mm
Width200 mm
Weight2.465 kg
CertificationsIEC/EN 60947-3; IEC/EN 60204; KEMA; RoHS; Lloyds; VDE 0660; CE; EAC; IEC/EN 60947
Actuator colorOther
Actuator typeShort thumb-grip
Ambient operating temperature - max40 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - min-40 °C
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Equipment heat dissipation, current-dependent Pvid4.9 W
Heat dissipation per pole, current-dependent Pvid4.5 W
Rated operational current for specified heat dissipation (In)125 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)1000 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)528 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)336 A
Rated insulation voltage (Ui)1000 V
Rated operational current (Ie) at AC-21, 400 V, 415 V125 A
Rated operational current (Ie) at AC-21, 500 V125 A
Rated operational current (Ie) at AC-21, 690 V125 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V125 A
Rated operational current (Ie) at AC-22, 500 V125 A
Rated operational current (Ie) at AC-22, 690 V125 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V63 A
Rated operational current (Ie) at AC-23A, 500 V63 A
Rated operational current (Ie) at AC-23A, 690 V45 A
Rated operational power at AC-23A, 400 V, 50 Hz30 kW
Rated operational power at AC-23A, 500 V, 50 Hz45 kW
Rated operational power at AC-23A, 690 V, 50 Hz40 kW
Rated operational voltage (Ue) at AC - max690 V
Rated uninterrupted current (Iu)125 A
Uninterrupted currentRated uninterrupted current Iu is specified for max. cross-section.
FeaturesVersion as main switch; Version as maintenance-/service switch
Fitted withBlue knob
FunctionsInterlockable
Locking mechanismCylinder lock
Number of polesFour-pole
AccessoriesAuxiliary contact fitted by user.
Degree of protectionNEMA 12
Degree of protection (front side)IP65
Lifespan, mechanical10,000 Operations
Mounting methodSurface mounting
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product CategoryMain switch Switch-disconnector
Rated impulse withstand voltage (Uimp)6000 V
Safety parameter (EN ISO 13849-1)B10d values as per EN ISO 13849-1, table C.1
Suitable forGround mounting
Breaking current13.7 kA
Light-through energyMax. 134 kA²s
Rated conditional short-circuit current (Iq)50 kA; 30 kA at 415 V
Rated short-time withstand current (Icw)2.5 kA; 2,5 kA, Contacts, 1 second
Short-circuit protection rating125, Fuse, Contacts
Stripping length (main cable)21 mm
Terminal capacity6 - 70 mm², flexible with ferrules to DIN 46228
Tightening torque7 Nm, Screw terminals
Country of originUnited Kingdom

Properties

MOQ1

Cross-References