cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM38-11(220V50/60HZ)-PI

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM38-11(220V50/60HZ)-PI  ·  HS 8536.90
Contactor DILM38-11(220V50/60HZ)-PI

Eaton DILM38-11(220V50/60HZ)-PI Contactor, 3-pole, 380 V 400 V 18.5 kW, 1 N/O, 1 NC, 220 V 50/60 Hz, AC -Control, PI.

Technical Specifications

Manufacturer part number (MPN)DILM38-11(220V50/60HZ)-PI
EAN / GTIN4015081983742
HS code8536.90
Sales unitpcs
Eaton catalogue number199673
Depth115 mm
Height85 mm
Width45 mm
Weight0.441 kg
CertificationsVDE 0660; IEC/EN 60947
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)90 A
Conventional thermal current Ith (3-pole, enclosed)36 A
Conventional thermal current Ith at 55°C (3-pole, open)42 A
Conventional thermal current Ith of main contacts (1-pole, open)100 A
Rated breaking capacity at 220/230 V320 A
Rated breaking capacity at 380/400 V320 A
Rated breaking capacity at 500 V320 A
Rated breaking capacity at 660/690 V180 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)384 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V45 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V38 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V38 A
Rated operational current (Ie) at AC-3, 440 V38 A
Rated operational current (Ie) at AC-3, 500 V38 A
Rated operational current (Ie) at AC-3, 660 V, 690 V22.5 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V15 A
Rated operational current (Ie) at AC-4, 440 V15 A
Rated operational current (Ie) at AC-4, 500 V15 A
Rated operational current (Ie) at AC-4, 660 V, 690 V12 A
Rated operational current (Ie) at DC-1, 110 V40 A
Rated operational current (Ie) at DC-1, 220 V40 A
Rated operational current (Ie) at DC-1, 60 V40 A
Rated operational power at AC-3, 240 V, 50 Hz12 kW
Rated operational power at AC-3, 380/400 V, 50 Hz18.5 kW
Rated operational power at AC-3, 415 V, 50 Hz20 kW
Rated operational power at AC-4, 220/230 V, 50 Hz4 kW
Rated operational power at AC-4, 240 V, 50 Hz4.5 kW
Rated operational power at AC-4, 415 V, 50 Hz7.5 kW
Rated operational power at AC-4, 440 V, 50 Hz8 kW
Rated operational power at AC-4, 500 V, 50 Hz9 kW
Rated operational power at AC-4, 660/690 V, 50 Hz10 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Fitted withMirror contact
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionPush in terminals
Degree of protectionIP20
Lifespan, mechanical10,000,000 Operations (AC operated)
Operating frequency5000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage typeAC
Frame sizeFS2
Arcing time10 ms
Drop-out voltageAC operated: 0.6 - 0.3 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz62 VA, Dual-frequency coil in a cold state and 1.0 x Us; 58 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz62 VA, Dual-frequency coil in a cold state and 1.0 x Us; 58 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 50 Hz2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 60 Hz9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us; 6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max220 V
Rated control supply voltage (Us) at AC, 50 Hz - min220 V
Rated control supply voltage (Us) at AC, 60 Hz - max220 V
Rated control supply voltage (Us) at AC, 60 Hz - min220 V
Switching time (AC operated, make contacts, closing delay) - max22 ms
Switching time (AC operated, make contacts, closing delay) - min16 ms
Switching time (AC operated, make contacts, opening delay) - max14 ms
Switching time (AC operated, make contacts, opening delay) - min8 ms
Safe isolation400 V AC, Between coil and contacts, According to EN 61140; 400 V AC, Between the contacts, According to EN 61140
Short-circuit current rating (basic rating)5 kA, 125 A max. fuse CLASS RK5, SCCR (UL/CSA); 5 kA, 125 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA); 65 kA, 32 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V125 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V63 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V63 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V35 A gG/gL
Screwdriver size3 x 0.5 mm, Terminal screw; 3.0 x 0.5 mm, Terminal screw
Terminal capacity (flexible)2 x (0.5 - 2.5) mm²; 2 x (1-6) mm²; 1 x (0.5 - 2.5) mm²; 1 x (1 - 10) mm²
Terminal capacity (solid)1 x (1 - 6) mm²; 1 x (0.5 - 0.25) mm²; 2 x (1 - 6) mm²; 2 x (0.5 - 2.5) mm², Control circuit cables
Terminal capacity (flexible with ferrule)1 x (1 - 6) mm²; 2 x (1 - 4) mm²; 1 x (0.5 - 1.5) mm², Control circuit cables; 2 x (0.5 - 1.5) mm², Main cables
Terminal capacity (solid/stranded AWG)20 - 14; 18 - 8, Main cables

Properties

MOQ1

Cross-References

Attached Documents