cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM8-11(RDC24)-PI

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM8-11(RDC24)-PI  ·  HS 8536.90
Contactor DILM8-11(RDC24)-PI

Eaton DILM8-11(RDC24)-PI Contactor, 3-pole, 380 V 400 V 3 KW, 1 N/O, 1 NC, RDC 24: 24 - 27 V DC, DC -Control, PI.

Technical Specifications

Manufacturer part number (MPN)DILM8-11(RDC24)-PI
EAN / GTIN4015081973521
HS code8536.90
Sales unitpcs
Eaton catalogue number199268
Depth115 mm
Height85 mm
Width45 mm
Weight0.546 kg
CertificationsVDE 0660; IEC/EN 60947; UL Listed; CSA certified; UL Category Control No.: NLDX; CE marking; UL File No.: E29096; CSA Class No.: 2411-03
3211-04; CSA File No.012528
Catalog NotesAlso tested according to AC-3e.
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Connection to SmartWire-DTYes; In conjunction with DIL-SWD SmartWire DT contactor module
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)80 A
Conventional thermal current Ith (3-pole, enclosed)32 A
Conventional thermal current Ith at 55°C (3-pole, open)37 A
Conventional thermal current Ith of main contacts (1-pole, open)88 A
Heat dissipation capacity Pdiss0 W
Rated breaking capacity at 220/230 V70 A
Rated breaking capacity at 380/400 V70 A
Rated breaking capacity at 500 V50 A
Rated breaking capacity at 660/690 V40 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)112 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V40 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V8 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V8 A
Rated operational current (Ie) at AC-3
440 V8 A
Rated operational current (Ie) at AC-3
500 V5 A
Rated operational current (Ie) at AC-3, 660 V
690 V4 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V5 A
Rated operational current (Ie) at AC-4
440 V5 A
Rated operational current (Ie) at AC-4
500 V4.5 A
Rated operational current (Ie) at AC-4, 660 V
Rated operational power at AC-3, 240 V
50 Hz2.2 kW
Rated operational power at AC-3, 380/400 V
50 Hz3 kW
Rated operational power at AC-3, 415 V
50 Hz3.9 kW
Rated operational power at AC-4, 220/230 V
50 Hz1 kW
Rated operational power at AC-4, 240 V
50 Hz1.5 kW
Rated operational power at AC-4, 415 V
50 Hz2.3 kW
Rated operational power at AC-4, 440 V
50 Hz2.4 kW
Rated operational power at AC-4, 500 V
50 Hz2.5 kW
Rated operational power at AC-4, 660/690 V
50 Hz2.9 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Fitted withMirror contact; Suppressor circuit in actuating electronics
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionPush in terminals
Degree of protectionIP20
Lifespan, mechanical10,000,000 Operations (DC operated)
Operating frequency5000 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeDC
Frame sizeFS2
Arcing time10 ms
Duty factor100 %
Pick-up voltage0.7 - 1.2 V DC x Uc; 0.7 - 1.2 V DC x Us; 24 - 27 V DC (RDC 24)
Power consumption (pick-up) at DC12 W
Power consumption (sealing) at DC0.9 W
Rated control supply voltage (Us) at DC - max27 V
Rated control supply voltage (Us) at DC - min27 V
Switching time (DC operated, make contacts, closing delay) - max47 ms
Switching time (DC operated, make contacts, opening delay) - max30 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase0.25 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase1.5 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase1 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase2 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase3 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase5 HP
Safe isolation400 V AC, Between the contacts, According to EN 61140; 400 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)5 kA, 125 A max. fuse CLASS RK5, SCCR (UL/CSA); 5 kA, 125 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA); 65 kA, 32 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA)
Screwdriver size3 x 0.5 mm, Terminal screw; 3.0 x 0.5 mm, Terminal screw
Terminal capacity (flexible)1 x (0.5 - 2.5) mm²; 1 x (1 - 10) mm²; 2 x (1-6) mm²; 2 x (0.5 - 2.5) mm²
Terminal capacity (solid)2 x (1 - 6) mm²; 2 x (0.5 - 2.5) mm², Control circuit cables; 1 x (0.5 - 0.25) mm²; 1 x (1 - 6) mm²
Terminal capacity (flexible with ferrule)1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm²
Terminal capacity (solid/stranded AWG)20 - 14; 18 - 8, Main cables

Properties

MOQ1

Cross-References

Attached Documents