| Manufacturer part number (MPN) | DILM14-11(220V50/60HZ)-PI |
| EAN / GTIN | 4015081983667 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 199665 |
| Depth | 115 mm |
| Height | 85 mm |
| Width | 45 mm |
| Weight | 0.441 kg |
| Certifications | IEC/EN 60947; VDE 0660 |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Connection to SmartWire-DT | No |
| Number of main contacts (normally open contact) | 3 |
| Number of auxiliary contacts (normally closed contacts) | 1 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Number of contacts (normally closed) as main contact | 0 |
| Conventional thermal current Ith (1-pole, enclosed) | 80 A |
| Conventional thermal current Ith (3-pole, enclosed) | 32 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 37 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 88 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) | 14 A at AC-3, 220/230 V |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 40 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 14 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 14 A |
| Rated operational current (Ie) at AC-3, 440 V | 14 A |
| Rated operational current (Ie) at AC-3, 500 V | 10 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 7 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 7 A |
| Rated operational current (Ie) at AC-4, 440 V | 7 A |
| Rated operational current (Ie) at AC-4, 500 V | 6 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 5 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 3.5 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 5.5 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 7 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 2 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 2.2 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 3.4 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 3.6 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 3.5 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 4.4 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
| Fitted with | Mirror contact |
| Number of poles | Three-pole |
| Application | Contactors for Motors |
| Connection | Push in terminals |
| Degree of protection | IP20 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 5000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Voltage type | AC |
| Frame size | FS2 |
| Arcing time | 10 ms |
| Drop-out voltage | AC operated: 0.6 - 0.3 x UC, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc |
| Power consumption, pick-up, 50 Hz | 58 VA, Dual-frequency coil in a cold state and 1.0 x Us; 62 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, pick-up, 60 Hz | 62 VA, Dual-frequency coil in a cold state and 1.0 x Us; 58 VA, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 50 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz | 6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 220 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 220 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 220 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 220 V |
| Switching time (AC operated, make contacts, closing delay) - max | 22 ms |
| Switching time (AC operated, make contacts, closing delay) - min | 16 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 14 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 8 ms |
| Safe isolation | 400 V AC, Between the contacts, According to EN 61140; 400 V AC, Between coil and contacts, According to EN 61140 |
| Short-circuit current rating (basic rating) | 5 kA, 125 A max. fuse CLASS RK5, SCCR (UL/CSA); 5 kA, 125 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA); 65 kA, 32 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 70 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 30 A CLASS RK5, SCCR (UL/CSA) |
| Screwdriver size | 3.0 x 0.5 mm, Terminal screw; 3 x 0.5 mm, Terminal screw |
| Terminal capacity (flexible) | 1 x (0.5 - 2.5) mm²; 2 x (0.5 - 2.5) mm²; 2 x (1-6) mm²; 1 x (1 - 10) mm² |
| Terminal capacity (solid) | 1 x (0.5 - 0.25) mm²; 1 x (1 - 6) mm²; 2 x (1 - 6) mm²; 2 x (0.5 - 2.5) mm², Control circuit cables |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 20 - 14; 18 - 8, Main cables |