cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM15-10(24VDC)-PI

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM15-10(24VDC)-PI  ·  HS 8536.90
Contactor DILM15-10(24VDC)-PI

Eaton DILM15-10(24VDC)-PI Contactor, 3-pole, 380 V 400 V 7.5 kW, 1 N/O, 24 V DC, DC -Control, PI.

Technical Specifications

Manufacturer part number (MPN)DILM15-10(24VDC)-PI
EAN / GTIN4015081973378
HS code8536.90
Sales unitpcs
Eaton catalogue number199253
Depth75 mm
Height68 mm
Width45 mm
Weight0.285 kg
CertificationsIEC/EN 60947; VDE 0660; UL Listed; CSA certified; UL Category Control No.: NLDX; CE marking; UL File No.: E29096; CSA Class No.: 2411-03
3211-04; CSA File No.012528
Catalog NotesContacts according to EN 50012
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTYes; In conjunction with DIL-SWD SmartWire DT contactor module
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally open contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)45 A
Conventional thermal current Ith (3-pole, enclosed)18 A
Conventional thermal current Ith at 55°C (3-pole, open)21 A
Conventional thermal current Ith of main contacts (1-pole, open)50 A
Equipment heat dissipation, current-dependent Pvid2.4 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0.8 W
Static heat dissipation, non-current-dependent Pvs4.5 W
Rated breaking capacity at 220/230 V124 A
Rated breaking capacity at 380/400 V124 A
Rated breaking capacity at 500 V100 A
Rated breaking capacity at 660/690 V70 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)155 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V22 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V15.5 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V15.5 A
Rated operational current (Ie) at AC-3
440 V15.5 A
Rated operational current (Ie) at AC-3
500 V12.5 A
Rated operational current (Ie) at AC-3, 660 V
690 V9 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V7 A
Rated operational current (Ie) at AC-4
440 V7 A
Rated operational current (Ie) at AC-4
500 V6 A
Rated operational current (Ie) at AC-4, 660 V
690 V5 A
Rated operational current (Ie) at DC-1
110 V20 A
Rated operational current (Ie) at DC-1
220 V15 A
Rated operational current (Ie) at DC-1
60 V20 A
Rated operational power at AC-3, 240 V
50 Hz4.6 kW
Rated operational power at AC-3, 380/400 V
50 Hz7.5 kW
Rated operational power at AC-3, 415 V
50 Hz8 kW
Rated operational power at AC-4, 220/230 V
50 Hz2 kW
Rated operational power at AC-4, 240 V
50 Hz2.2 kW
Rated operational power at AC-4, 415 V
50 Hz3.4 kW
Rated operational power at AC-4, 440 V
50 Hz3.6 kW
Rated operational power at AC-4, 500 V
50 Hz3.5 kW
Rated operational power at AC-4, 660/690 V
50 Hz4.4 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Fitted withBuilt-in suppressor circuit
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionPush in terminals
Degree of protectionIP20
Lifespan, mechanical10,000,000 Operations (DC operated)
Operating frequency5000 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)6000 V AC
Resistance per pole4.6 mΩ
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage typeDC
Frame sizeFS1
Arcing time10 ms
Duty factor100 %
Pick-up voltage0.85 - 1.1 V AC x Uc; 0.7 - 1.3 V DC x Uc (without auxiliary contact module and at ambient air temperature + 40 °C); 0.8 - 1.1 V DC x Uc; 0.85 - 1.1 V DC x Uc (only with auxiliary contact module with 3 or more N/C contacts)
Power consumption (pick-up) at DC4.5 W
Power consumption (sealing) at DC4.5 W
Rated control supply voltage (Us) at DC - max24 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (DC operated, make contacts, closing delay) - max31 ms
Switching time (DC operated, make contacts, opening delay) - max12 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase1 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase5 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase3 HP
Assigned motor power at 230/240 V, 60 Hz
Assigned motor power at 460/480 V, 60 Hz
3-phase10 HP
Assigned motor power at 575/600 V, 60 Hz
Safe isolation400 V AC, Between the contacts, According to EN 61140; 400 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)5 kA, 45 A max. fuse, SCCR (UL/CSA); 5 kA, 45 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 60 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 60 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 25 A CLASS RK5 max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V63 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V50 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V20 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V20 A gG/gL
Special purpose rating of definite purpose rating15 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 90 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control9 A, 600 V 60 Hz 3-ph, (UL/CSA); 11 A, 480 V 60 Hz 3-ph, (UL/CSA); 2 HP, 200 V 60 Hz 3-ph, (UL/CSA); 3 HP, 240 V 60 Hz 3-ph, (UL/CSA); 7.8 A, 200 V 60 Hz 3-ph, (UL/CSA); 7.5 HP, 600 V 60 Hz 3-ph, (UL/CSA); 9.6 A, 240 V 60 Hz 3-ph, (UL/CSA); 7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)10 A, FLA 480 V 60 Hz 3phase; (CSA); 10 A, FLA 600 V 60 Hz 3phase; (CSA); 60 A, LRA 480 V 60 Hz 3phase; (CSA); 60 A, LRA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating20 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 20 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps14 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 14 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps20 A (480V 60Hz 3phase, 277V 60Hz 1phase); 20 A (600V 60Hz 3phase, 347V 60Hz 1phase)
Switching capacity (auxiliary contacts, general use)1 A, 250 V DC, (UL/CSA); 10 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600, AC operated (UL/CSA); P300, DC operated (UL/CSA)
Switching capacity (main contacts, general use)20 A, Maximum motor rating (UL/CSA)
Screwdriver size3.0 x 0.5 mm, Terminal screw; 3 x 0.5 mm, Terminal screw
Stripping length (main cable)10 mm
Terminal capacity (flexible with unisolated ferrule)1 x (0.5 - 2.5) mm²; 2 x (0.5 - 2.5) mm²
Terminal capacity (flexible)1 x (0.5 - 2.5) mm²; 2 x (0.5 - 2.5) mm²
Terminal capacity (flexible with ultrasonic welded cable end)1 x (0.5 - 2.5) mm²; 2 x (0.5 - 2.5) mm²
Terminal capacity (solid)1 x (0.5 - 2.5) mm²; 2 x (0.5 - 2.5) mm²
Terminal capacity (flexible with ferrule)1 x (0.5 - 2.5) mm²; 2 x (0.5 - 1.5) mm²
Terminal capacity (solid/stranded AWG)20 - 14

Properties

MOQ1

Cross-References

Attached Documents