DS7 Soft starter, SWD, 135AMP (DS7-34DSX135N0-D)

Eaton · Drives & Controllers · Soft Starters · Ireland · eaton.com
Part Number
DS7-34DSX135N0-D  ·  HS 8537.10
DS7 Soft starter, SWD, 135AMP (DS7-34DSX135N0-D)

Technical Specifications

Manufacturer part number (MPN)DS7-34DSX135N0-D
EAN / GTIN4015081317721
Sales unitpcs
Eaton catalogue number134957
Depth195 mm
Height215 mm
Width108 mm
Weight3.7 kg
CompliancesCE Marked; C-Tick Compliant
CertificationsUL Listed; EN 60947-4-2; IEC 60947-4-2; CSA Certified; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05; C-Tick; IEC/EN 60947-4-2; CSA22.2-14; CSA; UkrSEPRO; UL 508; GB 14048.6; CE; UL
Mounting positionVertical
Shock resistance8 g, 11 ms, Mechanical
Vibration resistance2M2 to EN 60721-3-2
AltitudeAbove 1000 m with 1 % derating per 100 m; Max. 2000 m
Ambient operating temperature - max40 °C
Ambient storage temperature - max60 °C
Ambient operating temperature - min-5 °C
Ambient storage temperature - min-25 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-3
Current consumption50 mA, Control circuit, Regulator supply; 1.6 mA, Control circuit, Digital inputs, External 24 V; 0,6 A/50 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
Drop-out time350 ms, Control circuit, Digital Inputs, DC operated
Drop-out voltage0 - 3 V, DC operated
Pick-up time250 ms at DC
Pick-up voltage17.3 - 27 V DC
Rated control supply voltage (Us) at DC - max24 V
Rated control supply voltage (Us) at DC - min24 V
Equipment heat dissipation, current-dependent Pvid24 W
Rated operational current for specified heat dissipation (In)135 A
Static heat dissipation, non-current-dependent Pvs24 W
Fault memory8 Faults
Fitted withInternal bypass; Internal bypass contacts
FunctionsPotential isolation between power and control sections; Suppression of closing transients; Suppression of DC components for motors; Soft start function; Current limitation, with PKE; Min. ramp time 1 s - fast switching (semiconductor contactor); Single direction
InterfacesSmartWire-DT (built-in)
ClassOther
Connection to SmartWire-DTYes
Degree of protectionIP20; NEMA 1
Frame size3; 4; FS4
Mains voltage - max480 V
Mains voltage - min200 V
Overvoltage categoryII
Pollution degree2
Product categorySmartWire-DT slave
Radio interference classClass B (EN 55011)
Suitable forBranch circuits, (UL/CSA)
TypeSoft starter for three-phase loads
Voltage typeDC
Number of outputs2 Relay Outputs (TOR, Ready)
Output voltage250 V AC (relay outputs)
ProtectionFinger and back-of-hand proof, Protection against direct contact
Rated control voltage (Uc)24 V DC; 24 V DC (-15 %/+10 %) or via SmartWire-DT
Rated operational current (Ie) at AC-111 A
Overload cycleAC-53a: 3 - 5: 75 - 10
Rated operational current (Ie) at AC-53135 A
Rated operational voltage (Ue) - max480 V
Rated operational voltage (Ue) - min230 V
Short-circuit protection rating3 x 170M4010, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths; NZMN2-M160, Type “1” coordination, Main conducting paths
Supply frequency50/60 Hz, fLN, Main circuit
Voltage rating - max480 V
Assigned motor power at 200/208 V, 60 Hz, 3-phase40 HP
Assigned motor power at 220/230 V, 60 Hz, 3-phase50 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase100 HP
Rated operational power at 220/230 V, 50 Hz30 kW
Rated operational power at 400 V, 50 Hz75 kW
Application1-phase motors: No 3-phase motors: Yes Soft starting of three-phase asynchronous motors
Current limitation(0 - 8) x Ie, Soft start function
Delay time0 - 30 s, Soft start function, Ramp times
Ramp/run-up time1 - 30 s
Start voltageMin. 30 %, Soft start function, Start voltage = turn-off voltage; Max. 100 %, Soft start function, Start voltage = turn-off voltage
Screwdriver sizePZ2, 1 x 6 mm, Terminal screw, Standard screwdriver; 0.6 x 3.5 mm, Terminal screws, Control circuit cables
Terminal capacity (copper band)2 x 9 x 0.8 mm, Main cables; 10 x 16 x 0.8 mm, Main cables
Terminal capacity (flexible with ferrule)1 x (0.5 - 1.5) mm², Control circuit cables; 2 x (0.5 - 0.75) mm², Control circuit cables
Terminal capacity (solid)1 x (0.5 - 2.5) mm², Control circuit cables; 2 x (0.5 - 1.0) mm², Control circuit cables; 1 x (4 - 185) mm², Main cables; 2 x (4 - 70) mm², Main cables
Terminal capacity (solid/stranded AWG)1 x (12 - 350 kcmil), Main cables; 2 x (12 - 00), Main cables; 2 x (21 - 18), Control circuit cables; 1 x (21 - 14), Control circuit cables
Terminal capacity (stranded)1 x (0.5 - 1.5) mm², Control circuit cables; 2 x (0.5 - 1.0) mm², Control circuit cables; 2 x (4 - 70) mm², Main cables; 1 x (4 - 185) mm², Main cables
Tightening torque14 Nm (> 10 mm²); 0.4 Nm, Screw terminals, Control circuit cables; 5 Nm (≤ 10 mm²)
With displayNo
Rated operating voltage Ue230–460 V
Rated control supply voltage DC24 V
Rated operation current Ie at 40 °C Tu135 A
Rated power three-phase motor, inline, at 230 V30 kW
Rated power three-phase motor, inline, at 400 V75 kW
Rated surrounding temperature without derating40 °C
Integrated motor overload protectionNo
Voltage type for actuatingDC
Internal bypassYes
Torque controlNo
Country of originUnited Kingdom

Properties

MOQ1

Cross-References