| Manufacturer part number (MPN) | DILM185A/22(RAC440) |
| EAN / GTIN | 4015081363162 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 139538 |
| Depth | 158 mm |
| Height | 190 mm |
| Width | 140 mm |
| Weight | 3.54 kg |
| Certifications | IEC/EN 60947-4-1; UL 60947-4-1; UL File No.: E29096; CE; UL Category Control No.: NLDX; VDE 0660; CSA; CSA File No.: 2389068; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947; CSA Class No.: 3211-04; UL |
| Catalog Notes | Contacts according to EN 50012 Also tested according to AC-3e up to 500 V. Also suitable for motors with efficiency class IE3. Conventional thermal current Ith of main contacts (1-pole, open) at 60° |
| Conventional thermal current Ith (1-pole, enclosed) | 613 A |
| Conventional thermal current Ith (3-pole, enclosed) | 245 A |
| Conventional thermal current Ith at 40°C (3-pole, open) | 337 A |
| Conventional thermal current Ith at 50°C (3-pole, open) | 301 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 287 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 275 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 688 A |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Number of auxiliary contacts (normally closed contacts) | 2 |
| Number of auxiliary contacts (normally open contacts) | 2 |
| Number of contacts (normally closed contacts) | 2 |
| Number of contacts (normally open contacts) | 2 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 5.33 W |
| Rated operational current for specified heat dissipation (In) | 185 A |
| Static heat dissipation, non-current-dependent Pvs | 2.1 W |
| Inrush current | Max. 30 x Ie (peak) |
| Rated breaking capacity at 1000 V | 760 A |
| Rated breaking capacity at 220/230 V | 2250 A |
| Rated breaking capacity at 380/400 V | 2250 A |
| Rated breaking capacity at 500 V | 2250 A |
| Rated breaking capacity at 660/690 V | 2250 A |
| Rated insulation voltage (Ui) | 1000 V |
| Rated making capacity (cos phi to IEC/EN 60947) | 2700 A |
| Rated operational current (Ie) | 133 A at 690 V (Individual compensation, three-phase capacitors, open); 220 A at up to 525 V (Individual compensation, three-phase capacitors, open) |
| Rated operational current (Ie) at AC-3 |
| 1000 V | 76 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V |
| 240 V | 185 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V |
| 415 V | 185 A |
| Rated operational current (Ie) at AC-3 |
| 440 V | 185 A |
| Rated operational current (Ie) at AC-3 |
| 500 V | 185 A |
| Rated operational current (Ie) at AC-3, 660 V |
| 690 V | 150 A |
| Rated operational current (Ie) at AC-4 |
| 1000 V | 55 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V |
| 240 V | 136 A |
| Rated operational current (Ie) at AC-4 |
| 440 V | 136 A |
| Rated operational current (Ie) at AC-4 |
| 500 V | 136 A |
| Rated operational current (Ie) at AC-4, 660 V |
| 690 V | 110 A |
| Rated operational power at AC-3, 1000 V |
| 50 Hz | 108 kW |
| Rated operational power at AC-3, 240 V |
| 50 Hz | 62 kW |
| Rated operational power at AC-3, 380/400 V |
| 50 Hz | 90 kW |
| Rated operational power at AC-3, 415 V |
| 50 Hz | 110 kW |
| Rated operational power at AC-3, 440 V |
| 50 Hz | 115 kW |
| Rated operational power at AC-3, 500 V |
| 50 Hz | 132 kW |
| Rated operational power at AC-3, 690 V |
| 50 Hz | 140 kW |
| Rated operational power at AC-4, 1000 V |
| 50 Hz | 77 kW |
| Rated operational power at AC-4, 220/230 V |
| 50 Hz | 41 kW |
| Rated operational power at AC-4, 240 V |
| 50 Hz | 45 kW |
| Rated operational power at AC-4, 415 V |
| 50 Hz | 80 kW |
| Rated operational power at AC-4, 440 V |
| 50 Hz | 85 kW |
| Rated operational power at AC-4, 500 V |
| 50 Hz | 96 kW |
| Rated operational power at AC-4, 660/690 V |
| 50 Hz | 102 kW |
| Rated operational voltage (Ue) at AC - max | 1000 V |
| Safe isolation | 1000 V AC, Between coil and contacts, According to EN 61140 |
| Special purpose rating of definite purpose rating | 1680 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 2016 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 336 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 280 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Accessories | Fitting options auxiliary contacts: on the side: 2 x DILM1000-XHI(V)11-SI; 2 x DILM1000-XHI11-SA |
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Electromagnetic compatibility | Designed for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression. |
| Fitted with | Suppressor circuit in actuating electronics |
| Lifespan, electrical | 100,000 Operations (at Condensor operation) |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 200 Operations/h; 3000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Shock resistance | 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces |
| Voltage type | AC |
| Drop-out voltage | AC operated: 0.25 x US max - 0.6 x US min |
| AC operated; AC operated | 0.2 x US max - 0.4 x US min, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.15 V AC x Us |
| Power consumption, pick-up |
| 50 Hz | 210 VA, Pull-in power, Coil in a cold state and 1.0 x Us; 180 W, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, pick-up |
| 60 Hz | 180 W, Pull-in power, Coil in a cold state and 1.0 x Us; 210 VA, Pull-in power, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing |
| 50 Hz | 2.1 W, Coil in a cold state and 1.0 x Us; 2.6 VA, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing |
| 60 Hz | 2.6 VA, Coil in a cold state and 1.0 x Us; 2.1 W, Coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at AC |
| 50 Hz - max | 440 V |
| Rated control supply voltage (Us) at AC |
| 50 Hz - min | 380 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - max | 440 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - min | 380 V |
| Switching time (AC operated, make contacts, closing delay) - max | 60 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 40 ms |
| Assigned motor power at 200/208 V, 60 Hz |
| 3-phase | 50 HP |
| Assigned motor power at 230/240 V, 60 Hz |
| 3-phase | 60 HP |
| Assigned motor power at 460/480 V, 60 Hz |
| 3-phase | 125 HP |
| Assigned motor power at 575/600 V, 60 Hz |
| 3-phase | 150 HP |
| Short-circuit current rating (basic rating) | 700 A, max. Fuse, SCCR (UL/CSA); 800 A, max. CB, SCCR (UL/CSA); 10 kA, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 350 A, max. CB, SCCR (UL/CSA); 600 A, Class J, max. Fuse, SCCR (UL/CSA); 65 kA, CB, SCCR (UL/CSA); 100 kA, Fuse, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 350 A, max. CB, SCCR (UL/CSA); 600 A, Class J, max. Fuse, SCCR (UL/CSA); 50 kA, CB, SCCR (UL/CSA); 100 kA, Fuse, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 1000 V | 200 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 400 V | 400 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 315 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 1000 V | 160 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 315 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 250 A gG/gL |
| Switching capacity (auxiliary contacts, general use) | 15 A, 600 V AC, (UL/CSA); 1 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA); A600, AC operated (UL/CSA) |
| Switching capacity (main contacts, general use) | 250 A, Maximum motor rating (UL/CSA) |
| Screw size | M10, Terminal screw, Main connections; M3.5, Terminal screw, Control circuit cables |
| Screwdriver size | 2, Terminal screw, Control circuit cables, Pozidriv screwdriver |
| Terminal capacity (busbar) | 32 mm width, Main connection |
| Terminal capacity (copper band) | Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks |
| Terminal capacity (flexible with cable lug) | 50 - 185 mm² |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) | 1/0 - 350 MCM, Main cables; 18 - 14, Control circuit cables |
| Terminal capacity (stranded with cable lug) | 50 - 185 mm² |
| Tightening torque | 24 Nm, Main cable connection screw/bolt; 1.2 Nm, Screw terminals, Control circuit cables |
| Width across flats | 16 mm |