| Manufacturer part number (MPN) | DS7-342SX012N0-N |
| EAN / GTIN | 4015081317448 |
| Sales unit | pcs |
| Eaton catalogue number | 134929 |
| Depth | 94 mm |
| Height | 130 mm |
| Width | 45 mm |
| Weight | 0.35 kg |
| Certifications | IEC/EN 60947-4-2; CSA File No.: 2511305; CSA Class No.: 321106; CSA-C22.2 No 14-05; CSA; UL 508; UL; CE; CSA22.2-14; CSA-C22.2 No 0-M91; C-Tick; GB 14048.6; UkrSEPRO; UL File No.: E251034 |
| Mounting position | Vertical |
| Shock resistance | 8 g, 11 ms, Mechanical |
| Vibration resistance | 2M2 to EN 60721-3-2 |
| Altitude | Above 1000 m with 1 % derating per 100 m; Max. 2000 m |
| Ambient operating temperature - max | 40 °C |
| Ambient storage temperature - max | 60 °C |
| Ambient operating temperature - min | -5 °C |
| Ambient storage temperature - min | -25 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-3; Damp heat, cyclic, to IEC 60068-2-30 |
| Current consumption | 50 mA, Control circuit, Regulator supply; 1.6 mA, Control circuit, Digital inputs, External 24 V |
| Drop-out time | 350 ms, Control circuit, Digital Inputs, AC operated |
| Drop-out voltage | AC operated: 0 - 15 V, AC operated |
| Pick-up time | 250 ms at AC |
| Pick-up voltage | 108 - 253 V AC |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 110 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 230 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 110 V |
| Equipment heat dissipation, current-dependent Pvid | 0.6 W |
| Rated operational current for specified heat dissipation (In) | 12 A |
| Static heat dissipation, non-current-dependent Pvs | 0.6 W |
| Fitted with | Internal bypass; Internal bypass contacts |
| Functions | Suppression of DC components for motors; Suppression of closing transients; Min. ramp time 1 s - fast switching (semiconductor contactor); Potential isolation between power and control sections; Single direction; Soft start function |
| Class | Other |
| Connection to SmartWire-DT | No |
| Degree of protection | IP20; NEMA 1 |
| Frame size | FS1 |
| Mains voltage - max | 480 V |
| Mains voltage - min | 200 V |
| Overvoltage category | II |
| Pollution degree | 2 |
| Radio interference class | Class A (EN 55011) |
| Suitable for | Branch circuits, (UL/CSA) |
| Type | Soft starter for three-phase loads |
| Voltage type | AC |
| Input current | 4 mA (at 230 V AC, Digital inputs) |
| Number of outputs | 1 Relay Output (TOR) |
| Output voltage | 110 - 230 V AC |
| Protection | Finger and back-of-hand proof, Protection against direct contact |
| Rated control voltage (Uc) | 110 - 230 V AC (-15 %/+10 %); 110 - 230 V AC |
| Rated operational current (Ie) at AC-11 | 1 A |
| Overload cycle | AC-53a: 3 - 5: 75 - 10 |
| Rated operational current (Ie) at AC-53 | 12 A |
| Rated operational voltage (Ue) - max | 480 V |
| Rated operational voltage (Ue) - min | 230 V |
| Short-circuit protection rating | 3 x 170M1362, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths; PKM0-12 (+ CL-PKZ0), Type “1” coordination, Main conducting paths |
| Supply frequency | 50/60 Hz, fLN, Main circuit |
| Voltage rating - max | 480 V |
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 220/230 V, 60 Hz, 3-phase | 3 HP |
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 10 HP |
| Rated operational power at 220/230 V, 50 Hz | 3 kW |
| Rated operational power at 400 V, 50 Hz | 5.5 kW |
| Application | 1-phase motors: No 3-phase motors: Yes Soft starting of three-phase asynchronous motors |
| Delay time | 0 - 30 s, Soft start function, Ramp times |
| Ramp/run-up time | 1 - 30 s |
| Start voltage | Max. 100 %, Soft start function, Start voltage = turn-off voltage; Min. 30 %, Soft start function, Start voltage = turn-off voltage |
| Screwdriver size | PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver; 0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Main cables; 1 x (0.75 - 2.5) mm², Main cables |
| Terminal capacity (solid) | 1 x (0.75 - 4) mm², Main cables; 2 x (0.75 - 2.5) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 4) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) | 18 - 10, Control circuit cables; 18 - 10, Main cables |
| Tightening torque | 1.2 Nm; 1.2 Nm, Screw terminals, Control circuit cables |
| With display | No |
| Rated operating voltage Ue | 230–460 V |
| Rated control supply voltage AC 50 Hz | 110–230 V |
| Rated control supply voltage AC 60 Hz | 110–230 V |
| Rated operation current Ie at 40 °C Tu | 12 A |
| Rated power three-phase motor, inline, at 230 V | 3 kW |
| Rated power three-phase motor, inline, at 400 V | 5.5 kW |
| Rated surrounding temperature without derating | 40 °C |
| Integrated motor overload protection | No |
| Voltage type for actuating | AC |
| Internal bypass | Yes |
| Torque control | No |
| Country of origin | United Kingdom |