Contactor, lyslast, DILL20(230V50HZ) (DILL20(230V50HZ,240V60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILL20(230V50HZ,240V60HZ)  ·  HS 8536.90
Contactor, lyslast, DILL20(230V50HZ) (DILL20(230V50HZ,240V60HZ))

Eaton DILL20(230V50HZ,240V60HZ) DILL20 - Contactor for light, coil 230-240 VAC.

Technical Specifications

Manufacturer part number (MPN)DILL20(230V50HZ,240V60HZ)
EAN / GTIN4015081042258
HS code8536.90
Sales unitpcs
Package quantity64 pcs
Eaton catalogue number104408
Depth97 mm
Height85 mm
Width45 mm
Weight0.426 kg
CompliancesCE Marked
CertificationsIEC 60947-4-1; EN 60947-4-1; CSA Std. C22.2 No. 14-05; UL 508; VDE; CE; CSA Class No.: 3211-04; VDE 0660; CSA-C22.2 No. 60947-4-1-14; UL Category Control No.: NLDX; IEC/EN 60947; CSA File No.: 012528; CSA; IEC/EN 60947-4-1; UL 60947-4-1; UL; UL File No.: E29096
Shock resistance6.9 g, N/O main contact, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith at 60°C (3-pole, open)40 A
Equipment heat dissipation, current-dependent Pvid4.5 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid1.5 W
Rated operational current for specified heat dissipation (In)27 A
Static heat dissipation, non-current-dependent Pvs2.1 W
Permissible compensation capacity470 µF
Rated breaking capacity at 380/400 V320 A
Rated insulation voltage (Ui)690 V
Rated making capacity (cos phi to IEC/EN 60947)550 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V20 A
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Number of polesThree-pole
ApplicationContactors for lighting systems
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, electrical10,000 Operations
Lifespan, mechanical1,000,000 Operations (AC operated)
Operating frequency60 mechanical Operations/h (AC operated); 60 electrical Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryDILL Lighting contactors
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance per pole2.65 mΩ
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage typeAC
Drop-out voltageAC operated: 0.6 - 0.3 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, pick-up, 60 Hz67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max230 V
Rated control supply voltage (Us) at AC, 50 Hz - min230 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min240 V
Switching time (AC operated, make contacts, closing delay) - max22 ms
Switching time (AC operated, make contacts, closing delay) - min16 ms
Switching time (AC operated, make contacts, opening delay) - max14 ms
Switching time (AC operated, make contacts, opening delay) - min8 ms
Short-circuit current rating (basic rating)125 A, max. Fuse, SCCR (UL/CSA); 5 kA, SCCR (UL/CSA); 125 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, Fuse, SCCR (UL/CSA); 32 A, max. CB, SCCR (UL/CSA); 22 kA, CB, SCCR (UL/CSA); 125 A, Class J, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, Fuse, SCCR (UL/CSA); 32 A, max. CB, SCCR (UL/CSA); 125 A, Class J, max. Fuse, SCCR (UL/CSA); 22 kA, CB, SCCR (UL/CSA)
Short-circuit protection rating (type 2 coordination) at 400 V125 A gG/gL
Special purpose rating of tungsten incandescent lamps40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Switching capacity (main contacts, general use)40 A, Maximum motor rating (UL/CSA)

Properties

MOQ1

Cross-References

Attached Documents