Motor protection relay ZB150-70

Eaton · Switchgear & Protection · Overload Relays · Ireland · eaton.com
Part Number
ZB150-70  ·  HS 8536.30
Motor protection relay ZB150-70

Eaton ZB150-70 Motor Protection Relay 50-70A, 1N/O+1N/C.

Technical Specifications

Manufacturer part number (MPN)ZB150-70
EAN / GTIN4015082784638
Sales unitpcs
Eaton catalogue number278463
Depth134 mm
Height135 mm
Width118 mm
Weight1.208 kg
CertificationsUL File No.: E29184; UL; UL Category Control No.: NKCR; CE; CSA; CSA-C22.2 No. 60947-4-1-14; IEC/EN 60947; CSA File No.: 012528; CSA Class No.: 3211-03; IEC/EN 60947-4-1; VDE 0660; UL 60947-4-1
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Equipment heat dissipation, current-dependent Pvid21.6 W
Heat dissipation per pole, current-dependent Pvid7.2 W
Rated operational current for specified heat dissipation (In)70 A
Conventional thermal current Ith of auxiliary contacts (1-pole, open)6 A
Rated operational current (Ie) at AC-15, 120 V1.5 A
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V1.5 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V0.9 A
Rated operational current (Ie) at DC-13, 110 V0.4 A
Rated operational current (Ie) at DC-13, 220 V, 230 V0.2 A
Rated operational current (Ie) at DC-13, 24 V0.9 A
Rated operational current (Ie) at DC-13, 60 V0.75 A
Rated operational voltage (Ue) - max1000 V
Safe isolation440 V AC, Between main circuits, According to EN 61140; 240 V AC, Between auxiliary contacts, According to EN 61140; 440 V, Between auxiliary contacts and main contacts, According to EN 61140
Switching capacity (auxiliary contacts, pilot duty)B300 at opposite polarity, AC operated (UL/CSA); R300, DC operated (UL/CSA); B600 at opposite polarity, AC operated (UL/CSA)
Voltage rating - max600 VAC
FeaturesPhase-failure sensitivity (according to IEC/EN 60947, VDE 0660 Part 102); Reset pushbutton manual/auto; Trip-free release; Test/off button
Ambient operating temperature - max55 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
ClassCLASS 10 A / IEC 60947-4-1, 8.2.1.5.1.1. c) 4 min
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Degree of protectionIP00
Frame sizeZB150
Mounting methodDirect attachment; Direct mounting
Overload release current setting - max70 A
Overload release current setting - min50 A
Overvoltage categoryIII
Pollution degree3
Product categoryAccessories Overload relay ZB up to 150 A
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)4000 V (auxiliary and control circuits); 8000 V AC
Shock resistance10 g, Mechanical, Sinusoidal, Shock duration 10 ms
Suitable forBranch circuits, (UL/CSA)
Temperature compensationContinuous; ≤ 0.25 %/K, residual error for T > 40°
Short-circuit current rating (basic rating)250 A, max. Fuse, SCCR (UL/CSA); 10 kA, SCCR (UL/CSA); 250 A, max. CB, SCCR (UL/CSA)
Short-circuit protection rating250 A gG/gL, Fuse, Type “1” coordination; Max. 6 A gG/gL, fuse, without welding, Auxiliary and control circuits; 160 A gG/gL, Fuse, Type “2” coordination; Information on Type "1" and Type"2" coordination applies to 100 kA and 690 V
Screw sizeM3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main cables; 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
Screwdriver size1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver; 2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Stripping length (control circuit cable)8 mm
Stripping length (main cable)24 mm
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (4 - 70) mm², Main cables; 2 x (4 - 70) mm², Main cables; 1 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid)1 x (0.75 - 4) mm², Control circuit cables; 2 x (4 - 16) mm², Main cables; 1 x (4 - 16) mm², Main cables; 2 x (0.75 - 4) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)3/0, Main cables; 2 x (18 - 14), Control circuit cables
Terminal capacity (stranded)2 x (16 - 70) mm², Main cables; 1 x (16 - 70) mm², Main cables
Tightening torque10 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact1
Release classCLASS 10
Type of electrical connection of main circuitScrew connection
Max. rated operation voltage Ue1000 V
Adjustable current range50–70 A
Reset function inputNo
Reset function automaticYes
Reset function push-buttonYes
Country of originGermany

Properties

MOQ1

Cross-References