cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILM80(24V50/60HZ)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM80(24V50/60HZ)  ·  HS 8536.90
Contactor DILM80(24V50/60HZ)

Eaton DILM80(24V50/60HZ) Contactor 3-pole, 24 VAC.

Technical Specifications

Manufacturer part number (MPN)DILM80(24V50/60HZ)
EAN / GTIN4015082394066
HS code8536.90
Sales unitpcs
Eaton catalogue number239406
Depth160 mm
Height170 mm
Width90 mm
Weight2.18 kg
CertificationsUL 60947-4-1; CSA-C22.2 No. 60947-4-1-14; CSA Class No.: 2411-03
3211-04; CE; CSA File No.012528; UL File No.: E29096; UL; CSA; VDE 0660; IEC/EN 60947; UL Category Control No.: NLDX; IEC/EN 60947-4-1
Catalog NotesContacts according to EN 50012
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)200 A
Conventional thermal current Ith (3-pole, enclosed)80 A
Conventional thermal current Ith at 55°C (3-pole, open)94 A
Conventional thermal current Ith at 60°C (3-pole, open)90 A
Conventional thermal current Ith of main contacts (1-pole, open)225 A
Equipment heat dissipation, current-dependent Pvid9 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid3 W
Rated operational current for specified heat dissipation (In)80 A
Static heat dissipation, non-current-dependent Pvs5.8 W
Rated breaking capacity at 220/230 V800 A
Rated breaking capacity at 380/400 V800 A
Rated breaking capacity at 500 V800 A
Rated breaking capacity at 660/690 V650 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)1120 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V110 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V80 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V80 A
Rated operational current (Ie) at AC-3
440 V80 A
Rated operational current (Ie) at AC-3
500 V80 A
Rated operational current (Ie) at AC-3, 660 V
690 V65 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V40 A
Rated operational current (Ie) at AC-4
440 V40 A
Rated operational current (Ie) at AC-4
500 V40 A
Rated operational current (Ie) at AC-4, 660 V
690 V27 A
Rated operational current (Ie) at DC-1
110 V110 A
Rated operational current (Ie) at DC-1
220 V70 A
Rated operational current (Ie) at DC-1
60 V110 A
Rated operational power at AC-3, 240 V
50 Hz27.5 kW
Rated operational power at AC-3, 380/400 V
50 Hz37 kW
Rated operational power at AC-3, 415 V
50 Hz48 kW
Rated operational power at AC-3, 440 V
50 Hz51 kW
Rated operational power at AC-3, 500 V
50 Hz58 kW
Rated operational power at AC-3, 690 V
50 Hz63 kW
Rated operational power at AC-4, 220/230 V
50 Hz11.5 kW
Rated operational power at AC-4, 240 V
50 Hz13 kW
Rated operational power at AC-4, 415 V
50 Hz24 kW
Rated operational power at AC-4, 440 V
50 Hz25 kW
Rated operational power at AC-4, 500 V
50 Hz29 kW
Rated operational power at AC-4, 660/690 V
50 Hz26 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical7,000,000 Operations (Coil 50/60 Hz); 10,000,000 Operations (AC operated)
Operating frequency3600 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole0.6 mΩ
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage typeAC
Frame sizeFS4
Arcing time15 ms
Drop-out voltageAC operated: 0.6 - 0.3 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.1 V AC x Uc
Power consumption, pick-up
50 Hz328 VA, Dual-frequency coil in a cold state and 1.0 x Us; 372 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up
60 Hz372 VA, Dual-frequency coil in a cold state and 1.0 x Us; 328 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing
50 Hz5.8 W, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing
60 Hz22.6 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 5.8 W, Dual-frequency coil in a cold state and 1.0 x Us; 37.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC
50 Hz - max24 V
Rated control supply voltage (Us) at AC
50 Hz - min24 V
Rated control supply voltage (Us) at AC
60 Hz - max24 V
Rated control supply voltage (Us) at AC
60 Hz - min24 V
Switching time (AC operated, make contacts, closing delay) - max20 ms
Switching time (AC operated, make contacts, closing delay) - min14 ms
Switching time (AC operated, make contacts, opening delay) - max14 ms
Switching time (AC operated, make contacts, opening delay) - min9 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase7.5 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase25 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase15 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase30 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase60 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase75 HP
Safe isolation690 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 600 A max. fuse, SCCR (UL/CSA); 10 kA, 600 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA); 65 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V200 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V160 A gG/gL
Special purpose rating of definite purpose rating480 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 80 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control50 HP, 480 V 60 Hz 3-ph, (UL/CSA); 60 HP, 600 V 60 Hz 3-ph, (UL/CSA); 62 A, 600 V 60 Hz 3-ph, (UL/CSA); 62.1 A, 200 V 60 Hz 3-ph, (UL/CSA); 20 HP, 200 V 60 Hz 3-ph, (UL/CSA); 68 A, 240 V 60 Hz 3-ph, (UL/CSA); 65 A, 480 V 60 Hz 3-ph, (UL/CSA); 25 HP, 240 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)70 A, FLA 600 V 60 Hz 3phase; (CSA); 90 A, FLA 480 V 60 Hz 3phase; (CSA); 540 A, LRA 480 V 60 Hz 3phase; (CSA); 420 A, LRA 600 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps100 A (600V 60Hz 3phase, 347V 60Hz 1phase); 100 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (main contacts, general use)125 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main cables; 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver; 2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)24 mm
Terminal capacity (copper band)2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (solid)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 4) mm², Control circuit cables
Terminal capacity (stranded)1 x (16 - 70) mm², Main cables; 2 x (16 - 50) mm², Main cables
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 14 Nm, Screw terminals, Main cables
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables; 1 x (10 - 70) mm², Main cables; 2 x (10 - 50) mm², Main cables
Terminal capacity (solid/stranded AWG)Single 8…3/0, double 8…2/0, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References

Attached Documents