Eaton EMT6-DB(230V) Thermistor Motor-Protection Relay with Differential Trip

Eaton · Control & Automation · Relays & Timers · Ireland · eaton.com
Part Number
EMT6-DB(230V)  ·  HS 8536.49
Eaton EMT6-DB(230V) Thermistor Motor-Protection Relay with Differential Trip

Eaton EMT6-DB(230V) is a thermistor motor-protection relay with differential release, suitable for protection of EEx e motors. The 23 by 83 by 103 mm module carries one NO and one NC auxiliary contact rated 6 A conventional thermal current, with a 230 V AC/DC coil (3.5 VA at AC, 2 W at DC) and 400 V rated insulation voltage. Reset resistance is 1600 Ω, ambient service range -25 to 60 degrees C, with EN 55011 EMC compliance and UL/CSA/IEC certification.

Technical Specifications

Manufacturer part number (MPN)EMT6-DB(230V)
EAN / GTIN4015080664017
Sales unitpcs
Eaton catalogue number066401
Depth103 mm
Height83 mm
Width23 mm
Weight0.156 kg
CertificationsEN 55011; CSA File No.: 12528; CSA-C22.2 No. 14; IEC/EN 60947; UL File No.: E29184; CE; CSA Class No.: 3211-03; UL; UL Category Control No.: NKCR; IEC/EN 61000-4-3; UL 508; VDE 0660; IEC/EN 60947-8; IEC/EN 61000-4-2; CSA
Ambient operating temperature - max60 °C
Ambient storage temperature - max85 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max45 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-45 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Number of contacts (change-over contacts)0
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Static heat dissipation, non-current-dependent Pvs1.5 W
Conventional thermal current Ith of auxiliary contacts (1-pole, open)6 A
Pick-up voltage0.85 - 1.1 V x Uₑ
Power consumption3.5 VA at AC; 2 W at DC
Rated control supply voltage (Us) at AC, 50 Hz - max230 V
Rated control supply voltage (Us) at AC, 50 Hz - min230 V
Rated control supply voltage (Us) at AC, 60 Hz - max230 V
Rated control supply voltage (Us) at AC, 60 Hz - min230 V
Rated insulation voltage (Ui)400 V
Rated operational voltage (Ue) - max230 V
Reset resistance1600 Ω
Short-circuit protection ratingMax. 6 A gG/gL, Fuse, Contacts
Trip resistance3600 Ω
Voltage rating - max600 V
Air discharge8 kV
Burst impulse2 kV, Supply cable; 1 kV, Signal cable; According to IEC/EN 61000-4-4
Contact discharge6 kV
Electromagnetic fields3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3); 10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3); 1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference10 V (according to IEC/EN 61000-4-6)
Radio interference classClass B (EN 55011)
Surge ratingAccording to IEC/EN 61000-4-5, power pulses (Surge), EMC; 4 kV, asymmetrical, power pulses (Surge), EMC; 2 kV, symmetrical, power pulses (Surge), EMC
Electric connection typeScrew connection
FunctionsManual or remote resetting; External reset possible; Test function via separate button; Notifications of mains and faults via LED display; Manual reset
Degree of protectionIP20
Mounting positionAs required
Overvoltage categoryIII
Pollution degree3
Product categoryEMT6 thermistor overload relay for machine protection
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)4000 V AC; 6000 V AC
Safe isolation250 V AC, Between the contacts, According to EN 61140; 250 V AC, Between the contacts and power supply, According to EN 61140
Shock resistance10 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Voltage typeAC
Screw sizeM3.5, Terminal screw
Screwdriver size1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Terminal capacity20 - 14 AWG, solid or stranded; 2 x (0.5 - 1.5) mm², flexible with ferrule; 2 x (0.5 - 1.5) mm², solid; 1 x (0.5 - 2.5) mm², flexible with ferrule; 1 x (0.5 - 2.5) mm², solid
Tightening torque1.2 Nm, Screw terminals
Operating voltage AC 50 Hz230 V
Operating voltage AC 60 Hz230 V
Supply voltage AC 50 Hz230 V
Supply voltage AC 60 Hz230 V
Rated switch current6 A
Connection type auxiliary circuitScrew connection
Type of electric connectionScrew connection
Rated control supply voltage AC 50 Hz230 V
Rated control supply voltage AC 60 Hz230 V
Voltage type for actuatingAC
With detachable clampsNo
Number of measuring circuits1
Error registration possibleNo
External reset possibleYes
Number of contacts as normally closed contact1
Number of contacts as normally open contact1
Resistance measuring range750–12000 Ohm
Country of originChina

Properties

MOQ1

Cross-References