Eaton ZE-9 Motor Protection Relay 6-9 A for DILEM Contactor (ZE-9)

Eaton · Switchgear & Protection · Overload Relays · Ireland · eaton.com
Part Number
ZE-9  ·  HS 8536.30
Eaton ZE-9 Motor Protection Relay 6-9 A for DILEM Contactor (ZE-9)

Eaton ZE-9 is a thermal overload relay with a 6-9 A setting range, designed for use with DILEM contactors. It provides phase-loss sensitive protection suitable for Ex e motors, with a differential tripping mechanism to enhance response to unbalanced conditions. The unit carries one normally open and one normally closed auxiliary contact and is rated up to 690 V.

Technical Specifications

Manufacturer part number (MPN)ZE-9
EAN / GTIN4015080147084
Sales unitpcs
Package quantity5 pcs
Eaton catalogue number014708
Depth52 mm
Height65 mm
Width45 mm
Weight0.08 kg
CertificationsCE; IEC/EN 60947-4-1; CSA; UL; UL 508; IEC/EN 60947; IEC/EN 60947-5-1; UL File No.: E29184; CSA-C22.2 No. 14; CSA Class No.: 3211-03; CSA File No.: 012528; UL Category Control No.: NKCR; VDE 0660
Number of auxiliary contacts (change-over contacts)0
Number of auxiliary contacts (normally closed contacts)1
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Equipment heat dissipation, current-dependent Pvid5.1 W
Heat dissipation per pole, current-dependent Pvid1.7 W
Rated operational current for specified heat dissipation (In)9 A
Conventional thermal current Ith of auxiliary contacts (1-pole, open)6 A
Rated operational current (Ie) at AC-15, 120 V1.5 A
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V1.5 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V0.7 A
Rated operational current (Ie) at AC-15, 500 V0.5 A
Rated operational current (Ie) at DC-13, 110 V0.4 A
Rated operational current (Ie) at DC-13, 220 V, 230 V0.2 A
Rated operational current (Ie) at DC-13, 24 V0.9 A
Rated operational current (Ie) at DC-13, 60 V0.75 A
Rated operational voltage (Ue) - max690 V
Safe isolation300 V AC, Between auxiliary contacts and main contacts, According to EN 61140; 300 V AC, Between main circuits, According to EN 61140; 250 V AC, Between auxiliary contacts, According to EN 61140
Switching capacity (auxiliary contacts, general use)1.5 A, 240V AC, (UL/CSA); 0.6 A, 600V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)D300, AC operated (UL/CSA); R300, DC operated (UL/CSA)
Voltage rating - max600 VAC
FeaturesPhase-failure sensitivity (according to IEC/EN 60947, VDE 0660 Part 102); Test/off button; Reset pushbutton manual/auto; Trip-free release
Ambient operating temperature - max50 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
ClassCLASS 10 A / IEC 60947-4-1, 8.2.1.5.1.1. c) 4 min
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Degree of protectionIP20; IP00
Mounting methodDirect attachment; Direct mounting
Overload release current setting - max9 A
Overload release current setting - min6 A
Overvoltage categoryIII
Pollution degree3
Product categoryZE overload relays for mini contactor relays
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)4000 V (auxiliary and control circuits); 6000 V AC
Shock resistance10 g, Mechanical, Sinusoidal, Shock duration 10 ms
Suitable forBranch circuits, (UL/CSA)
Temperature compensationContinuous; ≤ 0.25 %/K, residual error for T > 40°
Short-circuit current rating (basic rating)5 kA, SCCR (UL/CSA); 35 A, max. Fuse, SCCR (UL/CSA); 15 A, max. CB, CB for max. 480 V, SCCR (UL/CSA)
Short-circuit protection ratingMax. 4 A gG/gL, Fuse, Auxiliary contacts; 35 A gG/gL, Fuse, Type “1” coordination; 10 A gG/gL, Fuse, Type “2” coordination; 20 A gG/gL, Fuse, Type “2” coordination; Information on Type "1" and Type"2" coordination applies to 100 kA and 690 V
Screw sizeM3.5, Terminal screw
Screwdriver size2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5 mm, Terminal screw, Standard screwdriver
Stripping length (control circuit cable)8 mm
Stripping length (main cable)8 mm
Terminal capacity (flexible with ferrule)1 x (0.5 - 1.5) mm², Control circuit cables; 2 x (0.5 - 1.5) mm², Main cables; 1 x (0.5 - 1.5) mm², Main cables
Terminal capacity (solid)1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Main cables
Terminal capacity (solid/stranded AWG)18 - 14, Main cables; 2 x (18 - 12), Control circuit cables
Tightening torque1.2 Nm, Screw terminals
Number of auxiliary contacts as normally open contact1
Number of auxiliary contacts as normally closed contact1
Release classCLASS 10
Type of electrical connection of main circuitScrew connection
Max. rated operation voltage Ue690 V
Adjustable current range6–9 A
Reset function inputNo
Reset function automaticYes
Reset function push-buttonYes
Country of originGermany

Properties