CONTACTOR,65A AC-3, DC Coil (DILM65(RDC24))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM65(RDC24)  ·  HS 8536.90
CONTACTOR,65A AC-3, DC Coil (DILM65(RDC24))

Eaton DILM65(RDC24) KKontaktor 3-pole, 24 VDC.

Technical Specifications

Manufacturer part number (MPN)DILM65(RDC24)
EAN / GTIN4015082779085
HS code8536.90
Sales unitpcs
Eaton catalogue number277908
Depth132.1 mm
Height115 mm
Width55 mm
Weight1.052 kg
CertificationsCSA File No.: 012528; CSA-C22.2 No. 60947-4-1-14; UL Category Control No.: NLDX; CE; CSA Class No.: 2411-03
3211-04; UL File No.E29096; IEC/EN 60947; UL 60947-4-1; VDE 0660; UL; IEC/EN 60947-4-1; CSA
Catalog NotesContacts according to EN 50012
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)180 A
Conventional thermal current Ith (3-pole, enclosed)72 A
Conventional thermal current Ith at 55°C (3-pole, open)83 A
Conventional thermal current Ith at 60°C (3-pole, open)80 A
Conventional thermal current Ith of main contacts (1-pole, open)200 A
Equipment heat dissipation, current-dependent Pvid17.1 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid5.7 W
Rated operational current for specified heat dissipation (In)65 A
Static heat dissipation, non-current-dependent Pvs1 W
Rated breaking capacity at 220/230 V650 A
Rated breaking capacity at 380/400 V650 A
Rated breaking capacity at 500 V650 A
Rated breaking capacity at 660/690 V370 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)910 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V98 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V65 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V65 A
Rated operational current (Ie) at AC-3
440 V65 A
Rated operational current (Ie) at AC-3
500 V65 A
Rated operational current (Ie) at AC-3, 660 V
690 V37 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V25 A
Rated operational current (Ie) at AC-4
440 V25 A
Rated operational current (Ie) at AC-4
500 V25 A
Rated operational current (Ie) at AC-4, 660 V
690 V20 A
Rated operational current (Ie) at DC-1
110 V72 A
Rated operational current (Ie) at DC-1
220 V65 A
Rated operational current (Ie) at DC-1
60 V72 A
Rated operational power at AC-3, 240 V
50 Hz22 kW
Rated operational power at AC-3, 380/400 V
50 Hz30 kW
Rated operational power at AC-3, 415 V
50 Hz39 kW
Rated operational power at AC-3, 440 V
50 Hz41 kW
Rated operational power at AC-3, 500 V
50 Hz47 kW
Rated operational power at AC-3, 690 V
50 Hz35 kW
Rated operational power at AC-4, 220/230 V
50 Hz7 kW
Rated operational power at AC-4, 240 V
50 Hz7.5 kW
Rated operational power at AC-4, 415 V
50 Hz13 kW
Rated operational power at AC-4, 440 V
50 Hz14 kW
Rated operational power at AC-4, 500 V
50 Hz16 kW
Rated operational power at AC-4, 660/690 V
50 Hz17 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Fitted withSuppressor circuit in actuating electronics
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (DC operated)
Operating frequency5000 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance per pole1.9 mΩ
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeDC
Frame sizeFS3
Arcing time10 ms
Drop-out voltageAt least smoothed two-phase bridge rectifier or three-phase rectifier; 0.6 - 0.15 x UC, DC operated
Duty factor100 %
Pick-up voltage24 - 27 V DC (RDC 24); 0.7 - 1.2 V DC x Uc
Power consumption (pick-up) at DC24 W
Power consumption (sealing) at DC1 W
Rated control supply voltage (Us) at DC - max27 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (DC operated, make contacts, closing delay) - max54 ms
Switching time (DC operated, make contacts, opening delay) - max24 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase5 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase20 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase15 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase25 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase50 HP
Assigned motor power at 575/600 V, 60 Hz
3-phase60 HP
Safe isolation440 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 250 A max. fuse, SCCR (UL/CSA); 10 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 65 kA, 100 A max. CB, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V100 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V125 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V80 A gG/gL
Special purpose rating of definite purpose rating65 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 390 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control10 HP, 200 V 60 Hz 3-ph, (UL/CSA); 32.2 A, 200 V 60 Hz 3-ph, (UL/CSA); 15 HP, 240 V 60 Hz 3-ph, (UL/CSA); 30 HP, 480 V 60 Hz 3-ph, (UL/CSA); 42 A, 240 V 60 Hz 3-ph, (UL/CSA); 41 A, 600 V 60 Hz 3-ph, (UL/CSA); 40 A, 480 V 60 Hz 3-ph, (UL/CSA); 40 HP, 600 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of resistance air heating88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps88 A (600V 60Hz 3phase, 347V 60Hz 1phase); 88 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (main contacts, general use)88 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M6, Terminal screw, Main cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)14 mm
Terminal capacity (copper band)2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (solid)1 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 16) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 16) mm², Main cables
Terminal capacity (stranded)2 x (16 - 35) mm², Main cables; 1 x (16 - 50) mm², Main cables
Tightening torque3.3 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 35) mm², Main cables; 2 x (0.75 - 25) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)Single 14 - 1, double 14 - 2, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References