| Manufacturer part number (MPN) | DILM65(110V50HZ,120V60HZ) |
| EAN / GTIN | 4015082778910 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 277891 |
| Depth | 132.1 mm |
| Height | 115 mm |
| Width | 55 mm |
| Weight | 0.872 kg |
| Certifications | VDE 0660; CE; UL 60947-4-1; CSA; IEC/EN 60947-4-1; UL File No.: E29096; UL Category Control No.: NLDX; CSA Class No.: 2411-03 |
| 3211-04; CSA-C22.2 No. 60947-4-1-14; UL; CSA File No. | 012528; IEC/EN 60947 |
| Catalog Notes | Contacts according to EN 50012 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Connection to SmartWire-DT | No |
| Number of main contacts (normally open contact) | 3 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 0 |
| Number of contacts (normally closed) as main contact | 0 |
| Conventional thermal current Ith (1-pole, enclosed) | 180 A |
| Conventional thermal current Ith (3-pole, enclosed) | 72 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 83 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 80 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 200 A |
| Equipment heat dissipation, current-dependent Pvid | 17.1 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 5.7 W |
| Rated operational current for specified heat dissipation (In) | 65 A |
| Static heat dissipation, non-current-dependent Pvs | 4.1 W |
| Rated breaking capacity at 220/230 V | 650 A |
| Rated breaking capacity at 380/400 V | 650 A |
| Rated breaking capacity at 500 V | 650 A |
| Rated breaking capacity at 660/690 V | 370 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 910 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V |
| 415 V | 98 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V |
| 240 V | 65 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V |
| 415 V | 65 A |
| Rated operational current (Ie) at AC-3 |
| 440 V | 65 A |
| Rated operational current (Ie) at AC-3 |
| 500 V | 65 A |
| Rated operational current (Ie) at AC-3, 660 V |
| 690 V | 37 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V |
| 240 V | 25 A |
| Rated operational current (Ie) at AC-4 |
| 440 V | 25 A |
| Rated operational current (Ie) at AC-4 |
| 500 V | 25 A |
| Rated operational current (Ie) at AC-4, 660 V |
| 690 V | 20 A |
| Rated operational current (Ie) at DC-1 |
| 110 V | 72 A |
| Rated operational current (Ie) at DC-1 |
| 220 V | 65 A |
| Rated operational current (Ie) at DC-1 |
| 60 V | 72 A |
| Rated operational power at AC-3, 240 V |
| 50 Hz | 22 kW |
| Rated operational power at AC-3, 380/400 V |
| 50 Hz | 30 kW |
| Rated operational power at AC-3, 415 V |
| 50 Hz | 39 kW |
| Rated operational power at AC-3, 440 V |
| 50 Hz | 41 kW |
| Rated operational power at AC-3, 500 V |
| 50 Hz | 47 kW |
| Rated operational power at AC-3, 690 V |
| 50 Hz | 35 kW |
| Rated operational power at AC-4, 220/230 V |
| 50 Hz | 7 kW |
| Rated operational power at AC-4, 240 V |
| 50 Hz | 7.5 kW |
| Rated operational power at AC-4, 415 V |
| 50 Hz | 13 kW |
| Rated operational power at AC-4, 440 V |
| 50 Hz | 14 kW |
| Rated operational power at AC-4, 500 V |
| 50 Hz | 16 kW |
| Rated operational power at AC-4, 660/690 V |
| 50 Hz | 17 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
| Number of poles | Three-pole |
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 5000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Resistance per pole | 1.9 mΩ |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
| Voltage type | AC |
| Frame size | FS3 |
| Arcing time | 10 ms |
| Drop-out voltage | AC operated: 0.6 - 0.3 x UC, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc |
| Power consumption, pick-up |
| 50 Hz | 149 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, pick-up |
| 60 Hz | 178 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Power consumption, sealing |
| 50 Hz | 4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 16 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, sealing |
| 60 Hz | 4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 19 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Rated control supply voltage (Us) at AC |
| 50 Hz - max | 110 V |
| Rated control supply voltage (Us) at AC |
| 50 Hz - min | 110 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - max | 120 V |
| Rated control supply voltage (Us) at AC |
| 60 Hz - min | 120 V |
| Switching time (AC operated, make contacts, closing delay) - max | 18 ms |
| Switching time (AC operated, make contacts, closing delay) - min | 12 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 13 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 8 ms |
| Assigned motor power at 115/120 V, 60 Hz |
| 1-phase | 5 HP |
| Assigned motor power at 200/208 V, 60 Hz |
| 3-phase | 20 HP |
| Assigned motor power at 230/240 V, 60 Hz |
| 1-phase | 15 HP |
| Assigned motor power at 230/240 V, 60 Hz |
| 3-phase | 25 HP |
| Assigned motor power at 460/480 V, 60 Hz |
| 3-phase | 50 HP |
| Assigned motor power at 575/600 V, 60 Hz |
| 3-phase | 60 HP |
| Safe isolation | 440 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140 |
| Short-circuit current rating (basic rating) | 10 kA, 250 A max. fuse, SCCR (UL/CSA); 10 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 65 kA, 100 A max. CB, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA) |
| Short-circuit protection rating (type 1 coordination) at 400 V | 250 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 100 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 125 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 80 A gG/gL |
| Special purpose rating of definite purpose rating | 390 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 65 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
| Special purpose rating of elevator control | 30 HP, 480 V 60 Hz 3-ph, (UL/CSA); 10 HP, 200 V 60 Hz 3-ph, (UL/CSA); 40 A, 480 V 60 Hz 3-ph, (UL/CSA); 32.2 A, 200 V 60 Hz 3-ph, (UL/CSA); 42 A, 240 V 60 Hz 3-ph, (UL/CSA); 15 HP, 240 V 60 Hz 3-ph, (UL/CSA); 40 HP, 600 V 60 Hz 3-ph, (UL/CSA); 41 A, 600 V 60 Hz 3-ph, (UL/CSA) |
| Special purpose rating of resistance air heating | 88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of tungsten incandescent lamps | 88 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 88 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
| Special purpose rating of ballast electrical discharge lamps | 88 A (600V 60Hz 3phase, 347V 60Hz 1phase); 88 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
| Switching capacity (main contacts, general use) | 88 A, Maximum motor rating (UL/CSA) |
| Screw size | M6, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
| Stripping length (control circuit cable) | 10 mm |
| Stripping length (main cable) | 14 mm |
| Terminal capacity (copper band) | 2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables |
| Terminal capacity (solid) | 1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 16) mm², Main cables; 2 x (0.75 - 16) mm², Main cables |
| Terminal capacity (stranded) | 2 x (16 - 35) mm², Main cables; 1 x (16 - 50) mm², Main cables |
| Tightening torque | 1.2 Nm, Screw terminals, Control circuit cables; 3.3 Nm, Screw terminals, Main cables |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 35) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (0.75 - 25) mm², Main cables |
| Terminal capacity (solid/stranded AWG) | Single 14 - 1, double 14 - 2, Main cables; 18 - 14, Control circuit cables |