cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor 3P. 190-240V 50/60Hz (DILM170(RAC240))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM170(RAC240)  ·  HS 8536.90
Contactor 3P. 190-240V 50/60Hz (DILM170(RAC240))

Technical Specifications

Manufacturer part number (MPN)DILM170(RAC240)
EAN / GTIN4015081067817
HS code8536.90
Sales unitpcs
Eaton catalogue number107013
Depth160 mm
Height170 mm
Width90 mm
Weight2.25 kg
CertificationsCSA File No.: 012528; IEC/EN 60947; CSA-C22.2 No. 60947-4-1-14; UL Category Control No.: NLDX; VDE 0660; CE; IEC/EN 60947-4-1; UL 60947-4-1; UL; CSA; CSA Class No.: 2411-03
3211-04; UL File No.E29096
Catalog NotesContacts according to EN 50012
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)415 A
Conventional thermal current Ith (3-pole, enclosed)166 A
Conventional thermal current Ith at 55°C (3-pole, open)190 A
Conventional thermal current Ith at 60°C (3-pole, open)185 A
Conventional thermal current Ith of main contacts (1-pole, open)460 A
Equipment heat dissipation, current-dependent Pvid41.1 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid13.7 W
Rated operational current for specified heat dissipation (In)170 A
Static heat dissipation, non-current-dependent Pvs2.3 W
Rated breaking capacity at 220/230 V1500 A
Rated breaking capacity at 380/400 V1500 A
Rated breaking capacity at 500 V1500 A
Rated breaking capacity at 660/690 V1320 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)2100 A
Rated operational current (Ie) at AC-1, 380 V, 400 V
415 V225 A
Rated operational current (Ie) at AC-3, 220 V, 230 V
240 V170 A
Rated operational current (Ie) at AC-3, 380 V, 400 V
415 V170 A
Rated operational current (Ie) at AC-3
440 V170 A
Rated operational current (Ie) at AC-3
500 V170 A
Rated operational current (Ie) at AC-3, 660 V
690 V100 A
Rated operational current (Ie) at AC-4, 220 V, 230 V
240 V65 A
Rated operational current (Ie) at AC-4
440 V65 A
Rated operational current (Ie) at AC-4
500 V65 A
Rated operational current (Ie) at AC-4, 660 V
690 V50 A
Rated operational current (Ie) at DC-1
110 V160 A
Rated operational current (Ie) at DC-1
220 V90 A
Rated operational current (Ie) at DC-1
60 V160 A
Rated operational power at AC-3, 240 V
50 Hz57 kW
Rated operational power at AC-3, 380/400 V
50 Hz90 kW
Rated operational power at AC-3, 415 V
50 Hz100 kW
Rated operational power at AC-3, 440 V
50 Hz105 kW
Rated operational power at AC-3, 500 V
50 Hz120 kW
Rated operational power at AC-3, 690 V
50 Hz96 kW
Rated operational power at AC-4, 220/230 V
50 Hz20 kW
Rated operational power at AC-4, 240 V
50 Hz22 kW
Rated operational power at AC-4, 415 V
50 Hz39 kW
Rated operational power at AC-4, 440 V
50 Hz41 kW
Rated operational power at AC-4, 500 V
50 Hz47 kW
Rated operational power at AC-4, 660/690 V
50 Hz48 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Fitted withSuppressor circuit in actuating electronics
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (AC operated)
Operating frequency3000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole0.6 mΩ
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeAC
Frame sizeFS4
Arcing time15 ms
Drop-out voltageAC operated: 0.6 - 0.25 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.15 V AC x Uc
Power consumption, pick-up
50 Hz180 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, pick-up
60 Hz170 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing
50 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing
60 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC
50 Hz - max240 V
Rated control supply voltage (Us) at AC
50 Hz - min190 V
Rated control supply voltage (Us) at AC
60 Hz - max240 V
Rated control supply voltage (Us) at AC
60 Hz - min190 V
Switching time (AC operated, make contacts, closing delay) - max33 ms
Switching time (AC operated, make contacts, closing delay) - min28 ms
Switching time (AC operated, make contacts, opening delay) - max41 ms
Switching time (AC operated, make contacts, opening delay) - min35 ms
Assigned motor power at 115/120 V, 60 Hz
1-phase10 HP
Assigned motor power at 200/208 V, 60 Hz
3-phase50 HP
Assigned motor power at 230/240 V, 60 Hz
1-phase30 HP
Assigned motor power at 230/240 V, 60 Hz
3-phase60 HP
Assigned motor power at 460/480 V, 60 Hz
3-phase125 HP
Assigned motor power at 575/600 V, 60 Hz
Safe isolation690 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 600 A max. fuse, SCCR (UL/CSA); 10 kA, 600 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 600 A CLASS J max. fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 600 A CLASS J max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V250 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V250 A gG/gL
Special purpose rating of definite purpose rating170 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA); 1020 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
Special purpose rating of elevator control92 A, 200 V 60 Hz 3-ph, (UL/CSA); 40 HP, 240 V 60 Hz 3-ph, (UL/CSA); 75 HP, 480 V 60 Hz 3-ph, (UL/CSA); 30 HP, 200 V 60 Hz 3-ph, (UL/CSA); 100 HP, 600 V 60 Hz 3-ph, (UL/CSA); 99 A, 600 V 60 Hz 3-ph, (UL/CSA); 104 A, 240 V 60 Hz 3-ph, (UL/CSA); 96 A, 480 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)540 A, LRA 600 V 60 Hz 3phase; (CSA); 540 A, LRA 480 V 60 Hz 3phase; (CSA); 90 A, FLA 600 V 60 Hz 3phase; (CSA); 90 A, FLA 480 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps160 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 160 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps160 A (600V 60Hz 3phase, 347V 60Hz 1phase); 160 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (main contacts, general use)225 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M10, Terminal screw, Main cables; 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)24 mm
Terminal capacity (copper band)2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (solid)1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (stranded)1 x (16 - 95) mm², Main cables; 2 x (16 - 70) mm², Main cables
Tightening torque14 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (10 - 95) mm², Main cables; 1 x (0.75 - 2.5) mm², Control circuit cables; 2 x (10 - 70) mm², Main cables
Terminal capacity (solid/stranded AWG)18 - 14, Control circuit cables; Single 8…3/0, double 8…2/0, Main cables

Properties

MOQ1

Cross-References

Attached Documents