| Manufacturer part number (MPN) | DILM32-10(400V50HZ,440V60HZ) |
| EAN / GTIN | 4015082772628 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Eaton catalogue number | 277262 |
| Depth | 97 mm |
| Height | 85 mm |
| Width | 45 mm |
| Weight | 0.428 kg |
| Compliances | CE Marked |
| Certifications | CSA Std. C22.2 No. 14-05; UL 508; IEC 60947-4-1; EN 60947-4-1; VDE; IEC/EN 60947; CSA; UL; VDE 0660 |
| Catalog Notes | Contacts according to EN 50012 |
| Altitude | Max. 2000 m |
| Ambient operating temperature - max | 60 °C |
| Ambient storage temperature - max | 80 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient storage temperature - min | -40 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Connection to SmartWire-DT | No |
| Number of main contacts (normally open contact) | 3 |
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Number of contacts (normally closed) as main contact | 0 |
| Conventional thermal current Ith (1-pole, enclosed) | 90 A |
| Conventional thermal current Ith (3-pole, enclosed) | 36 A |
| Conventional thermal current Ith at 55°C (3-pole, open) | 42 A |
| Conventional thermal current Ith at 60°C (3-pole, open) | 40 A |
| Conventional thermal current Ith of main contacts (1-pole, open) | 100 A |
| Equipment heat dissipation, current-dependent Pvid | 6.6 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 2.2 W |
| Rated operational current for specified heat dissipation (In) | 32 A |
| Static heat dissipation, non-current-dependent Pvs | 2.1 W |
| Rated breaking capacity at 220/230 V | 320 A |
| Rated breaking capacity at 380/400 V | 320 A |
| Rated breaking capacity at 500 V | 320 A |
| Rated breaking capacity at 660/690 V | 180 A |
| Rated insulation voltage (Ui) | 690 V |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 384 A |
| Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 45 A |
| Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 32 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 32 A |
| Rated operational current (Ie) at AC-3, 440 V | 32 A |
| Rated operational current (Ie) at AC-3, 500 V | 32 A |
| Rated operational current (Ie) at AC-3, 660 V, 690 V | 18 A |
| Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 15 A |
| Rated operational current (Ie) at AC-4, 440 V | 15 A |
| Rated operational current (Ie) at AC-4, 500 V | 15 A |
| Rated operational current (Ie) at AC-4, 660 V, 690 V | 12 A |
| Rated operational current (Ie) at DC-1, 110 V | 40 A |
| Rated operational current (Ie) at DC-1, 220 V | 40 A |
| Rated operational current (Ie) at DC-1, 60 V | 40 A |
| Rated operational power at AC-3, 240 V, 50 Hz | 11 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 15 kW |
| Rated operational power at AC-3, 415 V, 50 Hz | 19 kW |
| Rated operational power at AC-3, 440 V, 50 Hz | 20 kW |
| Rated operational power at AC-3, 500 V, 50 Hz | 23 kW |
| Rated operational power at AC-3, 690 V, 50 Hz | 17 kW |
| Rated operational power at AC-4, 220/230 V, 50 Hz | 4 kW |
| Rated operational power at AC-4, 240 V, 50 Hz | 4.5 kW |
| Rated operational power at AC-4, 415 V, 50 Hz | 7.5 kW |
| Rated operational power at AC-4, 440 V, 50 Hz | 8 kW |
| Rated operational power at AC-4, 500 V, 50 Hz | 9 kW |
| Rated operational power at AC-4, 660/690 V, 50 Hz | 10 kW |
| Rated operational voltage (Ue) at AC - max | 690 V |
| Emitted interference | According to EN 60947-1 |
| Interference immunity | According to EN 60947-1 |
| Number of poles | Three-pole |
| Application | Contactors for Motors |
| Connection | Screw terminals |
| Degree of protection | IP00 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Operating frequency | 5000 mechanical Operations/h (AC operated) |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 8000 V AC |
| Resistance per pole | 2.7 mΩ |
| Suitable for | Also motors with efficiency class IE3 |
| Utilization category | AC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running |
| Voltage type | AC |
| Frame size | FS2 |
| Arcing time | 10 ms |
| Drop-out voltage | AC operated: 0.6 - 0.3 x UC, AC operated |
| Duty factor | 100 % |
| Pick-up voltage | 0.8 - 1.1 V AC x Uc |
| Power consumption, pick-up, 50 Hz | 52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, pick-up, 60 Hz | 67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Power consumption, sealing, 50 Hz | 7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
| Power consumption, sealing, 60 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 400 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 400 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 440 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 440 V |
| Switching time (AC operated, make contacts, closing delay) - max | 22 ms |
| Switching time (AC operated, make contacts, closing delay) - min | 16 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 14 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 8 ms |
| Safe isolation | 440 V AC, Between coil and contacts, According to EN 61140; 440 V AC, Between the contacts, According to EN 61140 |
| Short-circuit protection rating (type 1 coordination) at 400 V | 125 A gG/gL |
| Short-circuit protection rating (type 1 coordination) at 690 V | 63 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 400 V | 63 A gG/gL |
| Short-circuit protection rating (type 2 coordination) at 690 V | 35 A gG/gL |
| Screw size | M5, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver |
| Stripping length (control circuit cable) | 10 mm |
| Stripping length (main cable) | 10 mm |
| Terminal capacity (solid) | 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 16) mm², Main cables; 1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 10) mm², Main cables |
| Terminal capacity (stranded) | 1 x 16 mm², Main cables |
| Tightening torque | 1.2 Nm, Screw terminals, Control circuit cables; 3.2 Nm, Screw terminals, Main cables |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 16) mm², Main cables; 2 x (0.75 - 10) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) | Single 18 - 6, double 18 - 8, Main cables; 18 - 14, Control circuit cables |