cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

CONTACTOR,32A AC-3, AC Coil (DILM32-10(400V50HZ,440V60HZ))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILM32-10(400V50HZ,440V60HZ)  ·  HS 8536.90
CONTACTOR,32A AC-3, AC Coil (DILM32-10(400V50HZ,440V60HZ))

Eaton DILM32-10(400V50HZ,440V60HZ) Contactor 3-pole, 400-440 VAC incl. 1NO.

Technical Specifications

Manufacturer part number (MPN)DILM32-10(400V50HZ,440V60HZ)
EAN / GTIN4015082772628
HS code8536.90
Sales unitpcs
Eaton catalogue number277262
Depth97 mm
Height85 mm
Width45 mm
Weight0.428 kg
CompliancesCE Marked
CertificationsCSA Std. C22.2 No. 14-05; UL 508; IEC 60947-4-1; EN 60947-4-1; VDE; IEC/EN 60947; CSA; UL; VDE 0660
Catalog NotesContacts according to EN 50012
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)3
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)1
Number of contacts (normally open contacts)1
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)90 A
Conventional thermal current Ith (3-pole, enclosed)36 A
Conventional thermal current Ith at 55°C (3-pole, open)42 A
Conventional thermal current Ith at 60°C (3-pole, open)40 A
Conventional thermal current Ith of main contacts (1-pole, open)100 A
Equipment heat dissipation, current-dependent Pvid6.6 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid2.2 W
Rated operational current for specified heat dissipation (In)32 A
Static heat dissipation, non-current-dependent Pvs2.1 W
Rated breaking capacity at 220/230 V320 A
Rated breaking capacity at 380/400 V320 A
Rated breaking capacity at 500 V320 A
Rated breaking capacity at 660/690 V180 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)384 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V45 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V32 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V32 A
Rated operational current (Ie) at AC-3, 440 V32 A
Rated operational current (Ie) at AC-3, 500 V32 A
Rated operational current (Ie) at AC-3, 660 V, 690 V18 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V15 A
Rated operational current (Ie) at AC-4, 440 V15 A
Rated operational current (Ie) at AC-4, 500 V15 A
Rated operational current (Ie) at AC-4, 660 V, 690 V12 A
Rated operational current (Ie) at DC-1, 110 V40 A
Rated operational current (Ie) at DC-1, 220 V40 A
Rated operational current (Ie) at DC-1, 60 V40 A
Rated operational power at AC-3, 240 V, 50 Hz11 kW
Rated operational power at AC-3, 380/400 V, 50 Hz15 kW
Rated operational power at AC-3, 415 V, 50 Hz19 kW
Rated operational power at AC-3, 440 V, 50 Hz20 kW
Rated operational power at AC-3, 500 V, 50 Hz23 kW
Rated operational power at AC-3, 690 V, 50 Hz17 kW
Rated operational power at AC-4, 220/230 V, 50 Hz4 kW
Rated operational power at AC-4, 240 V, 50 Hz4.5 kW
Rated operational power at AC-4, 415 V, 50 Hz7.5 kW
Rated operational power at AC-4, 440 V, 50 Hz8 kW
Rated operational power at AC-4, 500 V, 50 Hz9 kW
Rated operational power at AC-4, 660/690 V, 50 Hz10 kW
Rated operational voltage (Ue) at AC - max690 V
Emitted interferenceAccording to EN 60947-1
Interference immunityAccording to EN 60947-1
Number of polesThree-pole
ApplicationContactors for Motors
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (AC operated)
Operating frequency5000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance per pole2.7 mΩ
Suitable forAlso motors with efficiency class IE3
Utilization categoryAC-4: Normal AC induction motors: starting, plugging, reversing, inching; AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running
Voltage typeAC
Frame sizeFS2
Arcing time10 ms
Drop-out voltageAC operated: 0.6 - 0.3 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.1 V AC x Uc
Power consumption, pick-up, 50 Hz52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, pick-up, 60 Hz67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz; 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max400 V
Rated control supply voltage (Us) at AC, 50 Hz - min400 V
Rated control supply voltage (Us) at AC, 60 Hz - max440 V
Rated control supply voltage (Us) at AC, 60 Hz - min440 V
Switching time (AC operated, make contacts, closing delay) - max22 ms
Switching time (AC operated, make contacts, closing delay) - min16 ms
Switching time (AC operated, make contacts, opening delay) - max14 ms
Switching time (AC operated, make contacts, opening delay) - min8 ms
Safe isolation440 V AC, Between coil and contacts, According to EN 61140; 440 V AC, Between the contacts, According to EN 61140
Short-circuit protection rating (type 1 coordination) at 400 V125 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V63 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V63 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V35 A gG/gL
Screw sizeM5, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)10 mm
Terminal capacity (solid)2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 16) mm², Main cables; 1 x (0.75 - 4) mm², Control circuit cables; 2 x (0.75 - 10) mm², Main cables
Terminal capacity (stranded)1 x 16 mm², Main cables
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 3.2 Nm, Screw terminals, Main cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 16) mm², Main cables; 2 x (0.75 - 10) mm², Main cables; 2 x (0.75 - 2.5) mm², Control circuit cables; 1 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)Single 18 - 6, double 18 - 8, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References