cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor DILMP63(RDC24)

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMP63(RDC24)  ·  HS 8536.90
Contactor DILMP63(RDC24)

Eaton DILMP63(RDC24) Contactor 4-pole, 63A AC1 24VDC.

Technical Specifications

Manufacturer part number (MPN)DILMP63(RDC24)
EAN / GTIN4015081094370
HS code8536.90
Sales unitpcs
Eaton catalogue number109869
Depth132 mm
Height115 mm
Width74 mm
Weight1.2 kg
CertificationsCSA-C22.2 No. 60947-4-1-14; UL 60947-4-1; CE; UL File No.: E29096; UL; CSA Class No.: 2411-03, 3211-04; IEC/EN 60947; IEC/EN 60947-4-1; VDE 0660; UL Category Control No.: NLDX; CSA; CSA File No.: 012528
Catalog NotesAlso tested according to AC-3e.
Shock resistance5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-3
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)4
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)146 A
Conventional thermal current Ith (3-pole, enclosed)50 A
Conventional thermal current Ith at 55°C (3-pole, open)58 A
Conventional thermal current Ith at 60°C (3-pole, open)54 A
Conventional thermal current Ith of main contacts (1-pole, open)162 A
Equipment heat dissipation, current-dependent Pvid16.5 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid5.5 W
Rated operational current for specified heat dissipation (In)63 A
Static heat dissipation, non-current-dependent Pvs1 W
Rated breaking capacity at 220/230 V400 A
Rated breaking capacity at 380/400 V400 A
Rated breaking capacity at 500 V400 A
Rated breaking capacity at 660/690 V250 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)560 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V63 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V40 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V40 A
Rated operational current (Ie) at AC-3, 440 V40 A
Rated operational current (Ie) at AC-3, 500 V40 A
Rated operational current (Ie) at AC-3, 660 V, 690 V25 A
Rated operational current (Ie) at DC-1, 110 V63 A
Rated operational current (Ie) at DC-1, 220 V63 A
Rated operational current (Ie) at DC-1, 60 V63 A
Rated operational power at AC-1, 220/230 V, 50 Hz23 kW
Rated operational power at AC-1, 240 V, 50 Hz25 kW
Rated operational power at AC-1, 380/400 V, 50 Hz39 kW
Rated operational power at AC-1, 415 V, 50 Hz43 kW
Rated operational power at AC-1, 440 V, 50 Hz46 kW
Rated operational power at AC-1, 500 V, 50 Hz52 kW
Rated operational power at AC-1, 690 V, 50 Hz68 kW
Rated operational power at AC-3, 240 V, 50 Hz13.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz18.5 kW
Rated operational power at AC-3, 415 V, 50 Hz24 kW
Rated operational power at AC-3, 440 V, 50 Hz25 kW
Rated operational power at AC-3, 500 V, 50 Hz28 kW
Rated operational power at AC-3, 690 V, 50 Hz23 kW
Rated operational voltage (Ue) at AC - max690 V
Fitted withSuppressor circuit in actuating electronics
Number of polesFour-pole
ApplicationContactors for 4 pole electric consumers
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (AC operated); 10,000,000 Operations (DC operated)
Operating frequency5000 mechanical Operations/h (AC operated); 5000 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole1.9 mΩ
Utilization categoryAC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage typeDC
Arcing time10 ms
Drop-out voltage0.2 - 0.6 x UC, DC operated
Duty factor100 %
Pick-up voltage0.7 - 1.2 V DC x Uc; 0.85 - 1.1 V AC/DC x Us
Power consumption (pick-up) at DC24 W
Power consumption (sealing) at DC1 W
Rated control supply voltage (Us) at DC - max27 V
Rated control supply voltage (Us) at DC - min24 V
Switching time (DC operated, make contacts, closing delay) - max54 ms
Switching time (DC operated, make contacts, opening delay) - max24 ms
Assigned motor power at 115/120 V, 60 Hz, 1-phase3 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase10 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase7.5 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase15 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase30 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase40 HP
Safe isolation440 V AC, Between coil and contacts, According to EN 61140; 440 V AC, Between the contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 250 A max. fuse, SCCR (UL/CSA); 10 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 65 kA, 100 A max. CB, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 150 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. fuse, SCCR (UL/CSA); 30 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V125 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V80 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V63 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V50 A gG/gL
Special purpose rating of elevator control7.5 HP, 200 V 60 Hz 3-ph, (UL/CSA); 25.3 A, 200 V 60 Hz 3-ph, (UL/CSA); 10 HP, 240 V 60 Hz 3-ph, (UL/CSA); 34 A, 480 V 60 Hz 3-ph, (UL/CSA); 25 HP, 480 V 60 Hz 3-ph, (UL/CSA); 30 HP, 600 V 60 Hz 3-ph, (UL/CSA); 28 A, 240 V 60 Hz 3-ph, (UL/CSA); 32 A, 600 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of resistance air heating79 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 79 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps74 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 74 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps79 A (480V 60Hz 3phase, 277V 60Hz 1phase); 79 A (600V 60Hz 3phase, 347V 60Hz 1phase)
Switching capacity (main contacts, general use)63 A, Maximum motor rating (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables; M6, Terminal screw, Main cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver; 2, Terminal screw, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)10 mm
Terminal capacity (copper band)2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (flexible)1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm²
Terminal capacity (solid)1 x (2.5 - 16) mm², Main cables; 1 x (0.75 - 4) mm², Control circuit cables; 2 x (2.5 - 16) mm², Main cables; 2 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 2.5) mm²
Terminal capacity (stranded)2 x (16 - 35) mm², Main cables; 1 x (16 - 50) mm², Main cables
Tightening torque1.2 Nm, Screw terminals, Control circuit cables; 3.3 Nm, Screw terminals, Main cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid/stranded AWG)12 - 2, Main Cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References

Attached Documents