cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Contactor 4P. 190-230V 50/60Hz (DILMP125(RAC240))

Eaton · Electrical Components · Contactors · Ireland · eaton.com
Part Number
DILMP125(RAC240)  ·  HS 8536.90
Contactor 4P. 190-230V 50/60Hz (DILMP125(RAC240))

Eaton DILMP125(RAC240) Contactor 4-pole, attenuator integrated in DC-contactor.

Technical Specifications

Manufacturer part number (MPN)DILMP125(RAC240)
EAN / GTIN4015081094714
HS code8536.90
Sales unitpcs
Eaton catalogue number109905
Depth160 mm
Height170 mm
Width122 mm
Weight2.73 kg
CertificationsCSA File No.: 012528; CSA-C22.2 No. 60947-4-1-14; CE; CSA; UL File No.: E29096; UL; VDE 0660; UL 60947-4-1; UL Category Control No.: NLDX; IEC/EN 60947; IEC/EN 60947-4-1; CSA Class No.: 2411-03, 3211-04
Catalog NotesContacts according to EN 50012
Shock resistance5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-25 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-25 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, constant, to IEC 60068-2-3; Damp heat, cyclic, to IEC 60068-2-30
Connection to SmartWire-DTNo
Number of main contacts (normally open contact)4
Number of auxiliary contacts (normally closed contacts)0
Number of auxiliary contacts (normally open contacts)0
Number of contacts (normally closed) as main contact0
Conventional thermal current Ith (1-pole, enclosed)292 A
Conventional thermal current Ith (3-pole, enclosed)100 A
Conventional thermal current Ith at 55°C (3-pole, open)110 A
Conventional thermal current Ith at 60°C (3-pole, open)108 A
Conventional thermal current Ith of main contacts (1-pole, open)325 A
Equipment heat dissipation, current-dependent Pvid22.2 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid7.4 W
Rated operational current for specified heat dissipation (In)125 A
Static heat dissipation, non-current-dependent Pvs2.3 W
Rated breaking capacity at 220/230 V800 A
Rated breaking capacity at 380/400 V800 A
Rated breaking capacity at 500 V800 A
Rated breaking capacity at 660/690 V650 A
Rated insulation voltage (Ui)690 V
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)1120 A
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V125 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V80 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V80 A
Rated operational current (Ie) at AC-3, 440 V80 A
Rated operational current (Ie) at AC-3, 500 V80 A
Rated operational current (Ie) at AC-3, 660 V, 690 V65 A
Rated operational current (Ie) at DC-1, 110 V125 A
Rated operational current (Ie) at DC-1, 220 V125 A
Rated operational current (Ie) at DC-1, 60 V125 A
Rated operational power at AC-1, 220/230 V, 50 Hz45 kW
Rated operational power at AC-1, 240 V, 50 Hz49 kW
Rated operational power at AC-1, 380/400 V, 50 Hz78 kW
Rated operational power at AC-1, 415 V, 50 Hz85 kW
Rated operational power at AC-1, 440 V, 50 Hz90 kW
Rated operational power at AC-1, 500 V, 50 Hz103 kW
Rated operational power at AC-1, 690 V, 50 Hz136 kW
Rated operational power at AC-3, 240 V, 50 Hz27.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz37 kW
Rated operational power at AC-3, 415 V, 50 Hz48 kW
Rated operational power at AC-3, 440 V, 50 Hz51 kW
Rated operational power at AC-3, 500 V, 50 Hz58 kW
Rated operational power at AC-3, 690 V, 50 Hz63 kW
Rated operational voltage (Ue) at AC - max690 V
Interference immunityAccording to EN 60947-1
Fitted withSuppressor circuit in actuating electronics
Number of polesFour-pole
ApplicationContactors for 4 pole electric consumers
ConnectionScrew terminals
Degree of protectionIP00
Lifespan, mechanical10,000,000 Operations (AC operated); 10,000,000 Operations (DC operated)
Operating frequency3600 mechanical Operations/h (AC operated); 3600 mechanical Operations/h (DC operated)
Overvoltage categoryIII
Pollution degree3
Product categoryContactors
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)8000 V AC
Residual current1 mA (with actuation of A1 - A2 by the electronics with "0" signal)
Resistance per pole0.6 mΩ
Utilization categoryAC-3: Normal AC induction motors: starting, switch off during running; AC-1: Non-inductive or slightly inductive loads, resistance furnaces
Voltage typeAC
Drop-out voltageAC operated: 0.6 - 0.25 x UC, AC operated
Duty factor100 %
Pick-up voltage0.8 - 1.15 V AC/DC x Us; 0.8 - 1.15 V AC x Uc
Power consumption, pick-up, 50 Hz180 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz150 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz; 180 VA, Dual-frequency coil in a cold state and 1.0 x Us
Power consumption, sealing, 50 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz2.3 W, Dual-frequency coil in a cold state and 1.0 x Us; 3.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max240 V
Rated control supply voltage (Us) at AC, 50 Hz - min190 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min190 V
Switching time (AC operated, make contacts, closing delay) - max33 ms
Switching time (AC operated, make contacts, closing delay) - min28 ms
Switching time (AC operated, make contacts, opening delay) - max41 ms
Switching time (AC operated, make contacts, opening delay) - min35 ms
Assigned motor power at 115/120 V, 60 Hz, 1-phase7.5 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase25 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase15 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase30 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase60 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase75 HP
Safe isolation440 V AC, Between the contacts, According to EN 61140; 440 V AC, Between coil and contacts, According to EN 61140
Short-circuit current rating (basic rating)10 kA, 600 A max. fuse, SCCR (UL/CSA); 10 kA, 600 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA); 65 kA, 250 A max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA); 30 kA, 600 A max. fuse, SCCR (UL/CSA)
Short-circuit protection rating (type 1 coordination) at 400 V250 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V200 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V160 A gG/gL
Special purpose rating of elevator control68 A, 240 V 60 Hz 3-ph, (UL/CSA); 62.1 A, 200 V 60 Hz 3-ph, (UL/CSA); 25 HP, 240 V 60 Hz 3-ph, (UL/CSA); 50 HP, 480 V 60 Hz 3-ph, (UL/CSA); 60 HP, 600 V 60 Hz 3-ph, (UL/CSA); 20 HP, 200 V 60 Hz 3-ph, (UL/CSA); 62 A, 600 V 60 Hz 3-ph, (UL/CSA); 65 A, 480 V 60 Hz 3-ph, (UL/CSA)
Special purpose rating of refrigeration control (CSA only)420 A, LRA 600 V 60 Hz 3phase; (CSA); 90 A, FLA 480 V 60 Hz 3phase; (CSA); 70 A, FLA 600 V 60 Hz 3phase; (CSA); 540 A, LRA 480 V 60 Hz 3phase; (CSA)
Special purpose rating of resistance air heating100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA); 110 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of tungsten incandescent lamps100 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA); 100 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
Special purpose rating of ballast electrical discharge lamps100 A (600V 60Hz 3phase, 347V 60Hz 1phase); 100 A (480V 60Hz 3phase, 277V 60Hz 1phase)
Switching capacity (main contacts, general use)125 A, Maximum motor rating (UL/CSA)
Screw sizeM10, Terminal screw, Main cables; M3.5, Terminal screw, Control circuit cables; 5 mm AF, Hexagon socket-head spanner, Terminal screw, Main cables
Screwdriver size0.8 x 5.5/1 x 6 mm, Terminal screw, Control circuit cables, Standard screwdriver; 2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Stripping length (control circuit cable)10 mm
Stripping length (main cable)15 mm
Terminal capacity (copper band)2 x (6 x 16 x 0.8) mm (Number of segments x width x thickness), Main cables
Terminal capacity (flexible)1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm²
Terminal capacity (solid)2 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 4) mm², Control circuit cables; 1 x (0.75 - 2.5) mm²
Terminal capacity (stranded)2 x (16 - 95) mm², Main cables; 1 x (16 - 120) mm², Main cables
Tightening torque14 Nm, Screw terminals, Main cables; 1.2 Nm, Screw terminals, Control circuit cables
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid/stranded AWG)8 - 3/0, Main cables; 18 - 14, Control circuit cables

Properties

MOQ1

Cross-References

Attached Documents