| Manufacturer part number (MPN) | DILER-31(24V50HZ) |
| EAN / GTIN | 4015080102519 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Package quantity | 5 pcs |
| Eaton catalogue number | 010251 |
| Depth | 52 mm |
| Height | 58 mm |
| Width | 45 mm |
| Weight | 0.17 kg |
| Certifications | CSA Class No.: 3211-03; CSA-C22.2 No. 14-05; IEC/EN 60947-4-1; UL; IEC/EN 60947; CSA File No.: 012528; EN 60947-5-1; VDE 0660; CE; UL Category Control No.: NKCR; UL File No.: E29184; CSA; UL 508 |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 |
| Code number | 31E |
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of auxiliary contacts (change-over contacts) | 0 |
| Number of auxiliary contacts (normally closed contacts) | 1 |
| Number of auxiliary contacts (normally open contacts) | 3 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.4 W |
| Rated operational current for specified heat dissipation (In) | 6 A |
| Static heat dissipation, non-current-dependent Pvs | 1.8 W |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) | 2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series); 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series); 1.5 A at 110 V, DC L/R ≤ 15 ms (with 3 contacts in series); 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series); 10 A |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 3 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Rated operational voltage (Ue) at AC - max | 600 V |
| Safe isolation | 300 V AC, Between coil and auxiliary contacts, According to EN 61140; 300 V AC, Between auxiliary contacts, According to EN 61140 |
| Features | Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module |
| Fitted with | Interlocked opposing contacts |
| Application | Contactor relays |
| Degree of protection | IP20 |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) |
| Mounting method | DIN-rail/screw |
| Mounting position | As required (except vertical with terminals A1/A2 at the bottom) |
| Operating frequency | 9000 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | DILER Mini-contactors |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 10 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 8 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Voltage type | AC |
| Duty factor | 100 % |
| Pick-up voltage | 0.85 - 1.1 V AC x Uc (voltage tolerance - dual frequency coil 50/60 Hz); 0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz) |
| Power consumption, pick-up, 50 Hz | 25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, pick-up, 60 Hz | 25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, sealing, 50 Hz | 1.3 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz; 4.6 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Power consumption, sealing, 60 Hz | 1.3 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 24 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 24 V |
| Switching time (AC operated, make contacts, closing delay) - max | 21 ms |
| Switching time (AC operated, make contacts, closing delay) - min | 14 ms |
| Switching time (AC operated, make contacts, opening delay) - max | 18 ms |
| Switching time (AC operated, make contacts, opening delay) - min | 8 ms |
| Short-circuit protection rating | 10 A fast, 500V, Maximum fuse, Short-circuit rating without welding, Contacts |
| Short-circuit protection rating without welding | 6 A gG/gL, 500 V, Max. Fuse, Contacts |
| Switching capacity (auxiliary contacts, general use) | 10 A, 600 V AC, (UL/CSA); 0.5 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | A600, AC operated (UL/CSA); P300, DC operated (UL/CSA) |
| Screw size | M3.5, Terminal screw |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
| Stripping length (main cable) | 8 mm |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm²; 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 1 x (18 - 14); 2 x (18 - 14); 18 - 14 |
| Tightening torque | 1.2 Nm, Screw terminals |