| Manufacturer part number (MPN) | DILM32-XTED11-10(RAC240) |
| EAN / GTIN | 4015081048038 |
| Sales unit | pcs |
| Eaton catalogue number | 104945 |
| Depth | 86 mm |
| Height | 38 mm |
| Width | 45 mm |
| Weight | 0.073 kg |
| Certifications | VDE 0660; IEC/EN 60947-4-1; DIN EN 61812; IEC/EN 60947; UL File No.: E29184; CE; CSA; UL Category Control No.: NKCR; CSA File No.: 012528; CSA Class No.: 3211-03; CSA-C22.2 No. 14-05; UL; UL 508 |
| Catalog Notes | Cannot be combined with top mounting auxiliary contacts |
| Mounting position | As required (except suspended) |
| Shock resistance | 6 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 6 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Ambient operating temperature - max | 60 °F |
| Ambient storage temperature - max | 80 °F |
| Ambient operating temperature - min | -25 °F |
| Ambient operating temperature (enclosed) - max | 40 °F |
| Ambient operating temperature (enclosed) - min | 25 °F |
| Ambient storage temperature - min | 40 °F |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78 |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 4 A |
| Fitted with | Suppressor circuits |
| Operating mode | Electronic |
| Switch function type | Time-delay dropped out |
| Degree of protection | IP20 |
| Delay time | 50 ms, On-delayed; 200 ms, Off-delayed |
| Lifespan, mechanical | 3,000,000 Operations (DC operated); 3,000,000 Operations (AC operated) |
| Operating frequency | 360 mechanical Operations/h; 3600 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Product category | Accessories |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Recovery time | 70 ms (after 100 % time delay) |
| Repetition accuracy | < 5 % (deviation) |
| Used with | DILMP20; DILMP32-45; DILA; DILM7-32 |
| Duty factor | 100 % |
| Pick-up voltage | 0.7 - 1.2 V DC x Uc; 0.85 - 1.1 V AC x Uc |
| Power consumption (sealing) at DC | 1.8 W |
| Power consumption, sealing, 50 Hz | 2 VA, Coil in a cold state and 1.0 x Us |
| Power consumption, sealing, 60 Hz | 2 VA, Coil in a cold state and 1.0 x Us |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 240 V |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 100 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 240 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 100 V |
| Safe isolation | 250 V AC, Between auxiliary contacts, According to EN 61140; 250 V AC, Between coil and auxiliary contacts, According to EN 61140 |
| Short-circuit current rating (basic rating) | 125 A, max. Fuse, SCCR (UL/CSA); 125 A, max. CB, SCCR (UL/CSA); 5 kA, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 480 V) | 10/65 kA, CB, SCCR (UL/CSA); 10/100 kA, Fuse, SCCR (UL/CSA); 125/70 A, Class J, max. Fuse, SCCR (UL/CSA); 50/32 A, max. CB, SCCR (UL/CSA) |
| Short-circuit current rating (high fault at 600 V) | 10/100 kA, Fuse, SCCR (UL/CSA); 10/22 kA, CB, SCCR (UL/CSA); 50/32 A, max. CB, SCCR (UL/CSA); 125/125 A, Class J, max. Fuse, SCCR (UL/CSA) |
| Short-circuit protection rating | Max. 4 A gG/gL, fuse, without welding, Auxiliary and control circuits |
| Switching capacity (auxiliary contacts, general use) | 5 A, 24 V DC, (UL/CSA); 5 A, 240 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | B300, AC operated (UL/CSA); R300, DC operated (UL/CSA) |
| Screw size | M3.5, Terminal screw, Control circuit cables |
| Screwdriver size | 2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
| Terminal capacity (solid) | 2 x (0.75 - 1.5) mm²; 1 x (0.75 - 2.5) mm² |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Switching function | Time-delay dropped out |
| Setting time | 0.5–10 s |
| Number of contacts as normally open contact | 1 |
| Number of contacts as normally closed contact | 1 |
| Operating principle | Electronic |
| Country of origin | Germany |