cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Time Module DILM32-XTED11-10(RAC240)

Eaton · Ireland · eaton.com
Part Number
DILM32-XTED11-10(RAC240)  ·  HS 8538.90
Time Module DILM32-XTED11-10(RAC240)

Eaton DILM32-XTED11-10(RAC240) DILM32-XTED11-10(RAC240).

Technical Specifications

Manufacturer part number (MPN)DILM32-XTED11-10(RAC240)
EAN / GTIN4015081048038
Sales unitpcs
Eaton catalogue number104945
Depth86 mm
Height38 mm
Width45 mm
Weight0.073 kg
CertificationsVDE 0660; IEC/EN 60947-4-1; DIN EN 61812; IEC/EN 60947; UL File No.: E29184; CE; CSA; UL Category Control No.: NKCR; CSA File No.: 012528; CSA Class No.: 3211-03; CSA-C22.2 No. 14-05; UL; UL 508
Catalog NotesCannot be combined with top mounting auxiliary contacts
Mounting positionAs required (except suspended)
Shock resistance6 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms; 6 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Ambient operating temperature - max60 °F
Ambient storage temperature - max80 °F
Ambient operating temperature - min-25 °F
Ambient operating temperature (enclosed) - max40 °F
Ambient operating temperature (enclosed) - min25 °F
Ambient storage temperature - min40 °F
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Number of contacts (change-over contacts)0
Number of contacts (normally closed contacts)1
Number of contacts (normally open contacts)1
Conventional thermal current Ith of auxiliary contacts (1-pole, open)4 A
Fitted withSuppressor circuits
Operating modeElectronic
Switch function typeTime-delay dropped out
Degree of protectionIP20
Delay time50 ms, On-delayed; 200 ms, Off-delayed
Lifespan, mechanical3,000,000 Operations (DC operated); 3,000,000 Operations (AC operated)
Operating frequency360 mechanical Operations/h; 3600 Operations/h
Overvoltage categoryIII
Pollution degree3
Product categoryAccessories
ProtectionFinger and back-of-hand proof, Protection against direct contact when actuated from front
Rated impulse withstand voltage (Uimp)4000 V AC
Recovery time70 ms (after 100 % time delay)
Repetition accuracy< 5 % (deviation)
Used withDILMP20; DILMP32-45; DILA; DILM7-32
Duty factor100 %
Pick-up voltage0.7 - 1.2 V DC x Uc; 0.85 - 1.1 V AC x Uc
Power consumption (sealing) at DC1.8 W
Power consumption, sealing, 50 Hz2 VA, Coil in a cold state and 1.0 x Us
Power consumption, sealing, 60 Hz2 VA, Coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at AC, 50 Hz - max240 V
Rated control supply voltage (Us) at AC, 50 Hz - min100 V
Rated control supply voltage (Us) at AC, 60 Hz - max240 V
Rated control supply voltage (Us) at AC, 60 Hz - min100 V
Safe isolation250 V AC, Between auxiliary contacts, According to EN 61140; 250 V AC, Between coil and auxiliary contacts, According to EN 61140
Short-circuit current rating (basic rating)125 A, max. Fuse, SCCR (UL/CSA); 125 A, max. CB, SCCR (UL/CSA); 5 kA, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)10/65 kA, CB, SCCR (UL/CSA); 10/100 kA, Fuse, SCCR (UL/CSA); 125/70 A, Class J, max. Fuse, SCCR (UL/CSA); 50/32 A, max. CB, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)10/100 kA, Fuse, SCCR (UL/CSA); 10/22 kA, CB, SCCR (UL/CSA); 50/32 A, max. CB, SCCR (UL/CSA); 125/125 A, Class J, max. Fuse, SCCR (UL/CSA)
Short-circuit protection ratingMax. 4 A gG/gL, fuse, without welding, Auxiliary and control circuits
Switching capacity (auxiliary contacts, general use)5 A, 24 V DC, (UL/CSA); 5 A, 240 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)B300, AC operated (UL/CSA); R300, DC operated (UL/CSA)
Screw sizeM3.5, Terminal screw, Control circuit cables
Screwdriver size2, Terminal screw, Pozidriv screwdriver; 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Terminal capacity (solid)2 x (0.75 - 1.5) mm²; 1 x (0.75 - 2.5) mm²
Terminal capacity (flexible with ferrule)1 x (0.75 - 1.5) mm²; 2 x (0.75 - 1.5) mm²
Terminal capacity (solid/stranded AWG)18 - 14
Switching functionTime-delay dropped out
Setting time0.5–10 s
Number of contacts as normally open contact1
Number of contacts as normally closed contact1
Operating principleElectronic
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents